Danfoss Termix Compactstation 28 MS VVX Operating instructions

Type
Operating instructions
OperatingGuide
TermixCompact28MSVVX
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1MountingtheCompactstation..................................4
4.2Start-up..............................................................10
4.3Electricalconnections.............................................12
5.0Design.............................................................13
5.1Design...............................................................13
5.2Schematicdiagram................................................14
6.0Controls..........................................................15
6.1Heatingcircuit......................................................15
6.2Other.................................................................19
6.3Maintenance........................................................20
7.0Troubleshooting..............................................21
7.1Troubleshootingingeneral......................................21
7.2TroubleshootingDHW............................................22
7.3TroubleshootingHE...............................................23
7.4Disposal.............................................................25
8.0Declaration......................................................27
8.1Declarationofconformity........................................27
©Danfoss|2023.04AQ446329604344en-000101/LUK55032|1
2.0Functionaldescription
Districtheatingsubstationforindirectheatingand
instantaneousdomestichotwater.
Spaceheatinganddomestichotwater(DHW)
TheTermixCompact28MSVVXisacompleteunitforindirect
spaceheatinganddomestichotwaterfordistrictheatinginlarge
buildingssuchassportscentres,schools,blocksofflatsetc.
Itcanbeusedforconnectiontoindirectdistrictheatinginplaces
wherethedistrictheatingplantrequiresahydraulicbreak.Itis
alsosuitableforconversiontodistrictheatingwhenthesecondary
heatingsystemisunsuitabletobeingconnectedtodirectdistrict
heatingorwhenaparticularlyeffectivesecurityagainstleakagein
theheatingsystemisrequired.
Efficientheatexchanger
Thesubstationisfittedwithanefficientplateheatexchanger,
whichensuresthemostfavourableheatextractionandachieves
optimumcomfortandoperatingeconomy.
Electronicregulation
TheTermixCompact28MSVVXisbuiltwithaplateheatexchanger
forinstantaneousdomestichotwaterproductionandheat
exchangerforspaceheating.Eachcircuitisalsosuppliedwithits
ownflowcontroller.
Thisallowsthegreatestdegreeofindividualcontrol,thus
preventingoscillationatdifferentloads.Theelectroniccontrolleris
factorypre-set.Electricalcomponentsarepre-wired,andtheunitis
equippedwithaplugfor230Va.c.
Itisrecommendedthatbalancingvalvesareinstalledinthe
building’srisersintheheatsupplyandontheheatingsystem’s
returnlineimmediatelybeforetheunit.
Minimalheatloss
Completeinsulationoftheunitensuresminimalheatloss.
Easyinstallation
Theunitconsistsoftwomodules,oneforspaceheatingandone
fordomestichotwaterproduction,whichiseasilyassembled
intoonesinglemodule.Thismodulardesignmakesworkduring
installationsignificantlyeasier,astheweightissplitbetweentwo
modulesduringhandling.
Flexiblesolution
Pipeconnectioncanbemadefromeitherthetoporbottom,which
makesthissolutionhighlyflexible.Atthesametime,bothspace
andtimearesavedwheninstalling.
Reliableandeasytoinstall
TermixCompact28MSVVXisoperationallyreliable.Aquality
productmanufacturedinDenmarkwhichiseasytoinstalland
quicklycommissioned.
2|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheflowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-fire,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
REACH
AllDanfossA/SproductsfulfilltherequirementsinREACH.
OneoftheobligationsinREACHistoinformcustomersabout
presenceofCandidatelistsubstancesifany,weherebyinform
youaboutonesubstanceonthecandidatelist:Theproduct
containsbrasspartswhichcontainslead(CASno:7439-92-1)ina
concentrationabove0.1%w/w.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheflowmediuminthesubstationis
110°C.
Themaximumoperatingpressureofthesubstationis16bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallflangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|3
OperatingGuideTermixCompact28MSVVX
4.0Mounting
4.1MountingtheCompactstation
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Districtheating(DH)supply
2.Districtheating(DH)return
3.Hotwatercirculation(HWC)
4.Heating(HE)supply
5.Heating(HE)return
6.Domestichotwater(DHW)
7.Domesticcoldwater(DCW)
Connectionsizes:
DH+HE+DHW+DCW:G1”(int.thread)
HWC:G¾”(int.thread)
Dimensions(mm):
Withinsulation:H1063xW905xD400
Weight(approx.):55kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
Removethefront.
Removeotherblocks.
Attachthemountingrailtothewall.
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|5
OperatingGuideTermixCompact28MSVVX
Liftthestation.
Mountthestationonthemountingrail.
Attachthestationtothewallintheholesonthemountingplate.
6|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
InstallisolationvalvewithpressuregaugetotheleftHeating
supply.
InstallisolationvalvewithsafetyvalvetotherightHeating
return.
Installthecirculationpumpwiththesinglecheckvalve.
MountblockAontheleft-handsideofthepump.AttachblockE
toblockA,andattachittothepipeabovethepumpbyclicking
itinplace.
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|7
OperatingGuideTermixCompact28MSVVX
MountblockBontheright-handsideofthepump.
MountblockF.Theblockishingedandcanbedrawnaroundthe
valve.AttachtheblocktoblockBandE.
MountblockJandHaroundthevalveforthetankcontrol.
Mountthefrontcover.
8|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
4.1.1InstallingtheCompactstation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbefittedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,flangedorweldedconnections.
Keyholeformounting.
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|9
OperatingGuideTermixCompact28MSVVX
4.2Start-up
Start-up,Indirectheating
Filling:
1:Firstfill
Whencarryingoutfirstfill,theheatexchangermustbeslowlyfilled
withwateruntilitreachesworkingpressure.
2:Pressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.This
instructionmustbefollowedstrictly,toavoiddangeroussituations.
3:Supplyhose
AballvalvewithplugisinstalledintheHEreturnline.Tofillthe
system,theballvalvemustfirstbeclosed,theplugremovedand
asupplyhoseconnected.Onre-openingtheballvalve,system
fillcancommence.
4:Pre-pressure
Whenfillingthesystemwithwater,thepressuregaugeshouldbe
observedclosely.Theexpansionvesselissuppliedpre-pressurised
to0.5bar.Thepre-pressurerequiredateachsubstationwill
dependonsystemhead(thedistancebetweenthelowestand
highestpointinthesystem),forexample:
5:Fillingstop
Fillingmuststopwhenthepressuregaugeshowsapressure
approximately1-2barhigherthanthepre-pressuresetting.The
ballvalveisthenclosed,thehoseremovedandtheplugputback
in.
Start-up:
1:Pumpspeed
Setthepumptohighestspeedbeforestart-up.
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconfirmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
4:Ventsystem
Switchoffthepumpandventtheinstallationaftertheradiators
havebeenwarmedup.
5:Adjustpumpspeed
Setthepumptothelowestspeedconsistentwithcomfortand
electricityconsumption.
Normallythechange-overswitchissetinthemidposition(default).
Howeverforsystemswithunderfloorheatingorsinglepipeloop
systems,itmaybenecessarytoturnthechange-overswitch
upwards.
Higherpumpspeedsareonlyusediftheheatingrequirement
increases.
Re-tightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Pump
Thepumpmustbeswitchedoffduringsystemfill.
Height(m)Pressure(bar)
050,5
5101,0
10151,5
15202,0
10|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
Underfloorheating:
Pumpstopfunction
Ifthesubstationisusedinconnectionwithunderfloorheating,the
circulationpumpmustbeconnectedtothepumpstopfunctionin
theunderfloorheatingcontroller.Thepumpmustbestoppedif
allunderfloorheatingcircuitsareclosed.
Warranty
Ifthisisnotpossible,thenflowmustbecontinuedthroughthe
by-pass.Failingthis,thepumpwillbeatriskofseizureandany
remainingwarrantywillbewithdrawn.
Summeroperation:
Switchoffpump
Insummerthecirculationpumpmustbeswitchedoffandthe
shut-offvalvetoHEsupplyclosed.
Runningpumpbi-weekly
Itisrecommendedtostartupthecirculationpump(for2minutes)
onceamonthduringsummer;theshut-offvalveoftheHEsupply
mustbeshut.
Electroniccontroller
Mostelectroniccontrollerswillstartupthepumpautomatically
(pleasenotemanufacturer´sinstructions).
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|11
OperatingGuideTermixCompact28MSVVX
4.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
12|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
AHeatexchanger,HE9Strainer27Actuator
BHeatexchanger,DHW10Circulatorpump292–waymotorizedvalve
FElectroniccontroller11HWCpump30Flowcontrollerw/intg.controlvalve
1Isolationvalve19Surfacesensor31Differentialpressurecontroller
2Singlecheckvalve20Filling/drainvalve48Airvent,manual
4Safetyvalve,HE26Pressuregauge
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|13
OperatingGuideTermixCompact28MSVVX
5.2Schematicdiagram
5.2.1SchematicdiagramTermixCompact28MSVVX
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
AHeatexchanger,HTG10Circulatorpump26Pressuregauge
BHeatexchangerDHW11HWCpump27Actuator
FElectroniccontroller16Outdoorsensor292–waymotorizedvalve
1Isolationvalve19Surfacesensor30Flowcontrollerw/intg.controlvalve
2Singlevalve20Filling/drainvalve31Differentialpressurecontroller
4Safetyvalve23Ballvalve40Immersionsensor
9Strainer24Deliveredloosewithunit48Airvent,manual
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
HESupply:HeatingSupply
HEReturn:HeatingReturn
DHW:Domestichotwater
HWC:Hotwatercirculation
DCW:Domesticcoldwater
5.2.2Technicalparameters
Nominalpressure:PN16
Max.DHsupplytemperature:110°C
Brazingmaterial(HEX):Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
14|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
6.0Controls
6.1Heatingcircuit
6.1.1Differentialpressurecontroller
Thedifferentialpressurecontrollersmoothsoutthefluctuationsin
pressurearrivingfromthedistrictheatingnetwork.Theoperating
pressureinthesubstationisthusheldsteady.
6.1.2Flowcontrollerwithintegratedcontrolvalve
Thecontrollerisaself-actingflowcontrollerwithintegratedcontrol
valve.Thecontrollercloseswhensetmax.flowisexceededand
canbeusedincombinationwithDanfosselectricalactuatorswith
orwithoutsafetyfunction.Springreturnmotorcanbeusedas
safetyfunctionbypowerfailure.
6.1.3Electric2–waymotorizedvalve
Actuatorswithorwithoutsafetyfunctionareavailablefor3-point
controls.Spring-returnactuatorscanbeusedtoprovidesafety
shut-offintheeventofpowerfailure.
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|15
OperatingGuideTermixCompact28MSVVX
6.1.4Electroniccontrol
Substationswithelectroniccontrolmustbesetinaccordancewith
manufacturer´sinstructions.
Wheretheroomtemperatureiscontrolledbyradiatorthermostats,
itisrecommendedthatthermostatsbesetforminimum
temperatureineachroom.
6.1.5Outsidetemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
6.1.6CirculatorpumpUPM3
UPM3Pumpscanbecontrolledinconstantpressure,proportional
pressureorconstantspeedmodedefinedbythemeansofasmart
userinterface.
Thevariablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
16|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
6.1.7GrundfosUPM3AUTOinstructions
Controlmode
Eachpushonthebuttonswitchestothenextprogramsetting.Thechoiceofoperationmodedependsonthetypeofheatingsystem
andthepressurelossinthesystem.
Settings
Function:Recommendedfor:GreenGreenYellowYellowYellow
ProportionalpressureAutoadapt
ConstantpressureAutoadapt
Proportionalpressure1
Proportionalpressure22-pipesystems
Proportionalpressure3MAX
Constantpressure11-pipesystems
Constantpressure2Underfloorheating
Constantpressure3MAX
ConstantCurve1
ConstantCurve2
ConstantCurve3MAX
Alarmstatus
Function:Recommendedfor:RedGreenYellowYellowYellow
PowerSupplyfailure
Blocked
Supplyvoltagelow
Electricalerror
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|17
OperatingGuideTermixCompact28MSVVX
6.1.8HEpressuregauge
TheHEpressuregaugeindicatesthepressureoftheHEsystem.
18|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
6.2Other
6.2.1Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
6.2.2Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturersinstructions.
AQ446329604344en-000101/LUK55032©Danfoss|2023.04|19
OperatingGuideTermixCompact28MSVVX
6.3Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualifiedandauthorizedpersonnelonly.
20|©Danfoss|2023.04AQ446329604344en-000101/LUK55032
OperatingGuideTermixCompact28MSVVX
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21