Danfoss ECL Comfort 210, A267 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 210, A267 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort210,applicationA267
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................5
2.1Beforeyoustart.....................................................5
2.2Identifyingthesystemtype.......................................8
2.3Mounting...........................................................14
2.4Placingthetemperaturesensors................................18
2.5Electricalconnections.............................................20
2.6InsertingtheECLApplicationKey..............................25
2.7Checklist............................................................31
2.8Navigation,ECLApplicationKeyA267.........................32
3.0Dailyuse.........................................................36
3.1Howtonavigate...................................................36
3.2Understandingthecontrollerdisplay..........................37
3.3Ageneraloverview:Whatdothesymbolsmean?...........41
3.4Monitoringtemperaturesandsystem
components........................................................42
3.5Influenceoverview................................................43
3.6Manualcontrol.....................................................44
3.7Schedule............................................................45
4.0Settingsoverview............................................46
5.0Settings...........................................................48
5.1IntroductiontoSettings..........................................48
5.2Flowtemperature..................................................49
5.3Roomlimit..........................................................52
5.4Returnlimit.........................................................54
5.5Optimization........................................................60
5.6Controlparameters................................................67
5.7Application.........................................................71
5.8Heatcut-out........................................................81
5.9Tanktemperature..................................................84
5.10Anti-bacteria........................................................87
6.0Commoncontrollersettings..............................89
6.1Introductionto‘Commoncontrollersettings................89
6.2Time&Date.........................................................90
6.3Holiday..............................................................91
6.4Inputoverview.....................................................93
6.5Log...................................................................94
6.6Outputoverride....................................................95
6.7Keyfunctions.......................................................96
6.8System...............................................................98
7.0Miscellaneous................................................105
7.1ECA30/31setupprocedures.................................105
7.2Overridefunction................................................113
7.3Severalcontrollersinthesamesystem......................116
7.4Frequentlyaskedquestions....................................119
7.5Definitions........................................................122
7.6Type(ID6001),overview.......................................125
7.7ParameterIDoverview..........................................126
©Danfoss|2017.10VI.GU.G2.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisInstallationGuideisassociatedwithECLApplicationKeyA267
(ordercodeno.087H3816).
ThefunctionscanberealizedinECLComfort210aswellasECL
Comfort310.IftheA267keyisusedintheECLComfort310,the
functionalityremainsasintheECLComfort210.
TheapplicationA267complieswithECLComfortcontroller210
and310asofsoftwareversion1.11(visibleatstart-upofthe
controllerandin‘Commoncontrollersettings’in‘System’).
AdditionaldocumentationforECLComfort210andaccessoriesis
availableonwww.ecl.doc.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
2|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
VI.GU.G2.02
©Danfoss|2017.10|3
OperatingGuideECLComfort210,applicationA267
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
4|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
2.0Installation
2.1Beforeyoustart
TheapplicationA267isveryflexible.Thesearethebasicprinciples:
Heating(circuit1):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1).
Thelowertheoutdoortemperature,thehigherthedesiredflow
temperature.Bymeansofaweekschedule(upto3‘Comfort’
periods/day),theheatingcircuit1canbein‘Comfortor
‘Saving’mode(twodifferenttemperaturevaluesfordesiredroom
temperature).
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
Thereturntemperature(S5)tothedistrictheatingsupplyshould
notbetoohigh.Ifso,thedesiredflowtemperaturecanbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingofthe
motorizedcontrolvalve.
