Altronix eFlow104NA8 Series Installation guide

Type
Installation guide

Altronix eFlow104NA8 Series

The Altronix eFlow104NA8 Series is a dual output access power controller that provides up to eight independently controlled 12VDC or 24VDC protected outputs. These outputs can be used to power a variety of access control hardware devices, including mag locks, electric strikes, and magnetic door holders. The eFlow104NA8 Series also includes a built-in charger for sealed lead acid or gel type batteries, so that your system will continue to operate even in the event of a power outage.

Some of the key features of the eFlow104NA8 Series include:

  • Eight (8) selectable Fail Safe, Fail-Secure or Form “C” dry outputs

Altronix eFlow104NA8 Series

The Altronix eFlow104NA8 Series is a dual output access power controller that provides up to eight independently controlled 12VDC or 24VDC protected outputs. These outputs can be used to power a variety of access control hardware devices, including mag locks, electric strikes, and magnetic door holders. The eFlow104NA8 Series also includes a built-in charger for sealed lead acid or gel type batteries, so that your system will continue to operate even in the event of a power outage.

Some of the key features of the eFlow104NA8 Series include:

  • Eight (8) selectable Fail Safe, Fail-Secure or Form “C” dry outputs
eFlow104NKA8
- 12VDC or 5VDC up to 6A and/or 24VDC up to 10A (240W total power) selectable by output.
- Eight (8) fuse protected outputs.
- Eight (8) selectable Fail Safe, Fail-Secure or Form “C” dry outputs
- Fire Alarm Disconnect selectable by output
- Built-in Charger for sealed lead acid or gel type batteries
eFlow104NKA8D
- 12VDC or 5VDC up to 6A and/or 24VDC up to 10A (240W total power) selectable by output.
- Eight (8) Class 2 power-limited PTC protected outputs.
- Eight (8) selectable Fail Safe, Fail-Secure or Form “C” dry outputs.
- Fire Alarm Disconnect selectable by output.
- Built-in Charger for sealed lead acid or gel type batteries.
eFlow104NA8 Series
Dual Output Access Power Controllers
Models Include:
Rev. eFlow104NKA8-072220 More than just power.TM
Installing Company: _______________ Service Rep. Name: __________________________________
Address: _____________________________________________ Phone #: __________________
Installation Guide
- 2 - eFlow104NKA8(D) Installation Guide
Overview:
Altronix eFlow104NKA8 and eFlow104NKA8D distribute and switch power to access control systems and accesso-
ries. They convert a 120VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC protected outputs.
Access Power Controller’s dual input design allows power to be steered from two (2) factory installed independent
low voltage 12 or 24VDC Altronix power supplies to eight (8) independently controlled fuse (eFlow104NKA8) or
PTC (eFlow104NKA8D) protected outputs. Power outputs can be converted to dry form “C” contacts. Outputs are
activated by an open collector sink, normally open (NO), normally closed (NC) dry trigger input, or wet output from
an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. eFlow104NKA8(D) will route power to
a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc.
Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress,
Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually
selectable for any or all of the eight (8) outputs. The spade connectors allow you to daisy chain power to multiple
ACMS8(CB) modules. This feature allows you to distribute the power over more outputs for larger systems.
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH 0.4A/10A N/A 5 Mins./10A
12AH 1A/10A 0.3A/10A 15 Mins./10A
40AH 6A/10A 1.2A/10A Over 2 Hours/10A
65AH 6A/10A 1.5A/10A Over 4 Hours/10A
eFlow104NKA8(D) Installation Guide - 3 -
Specifications:
Inputs:
eFlow104NB:
• 120VAC, 60Hz, 4.5A.
ACMS8/ACMS8CB:
Eight (8) trigger inputs:
a) Normally open (NO) inputs (dry contacts).
b) Normally closed (NC) inputs (dry contacts).
c) Open collector sink inputs.
d) Wet Input (5VDC - 24VDC) with 10K resistor
e) Any combination of the above.
Outputs:
Power:
• 12VDC or 5VDC up to 6A, 24VDC up to 10A
(240W total power).
• Auxiliary Class 2 power-limited output
rated @ 1A (unswitched).
• Overvoltage protection.
ACMS8:
• Fuse protected outputs rated @ 2.5A per output,
non power-limited. Total output 6A max.
Do not exceed the individual power supply ratings.
ACMS8CB:
• PTC protected outputs rated @ 2A per output,
Class 2 power-limited. Total output 6A max.
Do not exceed the individual power supply ratings.
Eight (8) selectable independently controlled
outputs or eight (8) indepently controlled
Form “C” relay outputs (see below for ratings):
a) Fail-Safe and/or Fail-Secure power outputs.
b) Form “C” relays rated @ 2.5A. 12, 24VDC,
0.6 Power Factor (ACMS8 only).
c) Auxiliary power outputs (unswitched).
d) Any combination of the above.
Individual outputs may be set to OFF position for
servicing (output jumper set to middle position).
Does not apply to Dry Contact applications.
Any of the eight (8) fuse/PTC protected power
outputs are selectable to follow power Input 1 or
Input 2. Output voltage of each output is the same
as the input voltage of the input selected.
Surge suppression.
Fuse/PTC Ratings:
eFlow104NB:
- Input fuse is rated 6.3A/250V.
- Battery fuse rated 15A/32V.
ACMS8:
- Main input fuse is rated 15A/32V.
- Output fuses are rated 3A/32V.
ACMS8CB:
- Main input PTC is rated 9A.
- Output PTCs are rated 2A.
Battery Backup (eFlow104NB):
• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 1.54A.
• Automatic switch over to stand-by battery when
AC fails.
Transfer to stand-by battery power is instantaneous
with no interruption.
Supervision (eFlow104NB):
• AC fail supervision (form “C” contacts).
• Battery fail & presence supervision
(form “C” contacts).
• Low power shutdown. Shuts down DC output
terminals if battery voltage drops below 71-73% for
12V units and 70-75% for 24V units (depending on
the power supply). Prevents deep battery discharge.
Fire Alarm Disconnect:
eFlow104NB:
• Supervised Fire Alarm disconnect (latching or
non-latching) 10K EOL resistor. Operates on a
normally open (NO) or normally closed (NC) trigger.
ACMS8(CB):
Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open [NO] or normally closed [NC]
dry contact input. Polarity reversal input from
FACP signaling circuit.
FACP input WET is rated 5-30VDC 7mA.
FACP input EOL requires 10K end of line resistor.
FACP output relay [NC]:
Either Dry 1A/28VDC, 0.6 Power Factor or
10K resistance with [EOL JMP] intact.
Visual Indicators:
eFlow104NB:
Green AC LED: Indicates 120VAC present.
Red DC LED: Indicates DC output.
ACMS8(CB):
Red LEDs: Indicate outputs are triggered.
Blue LED: Indicates FACP disconnect
is triggered.
Individual
Voltage LEDs: Indicate 12VDC (Green) or
24VDC (Red).
Environmental:
• Operating temperature: 0ºC to 49ºC ambient.
• Humidity: 20 to 85%, non-condensing.
Enclosure Dimensions (approximate H x W x D):
15.5” x 12” x 4.5”
(393.7mm x 304.8mm x 114.3mm).
- 4 - eFlow104NKA8(D) Installation Guide
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, the Canadian
Electrical Code and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in
the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the
enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two
holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper
keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 8). Secure enclosure to earth ground.
2. Ensure all output jumpers [PWR1] - [PWR8] are placed in the
OFF (center) position (Fig. 1, pg. 3).
3. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N]
(Fig. 4a, pg. 5). Green “AC” LED on power supply board will turn on. This light
can be seen through the LED lens on the door of the enclosure. Use 14 AWG or
