Danfoss KE07204 Ramped Valve Driver Installation guide

Type
Installation guide
.
Unit Specification
3500 Annapolis Lane North, Minneapolis, MN 55447
Telephone: (763) 509-2084 Telefax: (763) 559-0108
ISSUE: 1 DATE: May 1993
KE07204
Ramped Valve Driver
GENERAL DESCRIPTION
This device is a ramped valve driver which accepts a setpoint potentiometer input from a control handle and drives a single
coil valve. It is pulse-width modulated and has adjustable acceleration/deceleration ramping. The PWM frequency is selected
by a jumper on the terminal strip. The threshold and full stroke forward outputs are adjustable. It does not have a reverse output.
OUTPUT CHARACTERISTICS
SUPPLY VOLTAGE
24 Vdc
PWM FREQUENCY
50 Hz or 30 Hz
OUTPUT CURRENT
800 mA maximum
FACTORY SETTINGS WITH 26 OHM LOAD
Threshold: 250 mA
Full Stroke 600 mA
DIMENSION AND CONNECTION DIAGRAM
1687
100,08
(3.94)
88,9
(3.50)
5,59 (0.22)
6,35 (0.25)
69,85 (2.75)
113,0 (4.45)
148,59 (5.85)
3,96 DIA (6)
(0.156)
THRESHOLD
FWD
F/S
RAMP
TIME
20,32 
(0.8)
N/C
N/C
POT GND
GND
+24V POWER
OUTPUT - FWD
POT +8V
POT WIPER
N/C
N/C
FOR 50HZ PWM JUMPER TERMINALS TB1-11 AND TB1-12
FOR 30HZ PWM REMOVE JUMPER
1 2 3 4 5 6 7 8 9 10
Dimensions in millimeters (inches).
.
© Danfoss, 2013-09 K14425 UNIT SPEC 1
Phased Out Products
ADJUSTMENTS
TIME - SECONDS
0 1 2 3 4 5 6
25
50
75
100
R40 MAX CCW
R40 MAX CW
VALVE OUTPUT - %
1679
INPUT VOLTS
0
0
OUTPUT CURRENT - mA
1 2 3 4 5 6 7 8
200
400
600
800
1000
FULL CW
R18
FACTORY
SETTING
FULL
CCW
1688
Threshold adjustment.
1689
Full stroke adjustment.
INPUT VOLTS
0
0
OUTPUT CURRENT - mA
1 2 3 4 5 6 7 8
200
400
600
800
1000
FULL CW
R30
FACTORY
SETTING
FULL
CCW