Furthermore,thereturntemperaturelimitationcandepend
ontheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Ifthemeasuredroomtemperature(S7)doesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Thecirculationpump(P1)isONatheatdemandoratfrost
protection.Thecirculationpump(P1)canbeswitchedOFF
whenheatingtheDHW(dependentpriority).Ifthesystemhas
achangeovervalve(P2)betweentheheatingandDHWheating
circuit,thecirculationpump(P1)isONwhenheatingtheDHW.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
TypicalA267application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
S1
Outdoortemperaturesensor
S2
Returntemperaturesensor,circuit2
S3
Flowtemperaturesensor,circuit1
S4
Flowtemperaturesensor,circuit2
S5
Returntemperaturesensor,circuit1
S6
DHWtanktemperaturesensor,upper
S7
Roomtemperaturesensor,circuits1and2
S8
DHWtanktemperaturesensor,lower
P1
Circulationpump,heating,circuit1
P2
DHWheatingpump,circuit3
P3
DHWcirculationpump,circuit3
P4
Circulationpump,heating,circuit2
M1
Motorizedcontrolvalve,circuits1and3
M2
Motorizedcontrolvalve,circuit2
VI.GU.G2.02
©Danfoss|2017.10|5
OperatingGuideECLComfort210,applicationA267
Heating(circuit2):
Thiscircuitworksaftersameprinciplesascircuit1.
TheflowtemperaturesensorS4isthemostimportantsensor.
Bymeansofaweekschedule(upto3Comfortperiods/day),the
heatingcircuit2canbeinComfortor‘Savingmode(twodifferent
temperaturevaluesfordesiredroomtemperature).Themotorized
controlvalveM2controlsthecircuit.
Thereturntemperature(S2)enableslimitationasdescribed
previously.
IfthemeasuredroomtemperatureS7doesnotequalthedesired
roomtemperature,thedesiredflowtemperaturecanbeadjusted.
Thecirculationpump(P4)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Heatingcircuit2canbeconnectedafterheatingcircuit1.Ifso,the
desiredflowtemperatureatS3canbeinfluencedbythedesired
flowtemperatureatS4.
Heatingcircuits1and2:
Theheatingcircuits1and2canusethesameroomtemperature
sensor(S7).However,eachheatingcircuitcanhaveanECA30,
RemoteControlUnit,inordertohaveseparateroomtemperature
signals.Anothersolution:UseS7foroneoftheheatingcircuitsand
ECA30fortheotherheatingcircuit.
A267.1examplea:
A267.1exampleb:
A267.1examplec:
6|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
DomesticHotWater(DHW,circuit3):
Bymeansofaweekschedule(upto3Comfortperiods/day),the
DHWcircuitcanbeinComfortor‘Saving’mode(twodifferent
temperaturevaluesfordesiredDHWtemperature).
IfthemeasuredDHWtemperature(S6)islowerthanthedesired
DHWtemperature,theheatingcirculationpump(P1)canbe
switchedOFFandtheDHWheatingpump(P2)isswitchedON.The
motorizedcontrolvalve(M1)iscontrolledinordertomaintainthe
DHWheatingtemperatureatS3.
TheDHWheatingtemperatureistypically10-15degreeshigher
thanthedesiredDHWtemperature.
DHWtankwith1temperaturesensor:
WhenthemeasuredDHWtemperature(S6)getshigherthanthe
desiredDHWtemperature,theDHWheatingpump(P2)isswitched
OFF.Apost-runtimecanbeset.Themotorizedcontrolvalve(M1)
willhereaftermaintainthedesiredflowtemperatureintheheating
circuit.
DHWtankwith2temperaturesensors:
WhenthemeasuredDHWtemperature(S6)getshigherthanthe
desiredDHWtemperatureandthelowertemperature(atS8)gets
higherthanthecut-outtemperature,theDHWheatingpump(P2)
isswitchedOFF.Apost-runtimecanbeset.Themotorizedcontrol
valve(M1)willhereaftermaintainthedesiredflowtemperaturein
theheatingcircuit.
A267.1exampled:
A267.1examplee:
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
VI.GU.G2.02
©Danfoss|2017.10|7
OperatingGuideECLComfort210,applicationA267
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
A267.1,examplea
Indirectlyconnectedsystemwith2heatingcircuitsandsecondarilyconnectedDHWtankwithinternalheatexchanger(optionalDHW
priority).
8|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
SpecialsettingsfortypeA267.1,examplea:
DHWcircuit(circuit3)
TheDHWheatingiscontrolledbymeansofDHWheatingpumpP2.
Navigation:IDno.:
Recommendedsetting:
MENU\Settings\Application:'Ch.-o.valve/P'
13051
ON
TheDHWtankisconnectedsecondarily.
MENU\Settings\Application:Tank,sec./prim.'
