2
Bri-KoEngineering,Inc. Spreadsheetdesignedby:B.Schwartz,PE
StructuralAnalysis Datedatainput: 13-May-16
CalcSht:EC-1 MechanicalEquipmentonRoofCurbCalc
Description: StructuralAnalysisofroofcurbmountedmechanical
equipmenttoresistwindforces.
DwgReference: ENG-1
Code: FloridaBuildingCode5thEd.(2014)andASCE7-10.
AISIS100-2007,NDS2005Ed.
Design Methodology and Load Combinations:
DesignMethod:
LRFD
Φ =
0.90
LoadCombos:
FBCEqn.16-1 1.4D+ 0.0 W Gravity
FBCEqn.16-6 0.9D+ 1.0 W Overturn/Sliding
Wind Forces:
based on FBC 2014, 1620.6, Af<0.1Bh, Af<0.1BL
Wind Design Requirements:
F=qh(GC
r
)A
f
Ult.DesignWindSpeed,Vult(3-secgust):
186 mph
MiamiDade
NominalDesignWindSpeed,Vasd: 144 mph
RiskCategory: IV
Height,h: 60 ft
Exp,Category: C
Enclosure Cat. N/A
Velocity Pressure
qh=0.00256K
z
K
zt
K
d
V
2
(lb/ft
2
) qh=
85.6 psf
(GC
r
) v,l= 1.5 vert. 3.1 lat. Fver,Flat:
128.3 psf, 265.2 psf
Limit States:
Selectmodel#forillustrationpurposes:
Size5
Unit Areas, (sf), Lng, shrt, tp:
20.76ft
2
15.50 ft
2
20.98 ft
2
Loads, (lbs):
Pwh=5506 Pwv=2693 D=551 for Overturn
Resistance to Unit overturn:
Mover=1.00*(Pwh·Al·(a/2)+Pwv·At·(b/2))= 179k-in
Mdeadwt=0.90*(unitwt·(b/2))= 12 k-in
MnomfromAnchors=R 270k-in
CHECKS OK
Resistance to sliding:
ReqdShear=1.00*(Pwh·Ar)=A=20.8sf 5506 lbs
CHECKS OK
Shearisresistedbyyroofcurbwithstrengthbasedonminimal
requirementsasperRoofCurbAttachmentdetail
Roof Curb Brace Requirements:
AISI S100, Comm. Sec B2, B2.1
Gravityloadperlinftofcurb: 87plf
OverturnLoadplfofcurb:
698 plf
Longsidelengthw/obracing,Nomplf: 64 in. 801 plf
CHECKS OK
Equipment Integrity: Sheet metal cover fastener resistance
Analysis based on AISI S100-2007 "Cold Formed Steel Structural Members",
SectionE4:ScrewConnections
Fw=
5506 lbs Seeabove
Minnumberofscrewsperlongside: 13
Numberofscrewsprovided: 14
CHECKS OK
Base Rail fastener resistance:
NominalSMSpull-down*8screws= 182 k-in
CHECKS OK
Screwsize,washerdia.(d,dw): (#10,1/2in.
Thknessofmtlshell,frame(t1,t2): 0.036 in. 0.030 in.
Screwyieldstrength: 50 ksi
Allowabletensilestrength/screw: 438 lbs
Allowablepull-overstrength/screw: 458 lbs SinceLRFD:
Allowableshearstrength/screw: 478lbs Φ = 0.50
Nortek Global
HVACSINGLEPACKAGE/ELECTRICHVACUNITS&COMMERCIALSPLITUNITS
FLATROOFCURBMOUNTCONFIGURATIONANDANCHORSELECTION-WINDLOADEXAMINATION