larger for all power connections. Secure green wire lead to earth ground.
Keep power-limited wiring separate from non power-limited wiring
(120VAC 60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before
installing or servicing equipment. There are no user serviceable parts inside.
Refer installation and servicing to qualified service personnel.
4. Set each output [OUT1] - [OUT8] to route power from Input 1 or 2 (Fig. 1, pg. 3).
Note: Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Turn power off before connecting devices.
6. Output options: eFlow104NKA8(D) will provide up to eight (8) switched power outputs or eight (8) dry
form “C” outputs, or any combination of both switched power and form “C” outputs, plus eight (8)
unswitched auxiliary power outputs.
Switched Power outputs:
Connect the negative (–) input of the device being powered to the terminal marked [COM].
For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal
marked [NC].
For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal
marked [NO].
Form “C” outputs:
When form “C” outputs are desired, the corresponding jumper (1-8) must be placed in the OFF position
(Fig. 7, pg. 9). Alternatively, the corresponding output fuse (1-8) can be removed (eFlow104NKA8 only).
Connect negative (–) of the power supply directly to the locking device.
Connect the positive (+) of the power supply to the terminal marked [C].
For Fail-Safe operation connect the positive (+) of the device being powered to the terminal marked [NC].
For Fail-Secure operation connect the positive (+) of the device being powered to the terminal marked [NO].
Dry contacts rated @ 2.5A, 28VDC.
Auxiliary Power outputs (unswitched):
Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (–)
of the device being powered to the terminal marked [COM]. Output can be used to provide power for
card readers, keypads etc.
7. Turn main power on after all devices are connected.
8. Input Trigger options:
Note: If Fire Alarm disconnect is not used, connect a 10K ohm resistor to terminals marked
[GND and EOL], plus connect a jumper to terminals marked [GND, RST].
Normally Open (NO) Input:
Slide input control logic DIP switch into the OFF position for [Switch 1-8]
(Fig. 2, on right). Connect your wires to terminals marked
[+ INP1 –] to [+ INP8 –].
Normally Closed (NC) Input:
Slide input control logic DIP switch into the ON position for [Switch 1-8]
(Fig. 2, on right). Connect your wires to terminals marked [+ INP1 –] to [+ INP8 –].
PWR1
PWR2
OFF
Fig. 1
1
2
3
4
INP Logic
NC <-> NO
ON
Fig. 2
eFlow104NKA8(D) Installation Guide - 5 -
Open Collector Sink Input:
Connect the open collector sink input to the terminal marked [+ INP1 –] to [+ INP8 –].
Wet (Voltage) Input Configuration:
Carefully observing polarity, connect the voltage input trigger wires and the supplied 10K resistor to
terminals marked [+ INP1 –] to [+ INP8 –].
If applying voltage to trigger input - set the corresponding INP Logic switch to the “OFF” position
If removing voltage to trigger input - set the corresponding INP Logic switch to the “ON” position.
9. Fire Alarm Interface options:
A normally closed [NC], normally open [NO] input or polarity reversal input from
FACP signaling circuit will trigger selected outputs. To enable FACP Disconnect for
an output turn the corresponding DIP switch [SW1-SW8] ON.
To disable FACP disconnect for an output turn the corresponding DIP switch
[SW1-SW8] OFF. Switch is located directly to the left of the
Fire Alarm Interface Terminals.
Normally Open Input:
Wire your FACP relay and 10K resistor in parallel on terminals marked
[GND] and [EOL].
Normally Closed Input:
Wire your FACP relay and 10K resistor in series on terminals marked [GND] and [EOL].
FACP Signaling Circuit Input Trigger:
Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked
[+ FACP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an
alarm condition).
Non-Latching Fire Alarm Disconnect: Connect a jumper to the terminals marked [GND, RST].
Latching Fire Alarm Disconnect: Connect a NO normally open reset switch to terminals marked [GND, RST].
10. FACP Dry NC output:
Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NC] and [C].
When [EOL JMP] is kept intact, the output is of 0 Ohm resistance in a normal condition.
When [EOL JMP] is clipped, a 10k resistance will be passed to next device when in a normal condition.
11. Stand-by Battery Connections (Fig. 6, pg. 8):
For U.S. Access Control applications batteries are optional. Batteries are required for Canadian installations
(ULC-S319). When batteries are not used, a loss of AC will result in the loss of output voltage.
When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect battery to terminals marked [– BAT +] (Fig. 4g, pg. 6). Use two (2) 12VDC batteries connected in
series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120
(12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 and
BAZR8 batteries of an appropriate rating.
12. Battery and AC Supervision outputs (Fig. 4, pg. 8):
It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT Fail]
supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices.
Use 22 AWG to 18 AWG for AC Fail & Low/No Battery reporting.
13. To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position (Fig. 4c, pg. 6).
To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position (Fig. 4c, pg. 6).
14. Fire Alarm Disconnect (Fig. 4c, pg. 6):
To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position.
To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position.
15. Installation of tamper switch:
Mount UL Listed tamper switch (Altronix model TS112 or equivalent) at the top of the enclosure. Slide the
tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 6a, pg. 8).
Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting
device. To activate alarm signal open the door of the enclosure.
Wiring:
Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).
Fig. 3
FACP
EN <-- > DIS
1
2
3
4
ON
- 6 - eFlow104NKA8(D) Installation Guide
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper
voltage level eFlow104NB: 24VDC nominal rated @ 10A max.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage
(24VDC @ 26.4) both at battery terminal and at the board terminals marked [– BAT +] to ensure that there is no
break in the battery connection wires.
Note: Maximum charging current under discharges is 1.54A.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Fig. 4 - eFlow104N Board Configuration
4a 4b
4g
4h
4e 4f4d4c
– DC +– BAT +
L G N NC C NO NC C NO
AC FAIL BAT FAIL
TRIGGER EOL
SUPERVISED
AC DCAC1 NO GND
RESET + AUX -
1 min enable
2 hr disable
NC C NO NC C NO
BAT FAILAC FAIL
POWER
SOURCE
RED INDICATING
LAMP
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Trouble/Time Limited Warning of Stand-by Batteries:
For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annun-
ciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by
battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a UL Listed
Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Fig. 5 - Battery trouble indication
For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure.
Wire one leg of a UL Listed, power-limited power source to the indicating lamp.
Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact termi-
nals marked [BAT FAIL - C, NO] (Fig. 5, pg. 6).
eFlow104NKA8(D) Installation Guide - 7 -
LED Diagnostics:
eFlow104NB Power Supply/Charger
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery is supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
ACMS8 and ACMS8CB Access Power Controller
LED ON OFF
LED 1- LED 8 (Red) Output relay(s) de-energized. Output relay(s) energized.
FACP FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Green Output 1-8 12VDC –
Red Output 1-8 24VDC –
Terminal Identification:
