Coopers Variospeed MK5 V3 Technical Manual

Category
Fire protection
Type
Technical Manual
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Variospeed® MK5 V3
Technical Manual
DOCUMENT VERSION:
Version 1 Sep 2019
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 2 of 29
Copyright Materials
This document is protected in law in the United Kingdom by the Copyright, Designs and Patents Act 1988.
It is also protected under International Copyright Law. Reproduction, distribution, display and use of this
document without written permission of the Coopers Fire Ltd. is prohibited.
DISCLAIMER
Introduction
The Building Regulations (England & Wales) 2010, The Building (Scotland) Regulations 2004 and The
Building Regulations (Northern Ireland) 2012 as are recognised as functional code addressing the design of
buildings with performance-based requirements. The current Building Regulations has been developed and
continue to be developed over a number of years. The enforcement of these Regulations is by Building
Control Authorities or Approved Inspectors at local and national level. A vital part of the development of
these standards is the involvement of industry and nationally recognised organisations in building product
development and the protection of public health, safety and welfare.
Attention is also drawn to the Regulatory Reform (Fire Safety) Order 2005, the Fire (Scotland) Act 2005 as
amended, the Fire Safety (Scotland) Regulations 2006 and the Fire Safety Regulations (Northern Ireland)
2010.
Legal Disclaimer
All the information appearing in this document is provided without representation or warranty whatsoever,
whether express or implied. Coopers Fire Ltd. makes no representation or warranties about the correctness
or the suitability of any information, data, products or service that appear, nor the soundness of any general
advice offered. Coopers Fire Ltd. shall not be responsible and disclaims all liability for any loss, liability,
damage (whether direct, indirect, special or consequential) or expense of any nature whatsoever, which
may be suffered as a result of, or which may be attributable, directly or indirectly, to the use of, or reliance
upon any information provided, or any actions and/ or liability for consequential or incidental damages.
Limitations
Coopers Fire Ltd. develops and manufacturers numerous fire and smoke rated products assemblies that
function as wide-spanning opening protectives. These building products enter the marketplace specifically
to assist design professionals and those authorities having jurisdiction in satisfying the requirements of
building regulations for open design without compromising fire and life safety requirements.
Application
Coopers Fire Ltd. products must be applied in accordance with either National or European directives in
accordance to regulations for construction materials in general with the applicable test certificates and
approvals for adoption. Products may only be applied to building design by trained professionals with
adequate knowledge and experience in doing so regarding opening protectives, and only after a thorough
and robust review for the applicability of their use.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 3 of 29
Contents
1 Version History ................................................................................................................................ 4
2 Contact Details ................................................................................................................................ 4
3 Safety Precautions ........................................................................................................................... 5
4 Important Symbols (Key) .................................................................................................................. 5
5 Control Panel Installation ................................................................................................................. 6
5.1 Control Panel Mounting ................................................................................................................ 6
5.1.1 Connection Cover Mounting (Optional) .................................................................................. 7
5.1.2 BMS Interface Mounting (Optional)........................................................................................ 7
5.2 Motor Cable Wiring ....................................................................................................................... 8
5.3 Setting Motor Direction ................................................................................................................. 9
6 Electrical Wiring & Connections ..................................................................................................... 10
6.1 Power Supply Unit (PSU) ........................................................................................................... 10
6.2 ARM1 Alarm Connection ............................................................................................................ 11
6.3 Single Smoke / Heat Detector .................................................................................................... 11
6.4 Dual Detector ............................................................................................................................. 12
6.5 Standard / Residential Emergency Retract ................................................................................. 12
6.6 Deluxe Emergency Retract ......................................................................................................... 13
6.7 Fireman’s Emergency Access .................................................................................................... 13
6.8 Residential Beam Detector ......................................................................................................... 14
6.9 Light Curtain ............................................................................................................................... 14
6.10 Voice Warning ............................................................................................................................ 15
6.11 Light Warning ............................................................................................................................. 15
6.12 BMS (Building Management System) Interface .......................................................................... 16
7 Commissioning .............................................................................................................................. 16
7.1 Initial Setup ................................................................................................................................ 16
7.2 Critical Settings .......................................................................................................................... 17
7.3 Optional Settings ........................................................................................................................ 20
7.4 Testing and Final Commissioning ............................................................................................... 22
8 Technical Information ..................................................................................................................... 25
8.1 General Specification ................................................................................................................. 25
8.2 Testing / Service Requirement ................................................................................................... 26
8.3 Replacement Parts ..................................................................................................................... 28
8.3.1 Fuse Replacement .............................................................................................................. 28
8.3.2 Battery Replacement ........................................................................................................... 28
9 Cleaning ........................................................................................................................................ 28
10 Removal/ Demolition Statement ..................................................................................................... 29
11 Environment Statement .................................................................................................................. 29
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 4 of 29
1 Version History
Document
Version Number
Author
Revision
Date
1
MA
September 2019
2 Contact Details
Contractor:
Coopers Fire Ltd.
Edward House
Penner Road
Havant
Hampshire, PO9 1QZ
United Kingdom
Tel: +44 (0)23 9245 4405
Email: info@coopersfire.com
Web: www.coopersfire.com
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 5 of 29
3 Safety Precautions
This product must be installed and commissioned by trained and approved Coopers Fire Ltd. personnel
under the IFC SDI05 Scheme for Installers of Smoke & Fire Barrier Assemblies recognized by United
Kingdom Accreditation Service (UKAS). Incorrect installation or operation can potentially cause personal
injury and/or damage to the system. Warning notices are given throughout where hazards and risks need to
be observed.
This manual shall be read in full before proceeding with the installation works. For any questions or
uncertainties you may have before proceeding with the installation, contact Coopers Fire Ltd.
This product is designed as a life safety system and is not designed for day-to-day use.
It is the owner’s legal obligation to periodically test the systems in accordance with guidance set out in
BS 9999:2008 or BS 9991:2012, and by the law where regulation exists. The owner may wish to engage in
a pro-active servicing contract for this life safety system which shall be serviced by those qualified to do
so that are under the IFC SDI05 Scheme for Installers of Smoke & Fire Barrier Assemblies recognized by
United Kingdom Accreditation Service. (UKAS).
Installation or use that is not in accordance with the manufacturer’s instructions may lead to
impairment of the safety of the equipment.
4 Important Symbols (Key)
Warning - Live Electrical Works
Caution!
Important Process
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 6 of 29
5 Control Panel Installation
5.1 Control Panel Mounting
The Control Panel has 4 fixing holes, all of which must be used.
The Power Supply must be secured using the approved fixings below.
Please note: it is the installer’s responsibility to ensure that the
substrate to which the control panel is to be fitted is suitable and
complies with the recommendations below.
Fixing Type
Sleeve Anchor
AnkaScrew
Coach Screw
Image
Fixing Size
M4 x 40
M4 x 40
M4 x 40
Suitable For
Concrete
Brick
Concrete
Brick
Wood
Wood
Clearance must be allowed below the Control Panel for the cable connections and fuse access.
The Control Panel should be installed in a suitable location to allow maintenance but also to protect the unit
from mechanical damage or tampering.
Where the effects of fire could result in the failure or incorrect operation of the fire curtain barriers for the
appropriate fire resistance of the compartment, all electrical wiring, the drive mechanism, the control
equipment, etc. shall be rated to 300 °C or located such that it is not exposed to temperatures above its
operational rating. This is of particular importance where Emergency Retract buttons are supplied.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 7 of 29
5.1.1 Connection Cover Mounting (Optional)
If provided, the MK5 Connection Cover is to be mounted directly underneath the MK5 Control Panel so it is
flush up against it. Additional clearance will be required below the MK5 Control Panel to accommodate this.
The Connection Cover needs to be positioned to the far left on the MK5 Control Panel so that the cut out of
the enclosure fits around the foot of the MK5 to retain full access to the fuses on the right.
The Connection Cover comes with 4 Qty
fixing holes located inside the body of the
enclosure, the same fixings used on the MK5
Control Panel are to be used.
There are a total of 15 Qty knock out points
located around the sides and bottom of the
enclosure. These can be fitted with the
standard 20mm diameter cable glands.
Once the enclosure has been mounted and
all the cables secured, the lid can then be slid
over the top to sit underneath the MK5
Control Panel lid and be secured using the 2
Qty fixing holes.
Note: Please ensure there is suitable clearance on the right-hand side to maintain easy
access to the 3 Qty fuse holders.
5.1.2 BMS Interface Mounting (Optional)
If supplied, the MK5 BMS Interface unit will need to be mounted locally to the MK5 Control Panel. Two of
these Interfaces will be required for full BMS (Curtain status and Battery status).
The Interface unit will need to be installed
by using the 4 Qty 4mm diameter fixing
points inside the enclosure. M3 fixings are
to be used to install.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 8 of 29
5.2 Motor Cable Wiring
Warning - The following instructions involve working on a live electrical
230Vac system. The following shall only be carried out by
suitably qualified electrical persons that are approved and
certified to work on Coopers Fire Ltd. systems.
Ensure the Control Panel is fully isolated before proceeding.
Refer to the motor extension cable sizes in the table below as a guide. Note: This table is a guide only
and does not consider site specific requirements or correction factors.
Install the supplied 100 x
100mm adaptable box within 1
metre of the motor location.
Run the motor cable into the
100 x 100mm adaptable box
through the supplied 20mm
cable gland.
Note: It is important that 3
core plus earth (3C+E) motor
cable is used to extend the
motor cable. 2 core plus
earth (2C+E) cannot be used.
100 x 100mm
adaptable box
Motor cable
Terminate the 3 motor cables into a 3-way
piece of 15 Amp terminal block.
Join motor cables 1 to 1, 2 to 2 and 3 to 3.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 9 of 29
5.3 Setting Motor Direction
It is important that the motor directions are set before the system is powered up. This is to ensure that
the drive shaft is driven in the correct direction to raise or lower the system.
If the motor is descending in an anti-clockwise rotation: -
If the motor is descending in a clockwise rotation: -
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 10 of 29
6 Electrical Wiring & Connections
Warning - The following instructions involve working on a live electrical 230Vac system.
The following shall only be carried out by suitably qualified electrical persons that are
approved and certified to work on Coopers Fire Ltd. systems.
Ensure the Control Panel is fully isolated before proceeding.
This manual is for general guidance. Attention must be paid to any site-specific requirements as
detailed in the Fitters Pack.
Any external circuits, including the connection to the Fire Alarm system, must be separated from
hazardous mains circuits by reinforced insulation.
6.1 Power Supply Unit (PSU)
Isolation from the mains supply is provided by both the plug and IEC inlet.
The mains outlet socket must be earthed.
A detachable power cord of inadequate rating must not be used.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 11 of 29
6.2 ARM1 Alarm Connection
The ARM1 (Alarm Resistor Module) PCB needs to be fitted in series with the Alarm cable at the Fire Alarm
Interface end for the MK5 to detect and monitor the Alarm status. Note: All MK5 Version 3s require this
module to be installed or the display will read ‘Alarm Shorted’.
6.3 Single Smoke / Heat Detector
8K28K2
ARM1
CN1
8K2
ARM1
CN1
WHITE
WHITE BROWN (1)
BLUE (2)
NORMALLY OPEN HELD
CLOSED, VOLT FREE
CONTACT - OPEN ON
ACTIVATION OR FAILSAFE.
AA
NORMALLY OPEN HELD
CLOSED, VOLT FREE
CONTACT - OPEN ON
ACTIVATION OR FAILSAFE.
A
CABLE TO CONTROL UNIT
(FITTED WITH 3 PIN CONNECTOR)
8K2
ARM1
CN1
WHITE
WHITE BROWN (1)
BLUE (2)
NORMALLY OPEN HELD
CLOSED, VOLT FREE
CONTACT - OPEN ON
ACTIVATION OR FAILSAFE.
A
CABLE TO CONTROL UNIT
(FITTED WITH 3 PIN CONNECTOR)
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 12 of 29
6.4 Dual Detector
6.5 Standard / Residential Emergency Egress Button
The ERBRM2 (Emergency Retract Button Resistor Module) PCB needs to be fitted with any Emergency
Egress Button or Emergency Access Button / Fireman’s Emergency Access (as shown on the drawings).
This is needed to monitor the connection for short circuits. Note: Every MK5 control panel will require
this module alongside every Access or Egress Button.
BROWN (1)
ERB
YELLOW / GREEN (2)
BLUE (3)
BLUE NOT CONNECTED,
MUST BE ISOLATED
BLUE NOT CONNECTED,
MUST BE ISOLATED
ERB
BROWN (1)
YELLOW / GREEN (2)
LINK CABLE
(3 CORE AS SUPPLIED)
CABLE TO CONTROL UNIT
(FITTED WITH 3 PIN CONNECTOR)
R1
82k
ERBRM2
R1
82k
ERBRM2
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 13 of 29
6.6 Deluxe Emergency Egress Button
6.7 Emergency Access Button / Fireman’s Emergency
Access
BROWN (1)
YELLOW / GREEN (2)
BLUE (3)
BROWN (1)
YELLOW / GREEN (2)
LINK CABLE
(3 CORE AS SUPPLIED)
CABLE TO CONTROL UNIT
(FITTED WITH 3 PIN CONNECTOR)
Dip switches to be set as below:
1 + 2 = Off
3 + 4 = On
NC C NO - + E
ON
1 2 3 4
RED
BLACK
YELLOW
WHITE
GREY
BLUE (3)
Dip switches to be set as below:
1 + 2 = Off
3 + 4 = On
NC C NO - + E
ON
1 2 3 4
RED
BLACK
YELLOW
WHITE
GREY
R1
82k
ERBRM2
R1
82k
ERBRM2
BROWN (1)
YELLOW / GREEN (2)
BLUE (3)
BLUE NOT CONNECTED,
MUST BE ISOLATED
CABLE TO CONTROL UNIT
(FITTED WITH 3 PIN CONNECTOR)
R1
82k
ERBRM2
Firemans
Access
Switch
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 14 of 29
6.8 Residential Beam Detector
6.9 Light Curtain
Do not cut down the light curtain cables, any excess
must be securely stored within the head box.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 15 of 29
6.10 Voice Warning
6.11 Light Warning
BROWN (1)
BLUE (3)
YELLOW / GREEN (2)
CABLE TO CONTROL UNIT
(FITTED WITH 3 PIN CONNECTOR)
POS
POS
NEG
NEG
M1
M2
M3
M4
COM
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 16 of 29
6.12 BMS (Building Management System) Interface
7 Commissioning
7.1 Initial Setup
Commissioning should not be attempted until the installation of the headbox, roller, bottom
bar and side guides (if required) have been fitted and all required accessories have been
connected.
If at any time you are not happy with the settings or you want to start again, power the unit down
fully by removing the Battery Fuse and mains power lead, ensuring the curtain is in the deployed
position beforehand.
1) Ensure that all accessory devices are connected to the unit before commencing commissioning.
Do not fit the battery fuse until instructed by the display.
2) Once the curtain is fully deployed the MK5 can be turned on. Connect the mains lead.
The MK5 will commence its start-up procedure. This will take approximately 5 seconds.
The MK5 will display ‘Testing LEDs’ for a few seconds and all three LEDs will be lit.
The display changes to ‘Please insert battery fuse’. The unit will be beeping.
Fit the Battery fuse.
3) Assuming that the accessory fuse is ok the MK5 will display ‘Fuses OK’ for a few seconds. If the
accessory fuse is not in place or has blown, the MK5 will indicate this.
The display changes to one of the following:
All Relays are NC when unpowered.
RL2 + 3 open on activation.
Please note on BMS 1: RL1 is Normally Closed Held
open, Closed on fault or loss of power.
BMS 1 BMS 2
RL1
RL2
RL3
CURTAIN FAULT
CURTAIN UP
CURTAIN DOWN
BATTERY LOW
BATTERY DISCONNECTED
BATTERY FAULT
COM NO NC
RL1
COM NO NC
RL2
COM NO NC
RL3
Coil
RL1
Coil
RL2
Coil
RL3
CN1 CN2
RED
BLACK WHITE
YELLOW
CABLE TO CONTROL UNIT
(FITTED WITH 5 PIN CONNECTOR)
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 17 of 29
ALARM - YES
DETECTOR - NO
ALARM - YES
DETECTOR - YES
ALARM - NO
DETECTOR - YES
Or
‘No alarms found.’
If the message is ‘No alarms found.’ is displayed, it can be cleared by adding a suitable initiation
device, such as a fire alarm signal and/or local heat or smoke detector.
4) The MK5 display will now prompt you to set the correct motor type, by default this will be set to the
10Nm (White) motor type. This can be changed to the 30Nm (Red) motor type if needed.
The MK5 display now changes to:
‘IN MANUAL MODE.
AUTO press OK.’
DO NOT PRESS THE ‘OK’ BUTTON UNTIL INSTRUCTED BELOW AS THIS WILL EXIT THE
‘MANUAL MODE’.
While this mode is active the curtain can be raised and lowered using the up and down
pushbuttons. When you have finished operating the curtain in manual mode please return the
curtain to the fully descended position.
Press the OK button and the unit will enter AUTO mode and the display will change to read ‘IN
AUTO MODE.’ and display the date and time.
If all the Alarm / Detector(s) are OK, the curtain will retract.
It is important that the settings are done in sequence as some settings are affected by
others.
5) Accessing the Menu
To enter the menu, press and hold the OK button until the display changes to ‘Enter Code’.
The code for this unit is: 8421
To enter the code, use the and to set each digit before using the and buttons to change
digit. Once the correct number is displayed, press the OK button to enter the menu.
7.2 Critical Settings
6) Setting the Clock
Use the and buttons to navigate the menu and select ‘Set Clock.’ by pressing the OK button.
First set the year. Use the and buttons to select the correct year and press the OK button.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 18 of 29
Now set the month. Use the and buttons to select the correct month and press the OK button.
Now set the date. Use the and buttons to select the correct date and press the OK button.
Now set the day. Use the and buttons to select the correct day and press the OK button.
Now set the hours. Use the and buttons to select the correct hour and press the OK button.
Now set the minutes. Use the and buttons to select the correct minutes and press the OK
button.
The display will now show ‘Start Clock. OK.’. Press the OK button to start the clock.
7) Enable Auto Test
Under BS 8524, when installed in a Dwelling (Domestic) property, the unit must be capable of
performing an automated test cycle once a month and record the test.
By default, the MK5 is set to have the Auto Test enabled.
To disable the Auto Test when used in a commercial / industrial environment use the and
buttons to navigate the menu and select ‘Enable Auto Test’ by pressing the OK button.
The display will now show the current setting on the top line.
Use the and buttons to select the required mode and press the OK button to set.
Do not disable the Auto Test function in a Dwelling (Domestic) property without written
instruction from the Project Manager.
8) Setting the Auto Test Day and Time
The default setting is Monday at 12:00. To change the day or time of the Auto Test use the and
buttons to navigate the menu and select ‘Set Auto Test.’ by pressing the OK button.
First set the day. Use the and buttons to select the correct year and press the OK button.
Now set the hours. Use the and buttons to select the correct hour and press the OK button.
Now set the minutes. Use the and buttons to select the correct minutes and press the OK
button.
The display will now show ‘OK. To set.’. Press the OK button to confirm the settings.
9) Setting the Motor Type
This setting will have been completed during the start-up but can be changed at any point.
Use the and buttons to navigate the menu and select ‘Set motor type.’ by pressing the OK
button.
The display will now show the current setting on the top line.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 19 of 29
Select the motor required with the and buttons and press the OK button to select.
INCORRECT SETTING OF MOTOR, WIDTH OR BARREL CAN SERIOUSLY DAMAGE THE
UNIT.
10) Setting the Curtain Descent Speed
Deploy the curtain by using the and buttons to navigate the menu and select ‘Test Curtain’ by
pressing the OK button.
Press the button to deploy the curtain. Time the descent and assess it visually to ensure it is a
smooth operation.
Press the OK button to complete the test and raise the curtain.
Divide the curtain height (in m) by the descent time recorded above. This will give you your m/s
speed of the curtain.
In order to be compliant with BS 8524, the curtain must descend at a rate of between 0.06m/s and
0.15m/s.
Use the and buttons to navigate the menu and select ‘Descent Speed’ by pressing the OK
button.
The message ‘Please refer to manual’ will be displayed.
To clear the message ‘Please refer to manual’ and proceed with the adjustment, press the
button.
The descent speed can be adjusted from 0 to 15 with 0 being the fastest and 15 being the slowest.
The display will now show the current setting on the top line.
The descent speed default is 7. Using the and buttons, select the new value required. Once the
new value has been selected, press the OK button.
Repeat until the speed is satisfactory.
Once a satisfactory speed has been set, record both the ascent and descent times as
these will be required later.
11) Ascent Time
For the Auto Test function to know if the curtain has operated within the acceptable limits, the unit
must be told the expected ascent and descent times.
Use the and buttons to navigate the menu and select ‘Ascent Time’ by pressing the OK button.
Use the and buttons to set the correct time to the nearest second as recorded above and press
the OK button to confirm the setting.
12) Descent Time
Use the and buttons to navigate the menu and select ‘Descent Time’ by pressing the OK button.
Document Version 1
September 2019
© 2019 Coopers Fire Ltd.
Page 20 of 29
Use the and buttons to set the correct time to the nearest second as recorded above and press
the OK button to confirm the setting.
If SDD is required, add the required ‘pause’ time to this figure.
7.3 Optional Settings
13) Set Reset Mode
Use the and buttons to navigate the menu and select ‘Set reset mode’ by pressing the OK
button.
Press the button to enable Manual Reset and the button to enable Auto Reset. Press the OK
button to exit.
The selection of Manual or Auto reset applies to the ‘Alarm’ only. Smoke / Heat detectors
will always be Manual reset.
14) Set Emergency Retract Hold Time
Use the and buttons to navigate the menu and select ‘EmRet top time:’ by pressing the OK
button.
Use the and buttons to adjust the ‘pause’ time. Press the OK button to exit.
By default, this time is set to 5 seconds but should be increased accordingly to account
for the occupancy of the building as advised within the fire strategy. If no details have
been provided, contact the Project Manager.
15) Double Knock
Double Knock is not available with HDD.
Double knock requires 2 active alarm signals to deploy the curtain. By default, the unit will be set to
‘Any Alarm’.
Below are the available options:
Any Alarm
Curtain will deploy immediately on activation of either the Alarm, Detector 1
or Detector 2.
Alarm and Det1
Curtain will not deploy until activation of both Alarm AND Detector 1.
(Detector 2 not used).
Alarm and Det2
Curtain will not deploy until activation of both Alarm AND Detector 2.
(Detector 1 not used).
Det1 and Det2
Curtain will not deploy until activation of both Detector 1 AND Detector 2.
(Alarm not used).
Use the and buttons to navigate the menu and select ‘Double Knock:’ by pressing the OK
button.
Use the and buttons to select the required operation. Press the OK button to confirm and exit.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29

Coopers Variospeed MK5 V3 Technical Manual

Category
Fire protection
Type
Technical Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI