Festo IIFB9-02 Series User manual

Type
User manual

This manual is also suitable for

Author: Heinz Hohner
Editors: Michael Holder, H.-J. Drung
Translation: Douglas Smith
Layout: Festo, Dept. PV-IDM
Type setting: DUCOM
Edition 9706
© (Festo AG & Co., D-73726 Esslingen, 1997)
The copying, distribution and utilization of this
document as well as the communication of its
contents to others without expressed authoriza-
tion is prohibited. Offenders will be held liable for
the payment of damages. All rights reserved, in
particular the right to carry out patent, utility
model or ornamental design registrations.
printed on 100% receycling paper
VIFB9 - 02
9706 I
Order no.: 151767
Title: MANUAL
Designation: P.BE-VIFB9-02-GB
VIFB9 - 02
II
9609
Contents
Kapitel 1 USER INSTRUCTIONS . . . . . . . . . . . . . . . . . 1-1
Kapitel 2 SYSTEM STRUCTURE . . . . . . . . . . . . . . . . . 2-1
Kapitel 3 TECHNICAL DESCRIPTION . . . . . . . . . . . . . 3-1
Kapitel 4 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1 FITTING THE VALVE TERMINAL/
VALVE SENSOR TERMINAL . . . . . . . . . 4-3
4.2 INSTALLING THE PNEUMATIC
COMPONENTS . . . . . . . . . . . . . . . . . . . . 4-5
4.3 INSTALLING THE ELECTRONIC
COMPONENTS . . . . . . . . . . . . . . . . . . . 4-16
Kapitel 5 COMMISSIONING. . . . . . . . . . . . . . . . . . . . . . 5-1
5.1 COMMISSIONING . . . . . . . . . . . . . . . . . . 5-3
5.2 SIEMENS . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5.3 GENERAL DP-MASTER . . . . . . . . . . . 5-36
Kapitel 6 DIAGNOSTICS AND ERROR TREATMENT. 6-1
6.1 SUMMARY OF DIAGNOSTIC
POSSIBILITIES . . . . . . . . . . . . . . . . . . . . 6-6
6.2 LED DISPLAYS . . . . . . . . . . . . . . . . . . . . 6-6
6.3 TESTING THE VALVES. . . . . . . . . . . . . 6-10
6.4 STATUS BITS . . . . . . . . . . . . . . . . . . . . 6-12
6.5 DIAGNOSIS VIA PROFIBUS-DP
(DP-STANDARD) . . . . . . . . . . . . . . . . . 6-15
6.6 DIAGNOSIS VIA SINEC L2-DP
(DP-SIEMENS) . . . . . . . . . . . . . . . . . . . 6-20
6.7 DIAGNOSIS VIA PROFIBUS-DP
(GENERAL DP-MASTER) . . . . . . . . . . . 6-23
6.8 ERROR TREATMENT . . . . . . . . . . . . . 6-27
Anhang A INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Contents
VIFB9 - 02
9609 III
VIFB9 - 02
IV
9609
1. USER INSTRUCTIONS
VIFB9 - 02 1. User instructions
9609 1-1
Contents
IMPORTANT USER INSTRUCTIONS . . . . . . 1-3
VIFB9 - 02 1. User instructions
1-2
9609
IMPORTANT USER INSTRUCTIONS
This manual contains instructions on the possible
dangers which can occur with the valve termi-
nals/valve sensor terminals.
A distinction is made between the following in-
structions:
WARNING
This means that personal injury or damage to
property may occur if these instructions are
not observed.
CAUTION
This means that damage to property may
occur if these instructions are not observed.
PLEASE NOTE
This means that this instruction must also be
observed.
VIFB9 - 02 1. User instructions
9609 1-3
This documentation describes the following
products:
PLEASE NOTE
This electronics manual describes node FB9
as from software status 31.5.95 and later.
The enclosed diskette contains device master
files and type files. Explanations can be found
on the file "Readme".
Product Design
Field bus
connection
Valve size Number of
valve locations
Valve terminal
type 02
VIFB-02-..
PROFIBUS-DP
Siemens
Sinec L2-DP
1
8
"
or
1
4
"
4 or
6 or
8 or
10 or
12 or
14 or
16
Valve sensor terminal
type 02
IFB-02-...
Fig. 1/1: Designs of valve terminal/valve sensor terminal
VIFB9 - 02 1. User instructions
1-4
9609
This manual describes the operation of the Festo
valve terminal/valve sensor terminal type 02 in
conjunction with the field bus protocols Siemens
SINEC L2-DP and PROFIBUS-DP as per EN
50170 (DIN 19245).
PLEASE NOTE
In conjunction with a Siemens SIMATIC S5,
both the SINEC L2-DP and the PROFIBUS-
DP protocols can be used; in conjunction with
other PLCs, PCs, industrial PCs, the
PROFIBUS-DP protocol must be set.
In this manual, the protocol variants are desig-
nated as DP-standard for PROFIBUS-DP and
DP-Siemens for the SINEC L2-DP.
The valve terminal does not contain the
PROFIBUS-FMS protocol (no combi-slave
functions).
VIFB9 - 02 1. User instructions
9609 1-5
VIFB9 - 02 1. User instructions
1-6
9609
2. SYSTEM STRUCTURE
VIFB9 - 02 2. System structure
9609 2-1
Contents
SYSTEM STRUCTURE. . . . . . . . . . . . . . . . . . 2-3
Valve terminal . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Valve sensor terminal . . . . . . . . . . . . . . . . . . . 2-4
Valve terminal/valve sensor terminal in
the control system . . . . . . . . . . . . . . . . . . . . . . 2-5
VIFB9 - 02 2. System structure
2-2
9609
SYSTEM STRUCTURE
Valve terminal
Festo offers a solution to automation problems at
the machine level in the form of the valve termi-
nal. Solenoid valves, double solenoid valves etc.
are already fitted onto a sub-base and have
already been tested. Valve terminals with from
4...16 valve locations are available for the auto-
mation process.
The valve terminal with field bus connection of-
fers the following advantages:
decentralized preprocessing
relieves the controller (PLC)
less wiring due to two-core cables
clarity in system structure due to separation
of controller and machine
valves already fitted
valve solenoid coils already wired
central air supply
central exhaust
device already tested
Valve terminal Circuitry
Field bus connection
via two-core cable
(twisted, screened)
Type 02
Fig. 2/1: Valve terminal type 02
VIFB9 - 02 2. System structure
9609 2-3
A field bus system also offers the following ad-
vantages:
a reduction in the number of output
modules in the controller
economic data transfer over long distances
high baud rate
a large number of slaves can be linked into
the network
error diagnosis is made easier
Valve sensor terminal
Complex automation tasks require the use of
sensors for which Festo offers the valve sensor
terminal. Solenoid valves, double solenoid valves
etc. are fitted onto a sub-base and have already
been tested; two sensors per valve can be con-
nected on site. Valve sensor terminals with from
4 ... 14 valves are available for the automation
process.
The valve sensor terminal includes all the advan-
tages of the valve terminal. It also offers:
two inputs per valve location, e.g. for sensors
two additional inputs
two additional outputs, e.g. for electric actua-
tors, displays etc..
Valve sensor terminal Circuitry
Field bus connection
via two-core cable
(twisted, screened)
Fig. 2/2: Valve sensor terminal type 02
Type 02
VIFB9 - 02 2. System structure
2-4
9609
Valve terminal/valve sensor terminal in the
control system
The valve terminals can be connected to the
control systems of various manufacturers. This
manual deals with configuration and addressing
instructions.
The following diagram represents an excerpt of
available master modules for the PROFIBUS-DP:
Controller
manufacturer
Controller (PLC) Field bus
module
Filed bus
Siemens SIMATIC
S5 series
S7 series
various SINEC L2-DP
Bosch CL300, 400, 500
PC600
BM DESI-DP COMNET-DP
Festo SF 50 integrated
PROFIBUS-DP
PC / IPC CP5410 from
Siemens etc.
Allen-Bradley PLC 5 PFBIB
(extract of possible control systems)
Fig. 2/3: Simatic S5 automation systems
VIFB9 - 02 2. System structure
9609 2-5
Fig. 2/4: Simatic S5 automation systems
Further field bus slaves
ET 200U
Industrial PC/
controller
- Simatic S5
- Bosch
- and others
Field bus
DP-Siemens
DP-Standard
Valve terminal
type 02
Valve sensor
terminal
type 02
VIFB9 - 02 2. System structure
2-6
9609
Explanation of the system structure
The field bus module controls the complete ex-
change of information between the field bus
slaves (decentral I/O modules), e.g. the valve
terminal/valve sensor terminals and the proces-
sor modules in the controller.
The field bus slaves are connected via the
PROFIBUS-DP interface on the module. Up to
31 field bus slaves can be connected to the in-
terface (without using repeaters/bus amplifiers).
If repeaters are used, the number of connected
valve terminals/valve sensor terminals can be in-
creased to max. 122.
VIFB9 - 02 2. System structure
9609 2-7
The field bus creates data communication be-
tween the controller and the field bus slaves
(e.g. valve terminal/valve sensor terminal) dis-
tributed throughout the system. Data trans-
mission is made in accordance with standard RS
485. Baud rates up to 1500 kBaud can be set.
The valve terminal as a decentral output mo-
dule processes the signals transmitted and con-
trols the actuators which are connected. The
valve terminal is supplied with current via an ex-
ternal power unit (AC 230V/DC 24V).
The valve sensor terminal as a decentral
input/output module functions like a valve termi-
nal. It also processes up to 30 inputs.
The air controlled by the valve terminal/valve
sensor terminal moves the actuators or is used
for other tasks.
The sensors record information (measured vari-
ables) from the control process and pass this on
to the valve sensor terminal (further process-
ing unit).
VIFB9 - 02 2. System structure
2-8
9609
3. TECHNICAL DESCRIPTION
VIFB9 - 02 3. Technical description
9609 3-1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165

Festo IIFB9-02 Series User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI