Reznor R6GI User guide

  • Hello! I am an AI chatbot trained to assist you with the Reznor R6GI User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
  • What are the available models of Reznor R6GI?
    What is the supply fan nominal airflow range for the R6GI-024-080 model?
    What is the gas heating input capacity for the R6GI-048-120 model?
    What is the SEER rating for the R6GI-036-100 model?
    What is the high-efficiency temperature rise for the R6GI-060-120 model?
    What is the voltage requirement for the R6GI-024-080 model?
    What is the MOP (maximum operating pressure) for the R6GI-048-120 model?
    What is the cabinet size for the R6GI-036-100 model?
The Energy Edge
Quick Selection
Guide
20 SEER, 81% AFUE
iQ Drive
®
Gas/Electric
Packaged System
Model R6GI
Options
Thermostat
Roof Curb (8” – 24”)
Manual or Motorized Fresh Air Damper
Economizer
Demand Control, CO
2
Sensor
Power Exhaust
Filter Kit
Hood Type Hail Guard
Duct Smoke Detector (Photo Electric) & Sample Tube
Low Ambient Kit
U.S. - LP/High Elevation Kit (0 - 10,000 ft.)
Canada - LP/High Elevation (0 - 4,500 ft.)
Universal Hard Start Kit
Extreme High Wind Kit - Roof Curb & Slab Mount
Freezestat Kit
Cap, Duct Adapter, 12” & 14” Round
Supply/return transition, 16” & 18”
Concentric diffuser, ush, 16” & 18”
Concentric diffuser, step down 16” & 18”
If installed in SCAQMD only: This gas/electric packaged system does not meet the SCAQMD Rule 1111
14 ng/J NOx emission limit (14 ng/J), and thus is subject to a mitigation fee of up to $450. This gas/electric
packaged system is not eligible for the Clean Air Furnace Rebate Program:
www.CleanAirFurnaceRebate.com.
Base Model
Supply Fan DX Cooling Gas Heating Power Cabinet
Nominal
Airow Range
Capacity
TC/Sen
SEER
Input
High/Low Efciency Temp Rise
Voltage
MCA /
MOP
Weight Size
(SCFM) (SCFM) (MBH) (MBH) AFUE (°F) (lbs) LxWxH (inches)
R6GI-024-080 800 800 - 1,375 24.1 / 17.8 20.0 80 / 64.8 81% 50.0 / 37.1 208/1 20.9 / 30 460
55.8 x 47.5 x 39
R6GI-036-100 1,175 875 - 1,500 35.3 / 26.7 20.0 100 / 81 81% 48 / 31.2 208/1 26.7 / 40 480
R6GI-048-120 1,450 1,200 - 2,000 43.5 / 31.5 20.0 120 / 97.2 81% 58.6 / 38.1 208/1 32.8 / 50 609
55.8 x 47.5 x 43
R6GI-060-120 1,640 1,200 - 2,000 54.5 / 39.8 20.0 120 / 97.2 81% 52.1 / 33.9 208/1 40.8 / 60 659
Capacity and SEER per AHRI Std 210/240; 80°F/67°F EAT @ 95°F Ambient ~ Natural Gas & Propane ~ 2 Stage Gas Control.
Reznor Edge: Easy to select, schedule & install.
Specications & illustrations subject to change without notice or incurring obligations.
© Nortek Global HVAC, LLC 2018. All rights reserved.
Reznor is a registered trademark of Nortek Global HVAC, LLC. Printed in U.S.A.
301E-1018
For complete catalog information including submittals, energy calculations,
dimension drawings, and more go to ReznorHVAC.com or call 800-695-1901.
What is the Reznor Edge?
ENERGY STAR
®
certification is awarded to products designed to reduce energy
consumption and utility costs. To qualify, packaged systems must have a
Seasonal Energy Efficiency Ratio (SEER) rating of 15.0 or higher and an Energy
Efficiency Ratio (EER) of 12.0 or higher. Packaged heat pumps are also rated by
a Heating Seasonal Performance Factor (HSPF) and must have a rating of 8.2
or higher.
/