eFlow104NB Power Supply/Charger
Terminal Legend Function/Description
L, N Connect 120VAC 60Hz to these terminals: L to hot, N to neutral (non power-limited)
(Fig. 4a, pg. 6).
– DC + 24VDC nominal @ 10A continuous output (non power-limited output) (Fig. 4h, pg. 6).
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (power-limited input) (Fig. 4d, pg. 6).
NO, GND RESET FACP interface latching or non-latching (power-limited) (Fig. 4e, pg. 6).
+ AUX – Auxiliary Class 2 power-limited output rated @ 1A (unswitched) (Fig. 4f, pg. 6).
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited) (Fig. 4b, pg. 6).
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Fig. 4b, pg. 6).
– BAT + Stand-by battery connections. Maximum charge current 1.54A (non power-limited)
(Fig. 4g, pg. 6).
ACMS8 and ACMS8CB Access Power Controller
Terminal Legend Function/Description
+ PWR1 Factory connected to eFlow104NB. Do not use these terminals.
+ PWR2 Factory connected to VR6 voltage regulator. Do not use these terminals.
+ INP1 – through
+ INP8 –
Eight (8) independently controlled Normally Open (NO), Normally Closed (NC),
Open Collector Sink or Wet Input Triggers.
C, NC FACP Dry NC output rated 1A/28VDC @ 0.6 Power Factor. Class 2 power-limited.
With EOL JMP intact, will provide 10k resistance in a normal state.
GND, RST FACP interface latching or non-latching. NO dry input. Class 2 power-limited.
To be shorted for non-latching FACP interface or Latch FACP reset.
GND, EOL EOL Supervised FACP Input terminals for polarity reversal FACP function.
Class 2 power-limited.
F, + F, – R, + R FACP Signaling Circuit Input and Return terminals. Class 2 power-limited.
Output 1 through
Output 8
NO, C, NC, COM
Eight (8) selectable independently controlled outputs [Fail-Safe (NC) or Fail-Secure
(NO)] and eight (8) independently controlled Form “C” Relay outputs.
- 8 - eFlow104NKA8(D) Installation Guide
Fig. 6 - eFlow104NKA8(D)
Supervision and
FACP Interface
(power-limited)
DC Output to devices
(eFlow104NKA8 - non power-limited, eFlow104NKA8D - power-limited)
Independently controlled Input Triggers
PTC
Protected
Outputs on
eFlow104NKA8D
PWR1 +
PWR2 +
COM -
COM -
PWR2 +
PWR1 +
+ PWR2 --
+ PWR1 --
INP Logic
NO <--> NC
FACP
EN <--> DIS FACP
FACP
FACP
Power 2
Power 1
+INP2--+INP1--+INP3-- +INP4-- +INP5-- +INP6-- +INP7-- +INP8--
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
ONON
NC RST EOL +F +R
C GND GND -F -R
NO C NC COM NO C NC COM
Output 1Output 2
NO C NC COM NO C NC COM
Output 3Output 4
NO C NC COM NO C NC COM
Output 5 Output 6
NO C NC COM NO C NC COM
Output 7 Output 8
eFlow104NB
Power Supply
– DC +– BAT +
L G N
Tamper Switch
ACMS8(CB)
Power Output
Factory wired to
ACMS8(CB) and VR6
(non power-limited)
24VDC from
eFlow104NB
12VDC from VR6
(mounted under
ACMS8(CB)
Battery Output
(non power-limited)
Optional Rechargeable Stand-by Battery
for UL294 Applications
Note: 12V batteries required for
ULC-S319 installations.
Optional Rechargeable Stand-by Battery
for UL294 Applications
Note: 12V batteries required for
ULC-S319 installations.
CAUTION: Use two (2) 12VDC stand-by batteries.
Keep power-limited wiring separate from non power-limited.
Use minimum 0.25” spacing.
12AH Rechargeable batteries are the largest batteries that
can fit in this enclosure.
A UL listed external battery enclosure must be used if using
40AH or 65AH batteries.
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Fig. 6a
eFlow104NKA8(D) Installation Guide - 9 -
Typical Application Diagram:
Fig. 7
OUT1
RISK OF FIRE REPLACE FUSES WITH SAME TYPE AND RATING
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
PWR1+
PWR1
PWR1<-- > PWR2
PWR1<-- > PWR2
PWR1<-- > PWR2
PWR1<-- > PWR2
PWR1<-- > PWR2
INP Logic
NC <-- > NO
FACP
EN <-- > DIS
FACP
PWR2+
Power 2
Power 1
+INP2--+INP1-- +INP3-- +INP4-- +INP5-- +INP6-- +INP7-- +INP8--
15
3
3
3
3
3
3
3
3
ACMS8
ACMS8CB
Altronix Corp.
Brooklyn, NY 11220
1
2
3
4
ON
15
PWR1+
PWR2+
