  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 310, A319 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort310,applicationA319
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype.......................................9
2.3Mounting...........................................................11
2.4Placingthetemperaturesensors................................15
2.5Electricalconnections.............................................17
2.6InsertingtheECLApplicationKey..............................27
2.7Checklist............................................................33
2.8Navigation,ECLApplicationKeyA319.........................34
3.0Dailyuse.........................................................38
3.1Howtonavigate...................................................38
3.2Understandingthecontrollerdisplay..........................39
3.3Ageneraloverview:Whatdothesymbolsmean?...........41
3.4Monitoringtemperaturesandsystem
components........................................................42
3.5Influenceoverview................................................43
3.6Manualcontrol.....................................................44
3.7Schedule............................................................45
4.0Settingsoverview............................................46
5.0Settings...........................................................48
5.1IntroductiontoSettings..........................................48
5.2Flowtemperature..................................................49
5.3Returnlimit.........................................................52
5.4Controlparameters................................................56
5.5Application.........................................................63
5.6Tanktemperature..................................................70
5.7Alarm................................................................73
5.8Alarmoverview....................................................76
6.0Commoncontrollersettings..............................77
6.1Introductionto‘Commoncontrollersettings................77
6.2Time&Date.........................................................78
6.3Holiday..............................................................79
6.4Inputoverview.....................................................81
6.5Log...................................................................82
6.6Outputoverride....................................................83
6.7Keyfunctions.......................................................84
6.8System...............................................................86
7.0Miscellaneous..................................................93
7.1ECA30/31setupprocedures...................................93
7.2Overridefunction................................................101
7.3Severalcontrollersinthesamesystem......................104
7.4Frequentlyaskedquestions....................................107
7.5Definitions........................................................110
7.6Type(ID6001),overview.......................................113
7.7ParameterIDoverview..........................................114
©Danfoss|2017.09VI.JM.L4.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwiththeECLApplicationKey
A319(codeno.087H3831)
TheECLApplicationKeyA319containstwosubtypes:
A319.1:Heatingsupply,directlyfrombuffer
A319.2:asA319.1,butwithmixingcircuitafterthebuffer
SeetheInstallationGuideforelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310whichalso
allowsM-bus,ModbusandEthernet(Internet)communication.
TheApplicationKeyA319complieswithECLComfort310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connected.
TheapplicationA319workswithadditionalInternalI/Omodules:
TheextensionmoduleECA32gives0-10Voltsignalforspeed
controlofchargingandcirculationpumps
TheextensionmoduleECA35gives0-10Voltsignalforspeed
controlofchargingandcirculationpumps.ECA35canalso
givePWM*signalforspeedcontrolofchargingandcirculation
pumps.
TheECLComfort310workswitheitheroneECA32oroneECA
35.TheInternalI/Omoduleinquestionisplacedinthebasepart
oftheECLComfort310.
*PWM=PulseWidthModulation
TogetherwiththeECLComfort310theadditionalInternalI/O
modulescanalsobeusedforextradatacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:http://district-heating.danfoss.com/download/tools/
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(codeno.087H3040)
ECLComfort310B,230volta.c.(codeno.087H3050)
ECLComfort310,24volta.c.(codeno.087H3044)
TheB-typehasnodisplayanddial.
TheB-typeisoperatedbymeansoftheremotecontrolunit
ECA30/31:
ECA30(codeno.087H3200)
ECA31(codeno.087H3201)
2|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
InternalI/Omodules:
ECA32(codeno.087H3202)
ECA35(codeno.087H3205)
BasepartforECLComfort310,230voltand24volt:(codeno.
087H3230).
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
VI.JM.L4.02
©Danfoss|2017.09|3
OperatingGuideECLComfort310,applicationA319
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
4|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.JM.L4.02
©Danfoss|2017.09|5
OperatingGuideECLComfort310,applicationA319
2.0Installation
2.1Beforeyoustart
TheECLapplicationkeyA319contains2subtypes:A319.1and
A319.2.
Theseheatingbasedapplicationsareveryflexible.
ThebasicprinciplesforapplicationA319.1:
Temperaturecontrolofbuffer
ThebuffertemperatureS6isadjustedaccordingtoyour
requirements.ThesupplytemperaturesensorS2,thebuffer
temperaturesensorsS6andS8andthechargingtemperature
sensorS3arethemostimportantsensorsandmustbeconnected.
