Danfoss Termix VVX C20 Operating instructions

Type
Operating instructions

Danfoss Termix VVX C20 is a compact substation for heating and hot water which offers an all-in-one solution for your home. It's designed for wall mounting and comes with many features that make it easy to use and maintain.

The Termix VVX C20 has a prefabricated district heating circuit with a differential pressure controller, thermometers, and ball valves. The heating circuit includes a plate heat exchanger, safety valve, pressure gauge, thermometers, ball valves, drain valve, air valve, expansion vessel, and circulation pump. Depending on your needs, different heat exchangers can be used.

For domestic hot water, the Termix VVX C20 uses a plate heat exchanger that provides efficient heat extraction with high output. The thermostatic control valve automatically maintains the comfort temperature of the hot water, even when the heating system is in reduced operation or if the district heating plant changes operating parameters.

Danfoss Termix VVX C20 is a compact substation for heating and hot water which offers an all-in-one solution for your home. It's designed for wall mounting and comes with many features that make it easy to use and maintain.

The Termix VVX C20 has a prefabricated district heating circuit with a differential pressure controller, thermometers, and ball valves. The heating circuit includes a plate heat exchanger, safety valve, pressure gauge, thermometers, ball valves, drain valve, air valve, expansion vessel, and circulation pump. Depending on your needs, different heat exchangers can be used.

For domestic hot water, the Termix VVX C20 uses a plate heat exchanger that provides efficient heat extraction with high output. The thermostatic control valve automatically maintains the comfort temperature of the hot water, even when the heating system is in reduced operation or if the district heating plant changes operating parameters.

InstallationGuide
TermixVVXCompact20
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.2Start-up..............................................................6
4.3Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
6.0Controls..........................................................10
6.1Heatingcircuit......................................................10
6.2DHWtemperaturecontrol........................................13
6.3Other.................................................................14
6.4Maintenance........................................................16
7.0Troubleshooting..............................................17
7.1Troubleshootingingeneral......................................17
7.2TroubleshootingDHW............................................17
7.3TroubleshootingHE...............................................18
7.4Disposal.............................................................19
8.0Declaration......................................................23
8.1Declarationofconformity........................................23
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
1
InstallationGuideTermixVVXCompact20
2.0Functionaldescription
Districtheatingsubstationforindirectheatingand
instantaneousdomestichotwaterwiththermostaticor
electroniccontrols.Designedforwall-mounting.
Application
TheTermixVVXCompact20substationisathecompletesolution
forhotwaterandspaceheatingwithoptimalsafety,efcient
energytransfer,service-friendlyconstructionandacompact
design.Thesubstationisapplicable,ifaheatexchangeris
requiredoronaconversiontodistrictheating,wheretheexisting
equipmentisunsuitablefordirectconnection.
Districtheating(DH)
Thedistrictheatingcircuitisprefabricatedwithadifferential
pressurecontrolleraswellasthermometersandballvalves.
Heating(HE)
Theheatingcircuitconsistsofaplateheatexchanger,safety
valve,manometer,thermometers,ballvalves,drainvalve,air
valve,expansionvesselandcirculationpump.Theheating
temperaturecanbecontrolledthermostaticallyorbyanelectronic
controllerwithanoutdoortemperaturesensor.Dependingonthe
application,differentheatexchangerscanbedimensioned.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerandthe
temperatureisregulatedwiththermostaticorelectroniccontrols.
TheefcientplateheatexchangerforDHWoffersexceptionally
goodheatextractionwithhighoutput.Noreadjustmentofthe
DHWtemperatureisrequiredafterinstallationandinitialsettingof
thecontrols.Thethermostaticcontrolvalveautomaticallyretains
thecomforttemperatureofthehotwater,evenwhentheheating
systemisinreducedoperationduringsummerorifthedistrict
heatingplantchangesoperatingparametersbetweensummerand
winter.Thiseitherbyloweringorincreasingtheowtemperature
ofthedistrictheatingwaterand/ortheoperatingpressureinthe
network.
2
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
3
InstallationGuideTermixVVXCompact20
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Heating(HE)supply
4.Heating(HE)return
5.Domestichotwater(DHW)
6.Domesticcoldwater(DCW)
7.Hotwatercirculation(HCW)
Connectionsizes:
DH+HE:
G1”(int.thread)
DCW+DHW:
G1”(int.thread)
HCW:
G¾”(int.thread)
Dimensions(mm):
Withoutcover:
H815xW505xD400
Withcover:
H815xW540xD430
Weight(approx.):30–40kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Thightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
5
InstallationGuideTermixVVXCompact20
4.2Start-up
Start-up,Indirectheating
Filling:
1:Firstll
Whencarryingoutrstll,theheatexchangermustbeslowlylled
withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This
instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tollthe
system,theballvalvemustrstbeclosed,theplugremovedand
asupplyhoseconnected.Onre-openingtheballvalve,system
llcancommence.
4:Pre-pressure
Whenllingthesystemwithwater,thepressuregaugeshouldbe
observedclosely.Theexpansionvesselissuppliedpre-pressurised
to0.5bar.Thepre-pressurerequiredateachsubstationwill
dependonsystemhead(thedistancebetweenthelowestand
highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure
approximately1-2barhigherthanthepre-pressuresetting.The
ballvalveisthenclosed,thehoseremovedandtheplugputback
in.
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderoorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemll.
Height(m)Pressure(bar)
050,5
5101,0
1015
1,5
15202,0
6
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
Underoorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderoorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderoorheatingcontroller.Thepumpmustbestoppedif
allunderoorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
7
InstallationGuideTermixVVXCompact20
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
A
Heatexchanger,HE
7
Thermostaticvalve
27
Actuator,HE
B
Heatexchanger,DHW
10
Circulationpump
31
Differentialpressurecontroller
1A
Summervalve
11
Domestichotwaterpump
48
Airvent,manual
4
Safetyvalve
20
Filling/drainvalve
26
Pressuregauge
8
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
5.2Schematicdiagram
DH
Supply
HE
Supply
DH
Return
HE
Return
DHW
DCW
HWC
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
A
Heatexchanger,HE
9
Strainer
23
Ballvalve
B
Heatexchanger,DHW
10
Circulationpump
24
Deliveredloosewithunit
F
Electroniccontroller
11
Domestichotwaterpump
26
Pressuregauge
1
Ballvalve
16
Outdoorsensor
27
Actuator
2
Singlecheckvalve
18
Thermometer
29
2-waymotorizedvalve
4
Safetyvalve
19
Surfacesensor
31
Differentialpressurecontroller
7
Thermostaticvalve
20
Filling/drainvalve
48
Airvent,manual
DHW:DomesticHotWater
DCW:
DomesticColdWater
HWC:
HotWaterCirculation
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
9
InstallationGuideTermixVVXCompact20
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsouttheuctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2RAVKcontroller
HEtemperaturecontrol
TheHEowtemperatureintheheatingcircuitiscontrolledbythe
HEtemperaturecontroller.
Thermostaticcontrol
ThetemperatureoftheHEowlineisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
RAVKcontroller(25-65°C).Thetemperaturesettingisasfollows:
1=25°C
2=35°C
3=45°C
4=55°C
5=65°C
Thevaluesareintendedasaguide.
10
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
6.1.3Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.owisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
6.1.4Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
6.1.5Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
11
InstallationGuideTermixVVXCompact20
6.1.6Outdoortemperaturesensor(ESMT)
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
6.1.7Circulationpump
ALPHA2pumpshavebothvariablespeedpressurecontrolled
operation,andstandardselectablethreespeedoperation.
TheuniqueAUTOADAPTfeatureallowsthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
ALPHA2Lpumpshavebothvariablespeedpressurecontrolled
operation,andstandardselectablethreespeedoperation.The
variablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
UPSpumpsareacompleterangeofcirculatorpumpswith3
speeds.
EnergylabellinguptoclassB
12
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
6.1.8HEpressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.
6.2DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.2.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows:
1=20°C
2=35°C
3=50°C
4=60°C
5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto
90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
6.2.2Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.owisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
13
InstallationGuideTermixVVXCompact20
6.2.3Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
6.3Other
6.3.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
6.3.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
14
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
6.3.3Fittingpiece
Thesubstationisequippedwithattingpieceforenergymeter.
Assemblyofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater
onthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththeenergymeter.Do
notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand
tightenallthreadedconnections.
Sensorpocket,energymeter
Thesensorsoftheenergymeterismountedinthesensorpockets.
6.3.4Domestichotwaterpump
Important!
Itisnecessarytomountadomestichotwatercirculationpumpon
thewaterheatertoavoidregulationproblems.
Thecirculationpumpcannotbeswitchedoff,sincethiswillresult
inregulationproblems.(noowatthesensor).
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
15
InstallationGuideTermixVVXCompact20
6.4Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
16
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
17
InstallationGuideTermixVVXCompact20
7.3TroubleshootingHE
ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinDHorHEcircuit
(radiatorcircuit).
Cleangate/strainer(s).
ThelterintheenergymeteronDHcircuit
clogged.
Cleanthelter(afterconsultingtheDH
plantoperator).
Defectiveorwronglyadjusteddifferential
pressurecontroller.
Checktheoperationofthedifferential
pressurecontrollercleanthevalveseatif
required.
Sensordefectiveorpossiblydirtinthe
valvehousing.
Checktheoperationofthethermostat
cleanthevalveseatifrequired.
Automaticcontrols,ifany,wronglysetor
defective-possiblypowerfailure.
Checkifthesettingofthecontroller
iscorrectseeseparateinstructions.
Checkthepowersupply.Temporary
settingofmotortomanual”controlsee
instructionsonautomaticcontrols.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
thatitturns.Checkifthereisairtrappedin
thepumphousingseepumpmanual.
Thepumpissetattoolowspeedof
rotation.
Setthepumpathigherspeedofrotation.
Pressuredropthepressuredropon
theradiatorcircuitshowslowerthan
recommendedoperatingpressure.
Fillwateronthesystemandcheckthe
functioningofthepressureexpansion
vesselifrequired.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperature
adjustedtoolow.
Adjustaccordingtoinstructions.
Defectiveradiatorvalves.
Checkreplace.
Unevenheatdistributioninbuilding
becauseofincorrectlysetbalancingvalves,
orbecausetherearenobalancingvalves.
Adjust/installbalancingvalves.
Diameterofpipetosubstationtoosmallor
branchpipetoolong.
Checkpipedimensions.
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
DHsupplytemperaturetoohigh.
Wrongsettingofthermostatorof
automaticcontrols,ifany.
Adjustautomaticcontrols,see
instructionsforautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callautomaticcontrolsmanufactureror
replacetheregulator.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
DHsupplytemperaturetoolow.
Wrongsettingofautomaticcontrols,ifany.
Adjustautomaticcontrolsseeinstructions
forautomaticcontrols.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callinautomaticcontrolsmanufactureror
replacecontroller.
Defectivesensoronself-actingthermostat.
Replacethermostatorsensoronly.
Wrongplacement/ttingofoutdoor
temperaturesensor.
Adjustlocationofoutdoortemperature
sensor.
Strainerclogged.Cleangate/strainer.
18
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
InstallationGuideTermixVVXCompact20
ToohighDHreturntemperature.
Toosmallheatingsurface/toosmall
radiatorscomparedtothetotalheating
requirementofthebuilding.
Increasetotalheatingsurface.
Poorutilizationofexistingheatingsurface.
Defectivesensoronself-actingthermostat.
Makesuretheheatisdistributedevenly
acrossthefullheatingsurfaceopenall
radiatorsandkeeptheradiatorsinthe
systemfromheatingupatthebottom.It
isextremelyimportanttokeepthesupply
temperaturetotheradiatorsaslowas
possible,whilemaintainingareasonable
levelofcomfort.
Thesystemissinglepipeloop.
Thesystemshouldfeatureelectronic
controlsaswellasreturnsensors.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Ventthesystem.
Defectiveorincorrectlysetradiator
valve(s).Singlepipeloopsystemsrequire
specialone-piperadiatorvalves.
Checkset/replace.
Dirtinthemotorizedvalveorinthe
differentialpressurecontroller.
Checkcleanout.
Defectivemotorizedvalve,sensoror
automaticcontroller.
Checkreplace.
Electroniccontrollernotadjustedcorrectly.Adjustaccordingtoinstructions.
Noiseinsystem.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Heatloadtoohigh.
Defectivemotorizedvalve,sensoror
electroniccontroller.
Checkreplace.
7.4Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossDistrictEnergy
VI.CW.R2.02/LUK41400
DEN-GT
19
InstallationGuideTermixVVXCompact20
20
DEN-GT
VI.CW.R2.02/LUK41400
DanfossDistrictEnergy
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Danfoss Termix VVX C20 Operating instructions

Type
Operating instructions

Danfoss Termix VVX C20 is a compact substation for heating and hot water which offers an all-in-one solution for your home. It's designed for wall mounting and comes with many features that make it easy to use and maintain.

The Termix VVX C20 has a prefabricated district heating circuit with a differential pressure controller, thermometers, and ball valves. The heating circuit includes a plate heat exchanger, safety valve, pressure gauge, thermometers, ball valves, drain valve, air valve, expansion vessel, and circulation pump. Depending on your needs, different heat exchangers can be used.

For domestic hot water, the Termix VVX C20 uses a plate heat exchanger that provides efficient heat extraction with high output. The thermostatic control valve automatically maintains the comfort temperature of the hot water, even when the heating system is in reduced operation or if the district heating plant changes operating parameters.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI