Danfoss Termix Compact 28 VVX-FI Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss Termix Compact 28 VVX-FI Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
TermixCompact28VVX-FI
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotesgeneral............................................4
4.0Mounting........................................................5
4.1MountingtheCompactstation..................................5
4.2Start-up..............................................................14
4.3Electricalconnections.............................................15
5.0Design.............................................................16
5.1Design...............................................................16
5.2Schematicdiagram................................................17
6.0Controls..........................................................18
6.1Heatingcircuit......................................................18
6.2DHWtemperaturecontrol........................................21
6.3Other.................................................................22
6.4Maintenance........................................................24
7.0Troubleshooting..............................................25
7.1Troubleshootingingeneral......................................25
7.2TroubleshootingDHW............................................25
7.3TroubleshootingHE...............................................26
7.4Disposal.............................................................27
8.0Declaration......................................................31
8.1Declarationofconformity........................................31
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
1
OperatingGuideTermixCompact28VVX-FI
2
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
2.0Functionaldescription
Districtheatingsubstationforindirectheatingand
instantaneousdomestichotwater.
Spaceheatinganddomestichotwater(DHW)
TheTermixCompact28VVX-FIisacompleteunitforindirect
spaceheatinganddomestichotwaterfordistrictheatinginlarge
buildingssuchassportscentres,schools,blocksofatsetc.
Itcanbeusedforconnectiontoindirectdistrictheatinginplaces
wherethedistrictheatingplantrequiresahydraulicbreak.Itis
alsosuitableforconversiontodistrictheatingwhenthesecondary
heatingsystemisunsuitabletobeingconnectedtodirectdistrict
heatingorwhenaparticularlyeffectivesecurityagainstleakagein
theheatingsystemisrequired.
Efcientheatexchanger
Thesubstationisttedwithanefcientplateheatexchanger,
whichensuresthemostfavourableheatextractionandachieves
optimumcomfortandoperatingeconomy.
Electronicregulation
TheTermixCompact28VVX-FIisbuiltwithaplateheatexchanger
forinstantaneousdomestichotwaterproductionandheat
exchangerforspaceheating.Eachcircuitisalsosuppliedwithits
ownowcontroller.
Thisallowsthegreatestdegreeofindividualcontrol,thus
preventingoscillationatdifferentloads.Theelectroniccontrolleris
factorypre-set.Electricalcomponentsarepre-wired,andtheunitis
equippedwithaplugfor230Va.c.
Itisrecommendedthatbalancingvalvesareinstalledinthe
building’srisersintheheatsupplyandontheheatingsystems
returnlineimmediatelybeforetheunit.
Minimalheatloss
Completeinsulationoftheunitensuresminimalheatloss.
Easyinstallation
Theunitconsistsoftwomodules,oneforspaceheatingandone
fordomestichotwaterproduction,whichiseasilyassembled
intoonesinglemodule.Thismodulardesignmakesworkduring
installationsignicantlyeasier,astheweightissplitbetweentwo
modulesduringhandling.
Flexiblesolution
Pipeconnectioncanbemadefromeitherthetoporbottom,which
makesthissolutionhighlyexible.Atthesametime,bothspace
andtimearesavedwheninstalling.
Reliableandeasytoinstall
TermixCompact28VVX-FIisoperationallyreliable.Aquality
productmanufacturedinDenmarkwhichiseasytoinstalland
quicklycommissioned.
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
3
OperatingGuideTermixCompact28VVX-FI
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
110°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
4.0Mounting
4.1MountingtheCompactstation
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
5.Domestichotwater(DHW)
6.Domesticcoldwater(DCW)
7.Hotwatercirculation(HWC)
Connectionsizes:
DH+HE:
G1”(int.thread)
DCW+DHW:
G1”(int.thread)
HWC:
G¾”(int.thread)
Dimensions(mm):
Withinsulation:
H890xW1460xD400
Weight(approx.):95kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
5
OperatingGuideTermixCompact28VVX-FI
Removethefront.
Removetheotherblocksandthewhitepolystyrene.
Attachthemountingrailtothewall.
Liftthestationsheatingsection.
6
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
Mountthestationasfartotheleftontherailaspossible.
Liftthestationsinstantaneousdomestichotwaterpart.
Mounttheinstantaneousdomestichotwaterpartonthe
right-handsideofthettings.
Pushthetwopartstogether.Thetwomountingplatesmustclick
togetherintheoverlap.
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
7
OperatingGuideTermixCompact28VVX-FI
Attachthestationtothewallintheholesonthemountingplate.
Assemblethepowerconnectoronthehotwaterpartofthestation.
Forproperfunctionality,connectorsmustbepairedbycolour.
Installthesafetyvalve.
Installtheballvalves.
MountblockA(CifitistheMagnapump)ontheleft-handsideof
thepump.AttachblockEtoblockA/C,andattachittothepipe
abovethepumpbyclickingitinplace.
8
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
MountblockB(DifitistheMagnapump)ontheright-handsideof
thepump.
MountblockF(GforVM2valve).Theblockishingedandcanbe
drawnaroundthevalve.AttachtheblocktoblockB/DandE.
MountblockL.Theblockishingedandcanbepulledaroundthe
UPM3pump.
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
9
OperatingGuideTermixCompact28VVX-FI
MountblockM.Theblockishingedandcanbedrawnaroundthe
valve.AttachtheblocktoblockL.
Mountthesmallfrontcover.
Mountthelargefrontcover.
10
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
4.1.1InstallingtheCompactstation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
11
OperatingGuideTermixCompact28VVX-FI
4.1.2Pipeconnectionsup
Removethetopblock.
Removethepipeplugsatthetopofthestation.
RemoveU-clamps.
Removepipes.
Anglesandteesareturnedsothatpipescanbeinstalledfrom
above.
12
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
Installthepipes.Districtheatingsupplypipestobeinterchanged.
FitU-clamps.
Fitthepipeplugsatthebottomofthestation.
Fitthetopblock.
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
13
OperatingGuideTermixCompact28VVX-FI
4.2Start-up
Start-up,Indirectheating
Filling:
1:Firstll
Whencarryingoutrstll,theheatexchangermustbeslowlylled
withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This
instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tollthe
system,theballvalvemustrstbeclosed,theplugremovedand
asupplyhoseconnected.Onre-openingtheballvalve,system
llcancommence.
4:Pre-pressure
Whenllingthesystemwithwater,thepressuregaugeshouldbe
observedclosely.Theexpansionvesselissuppliedpre-pressurised
to0.5bar.Thepre-pressurerequiredateachsubstationwill
dependonsystemhead(thedistancebetweenthelowestand
highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure
approximately1-2barhigherthanthepre-pressuresetting.The
ballvalveisthenclosed,thehoseremovedandtheplugputback
in.
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Height(m)Pressure(bar)
050,5
5101,0
1015
1,5
15202,0
14
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
15
OperatingGuideTermixCompact28VVX-FI
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
10
Circulatorpump
26
Pressuregauge,HE
B
Heatexchanger,DHW
11
Domestichotwaterpump
27AActuator,HE
F
Electroniccontroller
14
Sensorpocket,energymeter
27BActuator,DHW
4
Safetyvalve,HE
20
Filling/drainvalve
48
Airvent,manual
9
Strainer
25
Pressuregaugewithballvalve
16
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
5.2Schematicdiagram
DH
Supply
HE
Supply
DH
Return
HE
Return
DHW
DCW
HWC
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
10
Circulatorpump
24
Deliveredloosewithunit
B
Heatexchanger,DHW
11
Domestichotwaterpump
25
Pressuregaugewithballvalve
F
Electroniccontroller
14
Sensorpocket,energymeter
26
Pressuregauge
X
Plugconnections
16
Outdoorsensor
27
Actuator
1
Ballvalve
18
Thermometer
30
Flowcontrollerwithintegratedcontrolvalve
2
Singlecheckvalve
19
Surfacesensor
40
Immersionsensor
4
Safetyvalve
20
Filling/drainvalve
48
Airvent,manual
9
Strainer
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
DHW:
Domestichotwater
HWC:
Hotwatercirculation
DCW:
Domesticcoldwater
5.2.1Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
110°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
17
OperatingGuideTermixCompact28VVX-FI
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2HEtemperaturecontrol
TheHEowtemperatureintheheatingcircuitiscontrolledbythe
HEtemperaturecontroller.
6.1.3Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.owisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
18
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
OperatingGuideTermixCompact28VVX-FI
6.1.4Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
6.1.5Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
6.1.6Outsidetemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
DanfossDistrictEnergy
VI.LZ.K1.02/LUK42463
DEN-GT
19
OperatingGuideTermixCompact28VVX-FI
6.1.7Circulatorpump
TheUPML,UPMXLcirculatorpumpsaredesignedforcirculating
liquidsinheatingsystemswithvariableows,internallycontrolled
withthreeproportionalpressurecurvesandthreeconstant
pressure/powercurvestobeselectedviauserinterface.
EuP2015Ready.
TheMAGNA3circulatorpumpsaredesignedforcirculatingliquids
inheatingsystemswithvariableowswhereyouwanttooptimise
thesettingofthepumpdutypoint,thusreducingenergycosts.
EuP2015Ready.
6.1.8GrundfosUPML/UPMXLinstructions
PP=Proportionalpressure(fastash)
CP=Constantpressure(slowash)
20
DEN-GT
VI.LZ.K1.02/LUK42463
DanfossDistrictEnergy
/