Danfoss ECL Comfort 310, A319 Operating instructions

Category
Thermostats
Type
Operating instructions
OperatingGuide
ECLComfort310,applicationA319
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype.......................................9
2.3Mounting...........................................................11
2.4Placingthetemperaturesensors................................15
2.5Electricalconnections.............................................17
2.6InsertingtheECLApplicationKey..............................27
2.7Checklist............................................................33
2.8Navigation,ECLApplicationKeyA319.........................34
3.0Dailyuse.........................................................38
3.1Howtonavigate...................................................38
3.2Understandingthecontrollerdisplay..........................39
3.3Ageneraloverview:Whatdothesymbolsmean?...........41
3.4Monitoringtemperaturesandsystem
components........................................................42
3.5Influenceoverview................................................43
3.6Manualcontrol.....................................................44
3.7Schedule............................................................45
4.0Settingsoverview............................................46
5.0Settings...........................................................48
5.1IntroductiontoSettings..........................................48
5.2Flowtemperature..................................................49
5.3Returnlimit.........................................................52
5.4Controlparameters................................................56
5.5Application.........................................................63
5.6Tanktemperature..................................................70
5.7Alarm................................................................73
5.8Alarmoverview....................................................76
6.0Commoncontrollersettings..............................77
6.1Introductionto‘Commoncontrollersettings................77
6.2Time&Date.........................................................78
6.3Holiday..............................................................79
6.4Inputoverview.....................................................81
6.5Log...................................................................82
6.6Outputoverride....................................................83
6.7Keyfunctions.......................................................84
6.8System...............................................................86
7.0Miscellaneous..................................................93
7.1ECA30/31setupprocedures...................................93
7.2Overridefunction................................................101
7.3Severalcontrollersinthesamesystem......................104
7.4Frequentlyaskedquestions....................................107
7.5Definitions........................................................110
7.6Type(ID6001),overview.......................................113
7.7ParameterIDoverview..........................................114
©Danfoss|2017.09VI.JM.L4.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwiththeECLApplicationKey
A319(codeno.087H3831)
TheECLApplicationKeyA319containstwosubtypes:
A319.1:Heatingsupply,directlyfrombuffer
A319.2:asA319.1,butwithmixingcircuitafterthebuffer
SeetheInstallationGuideforelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310whichalso
allowsM-bus,ModbusandEthernet(Internet)communication.
TheApplicationKeyA319complieswithECLComfort310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connected.
TheapplicationA319workswithadditionalInternalI/Omodules:
TheextensionmoduleECA32gives0-10Voltsignalforspeed
controlofchargingandcirculationpumps
TheextensionmoduleECA35gives0-10Voltsignalforspeed
controlofchargingandcirculationpumps.ECA35canalso
givePWM*signalforspeedcontrolofchargingandcirculation
pumps.
TheECLComfort310workswitheitheroneECA32oroneECA
35.TheInternalI/Omoduleinquestionisplacedinthebasepart
oftheECLComfort310.
*PWM=PulseWidthModulation
TogetherwiththeECLComfort310theadditionalInternalI/O
modulescanalsobeusedforextradatacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:http://district-heating.danfoss.com/download/tools/
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(codeno.087H3040)
ECLComfort310B,230volta.c.(codeno.087H3050)
ECLComfort310,24volta.c.(codeno.087H3044)
TheB-typehasnodisplayanddial.
TheB-typeisoperatedbymeansoftheremotecontrolunit
ECA30/31:
ECA30(codeno.087H3200)
ECA31(codeno.087H3201)
2|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
InternalI/Omodules:
ECA32(codeno.087H3202)
ECA35(codeno.087H3205)
BasepartforECLComfort310,230voltand24volt:(codeno.
087H3230).
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
VI.JM.L4.02
©Danfoss|2017.09|3
OperatingGuideECLComfort310,applicationA319
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
4|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.JM.L4.02
©Danfoss|2017.09|5
OperatingGuideECLComfort310,applicationA319
2.0Installation
2.1Beforeyoustart
TheECLapplicationkeyA319contains2subtypes:A319.1and
A319.2.
Theseheatingbasedapplicationsareveryflexible.
ThebasicprinciplesforapplicationA319.1:
Temperaturecontrolofbuffer
ThebuffertemperatureS6isadjustedaccordingtoyour
requirements.ThesupplytemperaturesensorS2,thebuffer
temperaturesensorsS6andS8andthechargingtemperature
sensorS3arethemostimportantsensorsandmustbeconnected.
