Legrand Doc Form: BMS Interface Module Automation Scenarios Installation guide

Type
Installation guide
Smartwired
Switching System
BMS Interface Module Automation Scenarios
Scenario Data Required Contact Definition
Scheduled ON/OFF Timed override duration (10-240 min) Source of Input (What system?)
Blink warn (YES/NO) Input Contact (Occupied = Open or Closed)
Egrees time (0, 1, 10-240 min) Status Contact (Closed = Any ON, All ON, All OFF, Any OFF)
Manual ON/Scheduled OFF Same as above Same as above
Dark ON/OFF Define “Dark” from 2 to 200 fc Status Contact (Closed = Any ON, All ON, All OFF, Any OFF)
Dark ON/Scheduled OFF Egress time (0, 1, 10-240 min) Source of Input (What system?)
Define “Dark” from 2 to 200 fc Input Contact (Occupied = Open or Closed)
Status Contact (Closed = Any ON, All ON, All OFF, Any OFF)
CHANNEL DESCRIPTION AUTOMATION DATA CONTACT
OF GROUP SCENARIO DEFINITION
SCHEDULED ON/OFF
MANUAL ON/SCHEDULED OFF
A
DARK ON/OFF
DARK ON/SCHEDULED OFF
SCHEDULED ON/OFF
MANUAL ON/SCHEDULED OFF
B
DARK ON/OFF
DARK ON/SCHEDULED OFF
SCHEDULED ON/OFF
MANUAL ON/SCHEDULED OFF
C
DARK ON/OFF
DARK ON/SCHEDULED OFF
SCHEDULED ON/OFF
MANUAL ON/SCHEDULED OFF
D
DARK ON/OFF
DARK ON/SCHEDULED OFF
SCHEDULED ON/OFF
MANUAL ON/SCHEDULED OFF
E
DARK ON/OFF
DARK ON/SCHED OFF
SCHEDULED ON/OFF
MANUAL ON/SCHEDULED OFF
F
DARK ON/OFF
DARK ON/SCHEDULED OFF
SCHEDULED ON/OFF
MANUAL ON/SCHEDULED OFF
G
DARK ON/OFF
DARK ON/SCHEDULED OFF
SCHEDULED ON/OFF
MANUAL ON/SCHEDULED OFF
H
DARK ON/OFF
DARK ON/SCHEDULED OFF
HID-SSBMS 070901Lighting Control Panels Santa Clara, CA 95050