ThedesiredbuffertemperatureatS6iscalculatedintheECL
controller,basedonthedemandfromtheheatingcircuit
(consumer).ThisdemandisaresultoftheoutdoortemperatureS1,
theheatcurveandadesiredroomtemperature.Acompensation
fortheheatlossbetweenbuffertankandconsumercanbeset
as"Demandoffset" .
ThechargingtemperatureatS3isbasedonthedesiredbuffer
temperatureatS6andachargingdifference.
Startbufferchargingprocess:
1.BuffertemperatureS6temperaturegetslowerthan('Desired
buffertemperature'+'Startdifference').
Anexample:60°C+(-7)=53°C
2.X1isswitchedON
3.M1opensinordertoincreasethesupplytemperatureS2
4.P2isswitchedONwhensupplytemperatureS2getshigher
than('Desiredbuffertemperature'+'Pumpstartdiff.').
Example:60°C+3K=63°C
V2startswithminimumspeed,forexample20%
5.M1controlsthechargingtemperatureatS3
6.V2increasesthespeedaslongasthechargingtemperatureis
equaltothedesiredchargingtemperature.
Stopbufferchargingprocess:
1.BuffertemperatureS6temperaturegetshigherthan('Desired
buffertemperature'+'Startdifference)
AND
LowerbuffertemperatureS8getshigherthan('Desiredbuffer
temperature'+'Stopdifference).
Anexample:S6temperaturehigherthan(60°C+(-7)=53°C)
AND(60°C+(-4)=56°C)
2.P2isswitchedOFF,respecting'Char.Ppost-run'.V2changes
to0%.
NOTE:Post-runisnotrespectedifchargingtemperatureS3islower
thandesiredchargingtemperature.
3.X1isswitchedOFF
4.M1closesormaintainsthedesiredtemperatureatS3.
TypicalA319.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S1
Outdoortemperaturesensor
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S4
(monitoringonly)Flowtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Upperbuffertemperaturesensor
S7
notused
S8
(mandatory)Lowerbuffertemperaturesensor
S9
Pressuredifferencetransmitter(0-10V)
S10
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm
6|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
Bymeansofaweekschedule,thecircuitcanbeinComfortor
‘Saving’mode(twovaluesforthedesiredroomtemperature).In
'Saving'modetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M1)isopenedgraduallywhen
thechargingtemperatureislowerthanthedesiredcharging
temperatureandviceversa.
ThereturntemperatureS5canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredchargingtemperatureatS3canbe
adjusted(typicallytoalowervalue);thisresultsinagradualclosing
ofthemotorizedcontrolvalve.
Furthermore,thereturntemperaturelimitationcanbedependent
ontheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
TheON-OFFoutputX1isONatheatingdemand.
ThecirculationpumpP3isONatheatingdemandoratfrost
protection.
Unusedinputcan,bymeansofanoverrideswitchorrelaycontact,
beusedforoverridingthescheduletoafixed'Comfort','Saving' ,
'Frostprotection'or'Constanttemperature'mode.
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
The'Frostprotection'modemaintainsaselectabletemperature,
forexample10°C.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.TheECLControllersintheECL485bus
systemcanworkasmasterandslaves.
AlarmA1(=relay6)canbeactivatedif:
theactualchargingtemperaturediffersfromthedesiredcharge
temperature
thesupplytemperaturedoesnotreachthenecessarylevel
atemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
Pressuredifferencecontrol(optional):
ThecirculationpumpP3/V3can,asanalternativetoON-OFF
control,bespeedcontrolledbymeansofa0-10voltsignalora
PWMsignal.ThedesiredpressuredifferenceatS9canbesetforthe
speedcontrolprocedure.
VI.JM.L4.02
©Danfoss|2017.09|7
OperatingGuideECLComfort310,applicationA319
ThebasicprinciplesforapplicationA319.2:
TheapplicationA319.2workslikeA319.1andwiththeseadditional
features:
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe
flowtemperatureS4islowerthanthedesiredflowtemperature
andviceversa.
TypicalA319.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S1
Outdoortemperaturesensor
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S4
(mandatory)Flowtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Upperbuffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
Pressuredifferencetransmitter(0-10V)
S10
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
8|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
A319.1,ex.a
Chargingcontrolofbuffertemperatureandheatingsupplydirectlyfrombuffer.Controlofpressuredifference.
Sensoradvice:
SensorS3,S6andS8mustbeconnected.Ifnot,thechargingprocesswillnotwork.
IfpressuredifferencesensorS9isnotconnected,thespeedcontrolofP3/V3isnotinaction.
VI.JM.L4.02
©Danfoss|2017.09|9
OperatingGuideECLComfort310,applicationA319
A319.2,ex.a
Chargingcontrolofbuffertemperatureandheatingsupplyfrombufferviamixingcircuit.Controlofpressuredifference.
Sensoradvice:
SensorS3,S4,S6andS8mustbeconnected.Ifnot,thechargingprocesswillnotwork.
IfpressuredifferencesensorS9isnotconnected,thespeedcontrolofP3/V3isnotinaction.
10|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
VI.JM.L4.02
©Danfoss|2017.09|11
OperatingGuideECLComfort310,applicationA319
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
12|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
VI.JM.L4.02
©Danfoss|2017.09|13
OperatingGuideECLComfort310,applicationA319
2.3.3MountingtheinternalI/OmoduleECA32orECA35
TheECA32module(ordercodeno.087H3202)orECA35module
(ordercodeno.087H3205)canbeinsertedintotheECLComfort
310/310Bbasepartforadditionalinputandoutputsignalsin
relevantapplications.
ECA32
ECA35
14|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
VI.JM.L4.02
©Danfoss|2017.09|15
OperatingGuideECLComfort310,applicationA319
Pt1000temperaturesensor(IEC751B,1000/0°C)
Relationshipbetweentemperatureandohmicvalue:
16|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
Factoryestablishedjumpersinthebasepart:
5to8,9to14,Lto5andLto9,Nto10
VI.JM.L4.02
©Danfoss|2017.09|17
OperatingGuideECLComfort310,applicationA319
2.5.2Electricalconnections,230Va.c.,powersupply,pumps,motorizedcontrolvalvesetc.
Connections,ingeneral.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Aforinductiveload)
Triac(electronicrelay)terminals
0,2A/230Va.c.
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
2.5.3Electricalconnections,24Va.c.,powersupply,pumps,motorizedcontrolvalvesetc.
Connections,ingeneral.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/24Va.c.
(4Aforohmicload,2Aforinductiveload)
Triac(electronicrelay)terminals
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power
suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230
Va.c.from24Va.c.
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
18|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
Electricalconnections,ECA32/ECA35
Connections,ingeneral.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Maximumloadratings:
Terminals
ECA32ECA35
PWMOut1(52)
5k*
PWMOut2(53)
5k*
PWMOut3(54)
5k*
PWMOut4(55)
5k*
AnalogOut1(59)AnalogOut1(59)47k*
AnalogOut2(60)AnalogOut2(60)47k*
AnalogOut3(61)AnalogOut3(61)47k*
*Thevalueisaminimum.
VI.JM.L4.02
©Danfoss|2017.09|19
OperatingGuideECLComfort310,applicationA319
2.5.4Electricalconnections,Pt1000temperaturesensors
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
A319
TerminalSensor/description
Type
(recom.)
29and30
S1
Outdoortemperature
sensor*
ESMT
28and30
S2
Supplytemperature
sensor
ESM-11/
ESMB/
ESMC/
ESMU
27and30
S3
Chargingtemperature
sensor**
ESM-11/
ESMB/
ESMC/
ESMU
26and30
S4
A319.1:
Flowtemperature
sensor,monitoring
A319.2:
Flowtemperature
sensor
ESM-11/
ESMB/
ESMC/
ESMU
25and30
S5
Returntemperature
sensor
ESM-11/
ESMB/
ESMC/
ESMU
24and30
S6
Upperbuffer-tank
temperaturesensor
ESMB/
ESMU
23and30
S7
notused
22and30
S8
Upperbuffer-tank
temperaturesensor
ESMB/
ESMU
21and30
S9
Pressuredifference
transmitter(0-10V)
20and30
S10
0-10Voltasdesired
temperature
Temperaturesensorsmustbeconnectedinordertohavethe
desiredfunctionality.
*
Iftheoutdoortemperaturesensorisnotconnectedorthe
sensorcableisshort-circuited,thecontrollerassumesthat
theoutdoortemperatureis0(zero)°C.
**
Ifthesensorisnotconnectedorthesensorcableis
short-circuited,themotorizedcontrolvalvecloses(safety
function).
Factoryestablishedjumper:
30tocommonterminal.
20|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
/