COM--
COM--
5
6
7
8
1
2
3
4
5
6
7
8
ON
ONON
PWR2
OFF
+PWR1-- +PWR2--
NO C NC COM NO C NC COM
Output 1 Output 2
NO C NC COM NO C NC COM
Output 3 Output 4
NO C NC COM NO C NC COM
Output 5 Output 6
NO C NC COM NO C NC COM
Output 7 Output 8
FACP
FACP
EOL JMP
NC RST EOL +F +R
C GND GND -F -R
NC
NO
C
Normally Open (N.O.)
Door Releasing Device
Access Control Panel
Output
Relay
Mag. Lock
Electric
Strike
Electromagnetic
Door Holders
DC
Power
Supply
(optional)
DC
Power
Supply
(req'd.)
FACP
(Fire Alarm
Control
Panel)
ACMS8CBACMS8
3
- 10 - eFlow104NKA8(D) Installation Guide
Hook-Up Diagrams:
Fig. 8 - Daisy-chaining one or more ACMS8(CB) units.
EOL Jumper [EOL JMP] should be installed in the EOL position. Non-Latching.
Fig. 9 - Daisy-chaining one or more ACMS8(CB) units.
EOL Jumper [EOL JMP] should be installed in the EOL position. Latching Single Reset.
FACP
FACP
NC RST EOL +F +R
C GND GND -F -R
FACP
FACP
JumperJumper
NC RST EOL +F +R
C GND GND -F -R
EOL JMPEOL JMP
FACP
FACP
NC RST EOL +F +R
C GND GND -F -R
FACP
FACP
Jumper
NC RST EOL +F +R
C GND GND -F -R
EOL JMPEOL JMP
N.O.
Switch
FACP
FACP
NC RST EOL +F +R
C GND GND -F -R
FACP
FACP
NC RST EOL +F +R
C GND GND -F -R
EOL JMPEOL JMP
N.O.
Switch
N.O.
Switch
Fig. 10 - Daisy chaining one or more ACMS8(CB) units.
EOL Jumper [EOL JMP] should be installed in the EOL position. Latching Individual Reset.
eFlow104NKA8(D) Installation Guide - 11 -
Fig. 11 - Polarity reversal input from FACP
signaling circuit output (polarity is
referenced in alarm conditiion).
Non-Latching.
Fig. 12 - Polarity reversal input from FACP
signaling circuit output (polarity is
referenced in alarm condition).
Latching.
Hook-Up Diagrams:
FACP
FACP
10K
EOL
NC RST EOL +F +R
C GND GND -F -R
Jumper
Fig. 13 - Normally Closed trigger input
(Non-Latching).
FACP
FACP
10K
EOL
NC RST EOL +F +R
C GND GND -F -R
N.O.
Switch
Fig. 14 - Normally Closed trigger input
(Latching).
FACP
FACP
NC RST EOL +F +R
C GND GND -F -R
N.O.
Switch
Jumper
EOL
Fig. 15 - Normally Open trigger input
(Non-Latching).
FACP
FACP
NC RST EOL +F +R
C GND GND -F -R
N.O.
Switch
EOL
N.O.
Switch
Fig. 16 - Normally Open trigger input
(Latching).
FACP
FACP
+ --
Jumper
EOL
NC RST EOL +F +R
C GND GND -F -R
10K EOL
FACP
FACP
N.O.
Switch
NC RST EOL +F +R
C GND GND -F -R
+ --
EOL
10K EOL
- 12 - eFlow104NKA8(D) Installation Guide
1.5”
(38.1mm)
1.5”
(38.1mm)
4.615” (117.2mm) 4.615” (117.2mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
4.615” (117.2mm) 4.615” (117.2mm)
1.75”
(44.5mm)
1.75”
(44.5mm)
1.375”
(34.9mm)
1.125”
(28.6mm)
1.5”
(38.1mm)
1.5”
(38.1mm)
5.0” (127.0mm)
5.0” (127.0mm)
4.5” (114.3mm)4.5” (114.3mm) 1.25”
(31.8mm)
1.25”
(31.8mm)
0.79” (20.1mm)0.91”
(23.1mm)
0.91”
(23.1mm)
15.5” (393.7mm)
1.1”
(27.9mm)
1.1”
(27.9mm)
1.1”
(27.9mm)
12.23” (310.6mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
1.25” (31.8mm)1.25” (31.8mm)
Enclosure Dimensions (BC400):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Altronix is not responsible for any typographical errors.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IIeFlow104NKA8(D) G29U MEMBER
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Altronix eFlow104NA8 Series Installation guide

Type
Installation guide

Altronix eFlow104NA8 Series

The Altronix eFlow104NA8 Series is a dual output access power controller that provides up to eight independently controlled 12VDC or 24VDC protected outputs. These outputs can be used to power a variety of access control hardware devices, including mag locks, electric strikes, and magnetic door holders. The eFlow104NA8 Series also includes a built-in charger for sealed lead acid or gel type batteries, so that your system will continue to operate even in the event of a power outage.

Some of the key features of the eFlow104NA8 Series include:

  • Eight (8) selectable Fail Safe, Fail-Secure or Form “C” dry outputs

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI