2.0Installation
2.1Beforeyoustart
TheECLapplicationkeyA319contains2subtypes:A319.1and
A319.2.
Theseheatingbasedapplicationsareveryflexible.
ThebasicprinciplesforapplicationA319.1:
Temperaturecontrolofbuffer
ThebuffertemperatureS6isadjustedaccordingtoyour
requirements.ThesupplytemperaturesensorS2,thebuffer
temperaturesensorsS6andS8andthechargingtemperature
sensorS3arethemostimportantsensorsandmustbeconnected.
ThedesiredbuffertemperatureatS6iscalculatedintheECL
controller,basedonthedemandfromtheheatingcircuit
(consumer).ThisdemandisaresultoftheoutdoortemperatureS1,
theheatcurveandadesiredroomtemperature.Acompensation
fortheheatlossbetweenbuffertankandconsumercanbeset
as"Demandoffset" .
ThechargingtemperatureatS3isbasedonthedesiredbuffer
temperatureatS6andachargingdifference.
Startbufferchargingprocess:
1.BuffertemperatureS6temperaturegetslowerthan('Desired
buffertemperature'+'Startdifference').
Anexample:60°C+(-7)=53°C
2.X1isswitchedON
3.M1opensinordertoincreasethesupplytemperatureS2
4.P2isswitchedONwhensupplytemperatureS2getshigher
than('Desiredbuffertemperature'+'Pumpstartdiff.').
Example:60°C+3K=63°C
V2startswithminimumspeed,forexample20%
5.M1controlsthechargingtemperatureatS3
6.V2increasesthespeedaslongasthechargingtemperatureis
equaltothedesiredchargingtemperature.
Stopbufferchargingprocess:
1.BuffertemperatureS6temperaturegetshigherthan('Desired
buffertemperature'+'Startdifference)
AND
LowerbuffertemperatureS8getshigherthan('Desiredbuffer
temperature'+'Stopdifference).
Anexample:S6temperaturehigherthan(60°C+(-7)=53°C)
AND(60°C+(-4)=56°C)
2.P2isswitchedOFF,respecting'Char.Ppost-run'.V2changes
to0%.
NOTE:Post-runisnotrespectedifchargingtemperatureS3islower
thandesiredchargingtemperature.
3.X1isswitchedOFF
4.M1closesormaintainsthedesiredtemperatureatS3.
TypicalA319.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S1
Outdoortemperaturesensor
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S4
(monitoringonly)Flowtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Upperbuffertemperaturesensor
S7
notused
S8
(mandatory)Lowerbuffertemperaturesensor
S9
Pressuredifferencetransmitter(0-10V)
S10
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm
6|©Danfoss|2017.09
VI.JM.L4.02
OperatingGuideECLComfort310,applicationA319