13053
OFF
VI.GU.G2.02
©Danfoss|2017.10|9
OperatingGuideECLComfort210,applicationA267
A267.1,exampleb
Indirectlyconnectedsystemwith2heatingcircuitsandsecondarilyconnectedDHWtankwithinternalheatexchanger(DHWpriority).
SpecialsettingsfortypeA267.1,exampleb:
DHWcircuit(circuit3)
TheDHWheatingiscontrolledbymeansofchangeovervalve*P2.
Navigation:IDno.:
Recommendedsetting:
MENU\Settings\Application:'Ch.-o.valve/P'
13051
OFF
TheDHWtankisconnectedsecondarily.
MENU\Settings\Application:Tank,sec./prim.'
13053
OFF
*
Thechangeovervalvecanbeofthistype:
DanfossAMZ113
Normalpowersupplied.Whenthecontrolvoltageisapplied(fromterminal12),thechangeovervalvechangesflowdirection.
10|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
A267.1,examplec
Indirectlyconnectedsystemwith2heatingcircuitsandprimarilyconnectedDHWtankwithinternalheatexchanger(optionalDHW
priority).
SpecialsettingsfortypeA267.1,examplec:
DHWcircuit(circuit3)
TheDHWheatingiscontrolledbymeansofON/OFFvalve*P2.
Navigation:
IDno.:
Recommendedsetting:
MENU\Settings\Application:'Ch.-o.valve/P'
13051
ON
TheDHWtankisconnectedsecondarily.
MENU\Settings\Application:Tank,sec./prim.
13053
ON
*
Thechangeovervalvecanbeofthistype:
DanfossAMZ113
Normalpowersupplied.Whenthecontrolvoltageisapplied(fromterminal12),thechangeovervalvechangesflowdirection.
VI.GU.G2.02
©Danfoss|2017.10|11
OperatingGuideECLComfort210,applicationA267
A267.1,exampled
Indirectlyconnectedsystemwith2heatingcircuits(circuit2isconnectedassubcircuit)andsecondarilyconnectedDHWtankwith
internalheatexchanger(optionalDHWpriority).
SpecialsettingsfortypeA267.1,exampled:
Heatingcircuit1
Heatingcircuit1mustreceiveinformationaboutandreactonthedesiredflowtemperaturefromheatingcircuit2.
Navigation:IDno.:
Recommendedsetting:
MENU\Settings\Application:'Demandoffset'
11017
5K*
*
Thedesiredflowtemperatureinheatingcircuit1is5Kabovethedesiredflowtemperatureinheatingcircuit2.
Heatingcircuit2
Heatingcircuit2isconnectedsecondarilyandmustsendinformationaboutitsdesiredflowtemperaturetoheatingcircuit1.
Navigation:IDno.:
Recommendedsetting:
MENU\Settings\Application:'SenddesiredT'
12500
ON
DHWcircuit(circuit3)
TheDHWheatingiscontrolledbymeansofDHWheatingpumpP2.
Navigation:IDno.:
Recommendedsetting:
MENU\Settings\Application:'Ch.-o.valve/P'
13051
ON
TheDHWtankisconnectedsecondarily.
MENU\Settings\Application:Tank,sec./prim.'
13053
OFF
12|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
A267.1,examplee
Indirectlyconnectedsystemwith2heatingcircuits(circuit2isconnectedassubcircuit)andprimarilyconnectedDHWtankwith
internalheatexchanger(optionalDHWpriority).
SpecialsettingsfortypeA267.1,examplee:
Heatingcircuit1
Heatingcircuit1mustreceiveinformationaboutandreactonthedesiredflowtemperaturefromheatingcircuit2.
Navigation:
IDno.:
Recommendedsetting:
MENU\Settings\Application:'Demandoffset'
11017
5K*
*
Thedesiredflowtemperatureinheatingcircuit1is5Kabovethedesiredflowtemperatureinheatingcircuit2.
Heatingcircuit2
Heatingcircuit2isconnectedsecondarilyandmustsendinformationaboutitsdesiredflowtemperaturetoheatingcircuit1.
Navigation:
IDno.:
Recommendedsetting:
MENU\Settings\Application:'SenddesiredT'
12500
ON
DHWcircuit(circuit3)
TheDHWheatingiscontrolledbymeansofON/OFFvalve**P2/M3.
Navigation:
IDno.:
Recommendedsetting:
MENU\Settings\Application:'Ch.-o.valve/P'
13051
ON
TheDHWtankisconnectedsecondarily.
MENU\Settings\Application:Tank,sec./prim.'
13053
ON
**
Thechangeovervalvecanbeofthistype:
DanfossAMZ113
Normalpowersupplied.Whenthecontrolvoltageisapplied(fromterminal12),thechangeovervalvechangesflowdirection.
VI.GU.G2.02
©Danfoss|2017.10|13
OperatingGuideECLComfort210,applicationA267
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
14|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
VI.GU.G2.02
©Danfoss|2017.10|15
OperatingGuideECLComfort210,applicationA267
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
16|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
VI.GU.G2.02
©Danfoss|2017.10|17
OperatingGuideECLComfort210,applicationA267
2.4Placingthetemperaturesensors
2.4.1Placingthetemperaturesensors
Itisimportantthatthesensorsaremountedinthecorrectposition
inyoursystem.
Thetemperaturesensormentionedbelowaresensorsusedforthe
ECLComfort210/296/310serieswhichnotallwillbeneeded
foryourapplication!
Outdoortemperaturesensor(ESMT)
Theoutdoorsensorshouldbemountedonthatsideofthebuilding
whereitislesslikelytobeexposedtodirectsunshine.Itshouldnot
beplacedclosetodoors,windowsorairoutlets.
Flowtemperaturesensor(ESMU,ESM-11orESMC)
Placethesensormax.15cmfromthemixingpoint.Insystems
withheatexchanger,DanfossrecommendsthattheESMU-typeto
beinsertedintotheexchangerflowoutlet.
Makesurethatthesurfaceofthepipeiscleanandevenwhere
thesensorismounted.
Returntemperaturesensor(ESMU,ESM-11orESMC)
Thereturntemperaturesensorshouldalwaysbeplacedsothatit
measuresarepresentativereturntemperature.
Roomtemperaturesensor
(ESM-10,ECA30/31RemoteControlUnit)
Placetheroomsensorintheroomwherethetemperatureistobe
controlled.Donotplaceitonoutsidewallsorclosetoradiators,
windowsordoors.
Boilertemperaturesensor(ESMU,ESM-11orESMC)
Placethesensoraccordingtotheboilermanufacturer’s
specification.
Airducttemperaturesensor(ESMB-12orESMUtypes)
Placethesensorsothatitmeasuresarepresentativetemperature.
DHWtemperaturesensor(ESMUorESMB-12)
PlacetheDHWtemperaturesensoraccordingtothemanufacturer’s
specification.
Slabtemperaturesensor(ESMB-12)
Placethesensorinaprotectiontubeintheslab.
ESM-11:Donotmovethesensorafterithasbeenfastenedinorderto
avoiddamagetothesensorelement.
ESM-11,ESMCandESMB-12:Useheatconductingpasteforquick
measurementofthetemperature.
ESMUandESMB-12:Usingasensorpockettoprotectthesensorwill,
however,resultinaslowertemperaturemeasurement.
18|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
Pt1000temperaturesensor(IEC751B,1000/0°C)
Relationshipbetweentemperatureandohmicvalue:
VI.GU.G2.02
©Danfoss|2017.10|19
OperatingGuideECLComfort210,applicationA267
2.5Electricalconnections
2.5.1Electricalconnections230Va.c.
SafetyNote
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocablesize
andisolation(reinforcedtype).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangefortheECLComfortinoperationis
0-55°C.Exceedingthistemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thecommongroundterminalisusedforconnectionofrelevant
components(pumps,motorizedcontrolvalves).
ECL210/310
ECL296
SeealsotheInstallationGuide(deliveredwiththeapplicationkey)
forapplicationspecificconnections.
20|©Danfoss|2017.10
VI.GU.G2.02
OperatingGuideECLComfort210,applicationA267
/