ThedesiredbuffertemperatureatS6iscalculatedintheECL
controller,basedonthedemandfromtheheatingcircuit
(consumer).ThisdemandisaresultoftheoutdoortemperatureS1,
theheatcurveandadesiredroomtemperature.Acompensation
fortheheatlossbetweenbuffertankandconsumercanbeset
as"Demandoffset" .
ThechargingtemperatureatS3isbasedonthedesiredbuffer
temperatureatS6andachargingdifference.
Startbufferchargingprocess:
1.BuffertemperatureS6temperaturegetslowerthan('Desired
buffertemperature'+'Startdifference').
Anexample:60°C+(-7)=53°C
2.X1isswitchedON
3.M1opensinordertoincreasethesupplytemperatureS2
4.P2isswitchedONwhensupplytemperatureS2getshigher
than('Desiredbuffertemperature'+'Pumpstartdiff.').
Example:60°C+3K=63°C
V2startswithminimumspeed,forexample20%
5.M1controlsthechargingtemperatureatS3
6.V2increasesthespeedaslongasthechargingtemperatureis
equaltothedesiredchargingtemperature.
Stopbufferchargingprocess:
1.BuffertemperatureS6temperaturegetshigherthan('Desired
buffertemperature'+'Startdifference)
AND
LowerbuffertemperatureS8getshigherthan('Desiredbuffer
temperature'+'Stopdifference).
Anexample:S6temperaturehigherthan(60°C+(-7)=53°C)
AND(60°C+(-4)=56°C)
2.P2isswitchedOFF,respecting'Char.Ppost-run'.V2changes
to0%.
NOTE:Post-runisnotrespectedifchargingtemperatureS3islower
thandesiredchargingtemperature.
3.X1isswitchedOFF
4.M1closesormaintainsthedesiredtemperatureatS3.
TypicalA319.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S1
Outdoortemperaturesensor
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S4
(monitoringonly)Flowtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Upperbuffertemperaturesensor
S7
notused
S8
(mandatory)Lowerbuffertemperaturesensor
S9
Pressuredifferencetransmitter(0-10V)
S10
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm
6|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
Bymeansofaweekschedule,thecircuitcanbeinComfortor
‘Saving’mode(twovaluesforthedesiredroomtemperature).In
'Saving'modetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M1)isopenedgraduallywhen
thechargingtemperatureislowerthanthedesiredcharging
temperatureandviceversa.
ThereturntemperatureS5canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredchargingtemperatureatS3canbe
adjusted(typicallytoalowervalue);thisresultsinagradualclosing
ofthemotorizedcontrolvalve.
Furthermore,thereturntemperaturelimitationcanbedependent
ontheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
TheON-OFFoutputX1isONatheatingdemand.
ThecirculationpumpP3isONatheatingdemandoratfrost
protection.
Unusedinputcan,bymeansofanoverrideswitchorrelaycontact,
beusedforoverridingthescheduletoafixed'Comfort','Saving' ,
'Frostprotection'or'Constanttemperature'mode.
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
The'Frostprotection'modemaintainsaselectabletemperature,
forexample10°C.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.TheECLControllersintheECL485bus
systemcanworkasmasterandslaves.
AlarmA1(=relay6)canbeactivatedif:
theactualchargingtemperaturediffersfromthedesiredcharge
temperature
thesupplytemperaturedoesnotreachthenecessarylevel
atemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview)
Pressuredifferencecontrol(optional):
ThecirculationpumpP3/V3can,asanalternativetoON-OFF
control,bespeedcontrolledbymeansofa0-10voltsignalora
PWMsignal.ThedesiredpressuredifferenceatS9canbesetforthe
speedcontrolprocedure.
VI.JM.L4.02
©Danfoss|2017.09|7
OperatingGuideECLComfort310,applicationA319
ThebasicprinciplesforapplicationA319.2:
TheapplicationA319.2workslikeA319.1andwiththeseadditional
features:
Themotorizedcontrolvalve(M2)isopenedgraduallywhenthe
flowtemperatureS4islowerthanthedesiredflowtemperature
andviceversa.
TypicalA319.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S1
Outdoortemperaturesensor
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S4
(mandatory)Flowtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Upperbuffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
Pressuredifferencetransmitter(0-10V)
S10
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
8|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
A319.1,ex.a
Chargingcontrolofbuffertemperatureandheatingsupplydirectlyfrombuffer.Controlofpressuredifference.
Sensoradvice:
SensorS3,S6andS8mustbeconnected.Ifnot,thechargingprocesswillnotwork.
IfpressuredifferencesensorS9isnotconnected,thespeedcontrolofP3/V3isnotinaction.
VI.JM.L4.02
©Danfoss|2017.09|9
OperatingGuideECLComfort310,applicationA319
A319.2,ex.a
Chargingcontrolofbuffertemperatureandheatingsupplyfrombufferviamixingcircuit.Controlofpressuredifference.
Sensoradvice:
SensorS3,S4,S6andS8mustbeconnected.Ifnot,thechargingprocesswillnotwork.
IfpressuredifferencesensorS9isnotconnected,thespeedcontrolofP3/V3isnotinaction.
10|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
VI.JM.L4.02
©Danfoss|2017.09|11
OperatingGuideECLComfort310,applicationA319
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
12|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
VI.JM.L4.02
©Danfoss|2017.09|13
OperatingGuideECLComfort310,applicationA319
2.3.3MountingtheinternalI/OmoduleECA32orECA35
TheECA32module(ordercodeno.087H3202)orECA35module
(ordercodeno.087H3205)canbeinsertedintotheECLComfort
310/310Bbasepartforadditionalinputandoutputsignalsin
relevantapplications.
ECA32
ECA35
14|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
VI.JM.L4.02
©Danfoss|2017.09|15
OperatingGuideECLComfort310,applicationA319
Pt1000temperaturesensor(IEC751B,1000/0°C)
Relationshipbetweentemperatureandohmicvalue:
16|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
Factoryestablishedjumpersinthebasepart:
5to8,9to14,Lto5andLto9,Nto10
VI.JM.L4.02
©Danfoss|2017.09|17
OperatingGuideECLComfort310,applicationA319
2.5.2Electricalconnections,230Va.c.,powersupply,pumps,motorizedcontrolvalvesetc.
Connections,ingeneral.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/230Va.c.
(4Aforohmicload,2Aforinductiveload)
Triac(electronicrelay)terminals
0,2A/230Va.c.
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
2.5.3Electricalconnections,24Va.c.,powersupply,pumps,motorizedcontrolvalvesetc.
Connections,ingeneral.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Maximumloadratings:
Relayterminals
4(2)A/24Va.c.
(4Aforohmicload,2Aforinductiveload)
Triac(electronicrelay)terminals
1A/24Va.c.
Donotconnect230Va.c.poweredcomponentstoa24Va.c.power
suppliedcontrollerdirectly.Useauxilliaryrelays(K)toseparate230
Va.c.from24Va.c.
Wirecrosssection:0.5-1.5mm²
Incorrectconnectioncandamagetheelectronicoutputs.
Max.2x1.5mm²wirescanbeinsertedintoeachscrewterminal.
18|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
Electricalconnections,ECA32/ECA35
Connections,ingeneral.
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)forapplicationspecificconnections.
Maximumloadratings:
Terminals
ECA32ECA35
PWMOut1(52)
5k*
PWMOut2(53)
5k*
PWMOut3(54)
5k*
PWMOut4(55)
5k*
AnalogOut1(59)AnalogOut1(59)47k*
AnalogOut2(60)AnalogOut2(60)47k*
AnalogOut3(61)AnalogOut3(61)47k*
*Thevalueisaminimum.
VI.JM.L4.02
©Danfoss|2017.09|19
OperatingGuideECLComfort310,applicationA319
2.5.4Electricalconnections,Pt1000temperaturesensors
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
A319
TerminalSensor/description
Type
(recom.)
29and30
S1
Outdoortemperature
sensor*
ESMT
28and30
S2
Supplytemperature
sensor
ESM-11/
ESMB/
ESMC/
ESMU
27and30
S3
Chargingtemperature
sensor**
ESM-11/
ESMB/
ESMC/
ESMU
26and30
S4
A319.1:
Flowtemperature
sensor,monitoring
A319.2:
Flowtemperature
sensor
ESM-11/
ESMB/
ESMC/
ESMU
25and30
S5
Returntemperature
sensor
ESM-11/
ESMB/
ESMC/
ESMU
24and30
S6
Upperbuffer-tank
temperaturesensor
ESMB/
ESMU
23and30
S7
notused
22and30
S8
Upperbuffer-tank
temperaturesensor
ESMB/
ESMU
21and30
S9
Pressuredifference
transmitter(0-10V)
20and30
S10
0-10Voltasdesired
temperature
Temperaturesensorsmustbeconnectedinordertohavethe
desiredfunctionality.
*
Iftheoutdoortemperaturesensorisnotconnectedorthe
sensorcableisshort-circuited,thecontrollerassumesthat
theoutdoortemperatureis0(zero)°C.
**
Ifthesensorisnotconnectedorthesensorcableis
short-circuited,themotorizedcontrolvalvecloses(safety
function).
Factoryestablishedjumper:
30tocommonterminal.
20|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116