Mitsubishi Electric FR-F860 (600V CLASS User manual

Category
Power adapters & inverters
Type
User manual
INVERTER
INVERTER FR-F800
FR-F860 INSTRUCTION MANUAL (DETAILED)
B
INTRODUCTION
1
INSTALLATION AND WIRING
2
PRECAUTIONS FOR USE OF
THE INVERTER
3
BASIC OPERATION
4
PARAMETERS
5
PROTECTIVE FUNCTIONS
6
PRECAUTIONS FOR
MAINTENANCE AND
INSPECTION
7
SPECIFICATIONS
8
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
IB(NA)-0600688ENG-B(1903)MEE Printed in Japan Specifications subject to change without notice.
FR-F800
FR-F860 (600V CLASS SPECIFICATION INVERTER)
INSTRUCTION MANUAL (DETAILED)
FR-F860-00027 to 00450-N6
FR-F860-00680 to 04420
FR-F862-05450 to 08500
Inverter for fans and pumps
Safety Instructions
1
Thank you for choosing this Mitsubishi Electric inverter.
This Instruction Manual provides instructions for advanced use of the FR-F860 series inverters.
Incorrect handling might cause an unexpected fault. Before using this inverter, always carefully read this Instruction Manual and
the Instruction Manual (Startup) packed with the product to use this product correctly.
Electric Shock Prevention
Fire Prevention
Injury Prevention
Additional Instructions
The following instructions must be also followed. If the product
is handled incorrectly, it may cause unexpected fault, an injury,
or an electric shock.
Safety Instructions
Do not attempt to install, operate, maintain or inspect the
product until you have read through this Instruction Manual
and appended documents carefully and can use the
equipment correctly. Do not use this product until you have a
full knowledge of the equipment, safety information and
instructions.
Installation, operation, maintenance and inspection must be
performed by qualified personnel. Here, an expert means a
person who meets all the conditions below.
A person who took a proper engineering training. Such
training may be available at your local Mitsubishi Electric
office. Contact your local sales office for schedules and
locations.
A person who can access operating manuals for the
protective devices (e.g. light curtain) connected to the safety
control system. A person who has read and familiarized
himself/herself with the manuals.
In this Instruction Manual, the safety instruction levels are
classified into "WARNING" and "CAUTION"
Incorrect handling may cause
hazardous conditions, resulting in
death or severe injury.
Incorrect handling may cause
hazardous conditions, resulting in
medium or slight injury, or may cause
only material damage.
Note that even the level may even lead to
a serious consequence according to conditions. Be sure to
follow the instructions of both levels as they are critical to
personal safety.
WARNING
While the inverter power is ON, do not remove the front cover or
the wiring cover. Do not run the inverter with the front cover or
the wiring cover removed, as accidental contact with exposed
high-voltage terminals and internal components may occur,
resulting in an electrical shock.
Even if power is OFF, do not remove the front cover except for
wiring or periodic inspection. You may accidentally touch the
charged inverter circuits and get an electric shock.
Before wiring or inspection, the power lamp must be switched
OFF. Any person who is involved in wiring or inspection shall
wait for at least 10 minutes after the power supply has been
switched OFF and check that there are no residual voltage using
a tester or the like. The capacitor is charged with high voltage for
some time after power OFF, and it is dangerous.
This inverter must be earthed (grounded). Earthing (grounding)
must conform to the requirements of national and local safety
regulations and electrical code (NEC section 250, IEC 61140
class 1 and other applicable standards).
Any person who is involved in wiring or inspection of this
equipment shall be fully competent to do the work.
The inverter must be installed before wiring. Otherwise you may
get an electric shock or be injured.
Setting dial and key operations must be performed with dry
hands to prevent an electric shock. Otherwise you may get an
electric shock.
Do not subject the cables to scratches, excessive stress, heavy
loads or pinching. Doing so may cause an electric shock.
Do not change the cooling fan while power is ON. It is dangerous
to change the cooling fan while power is ON.
Do not touch the printed circuit board or handle the cables with
wet hands. Doing so may cause an electric shock.
When measuring the main circuit capacitor capacity, the DC
voltage is applied to the motor for 1s at powering OFF. Never
touch the motor terminal, etc. right after powering OFF to
prevent an electric shock.
A PM motor is a synchronous motor with high-performance
magnets embedded in the rotor. Motor terminals holds high-
voltage while the motor is running even after the inverter power
is turned OFF. Before wiring or inspection, the motor must be
confirmed to be stopped. In an application, such as fan and
blower, where the motor is driven by the load, a low-voltage
manual motor starter must be connected at the inverter's output
side, and wiring and inspection must be performed while the
motor starter is open. Otherwise you may get an electric shock.
WARNING
CAUTION
CAUTION
CAUTION
Inverter must be installed on a nonflammable wall without holes
(so that nobody touches the inverter heat sink on the rear side,
etc.). Mounting it to or near flammable material may cause a fire.
If the inverter has become faulty, the inverter power must be
switched OFF. A continuous flow of large current may cause a
fire.
Do not connect a resistor directly to the DC terminals P/+ and N/-.
Doing so could cause a fire.
Be sure to perform daily and periodic inspections as specified in
the Instruction Manual. If a product is used without any
inspection, a burst, breakage, or a fire may occur.
CAUTION
The voltage applied to each terminal must be the ones specified
in the Instruction Manual. Otherwise an explosion or damage
may occur.
The cables must be connected to the correct terminals.
Otherwise an explosion or damage may occur.
The polarity (+ and -) must be correct. Otherwise an explosion or
damage may occur.
While power is ON or for some time after power-OFF, do not
touch the inverter as it will be extremely hot. Touching these
devices may cause a burn.
CAUTION
Transportation and installation
Any person who is opening a package using a sharp object,
such as a knife and cutter, must wear gloves to prevent injuries
caused by the edge of the sharp object.
The product must be transported in correct method that
corresponds to the weight. Failure to do so may lead to injuries.
Do not stand or rest heavy objects on the product.
Do not stack the boxes containing inverters higher than the
number recommended.
When carrying the inverter, do not hold it by the front cover; it
may fall off or fail.
During installation, caution must be taken not to drop the inverter
as doing so may cause injuries.
The product must be installed on the surface that withstands the
weight of the inverter.
Do not install the product on a hot surface.
The mounting orientation of the inverter must be correct.
The inverter must be installed on a strong surface securely with
screws so that it will not drop.
Do not install or operate the inverter if it is damaged or has parts
missing.
Foreign conductive objects must be prevented from entering the
inverter. That includes screws and metal fragments or other
flammable substance such as oil.
As the inverter is a precision instrument, do not drop or subject it
to impact.
For the FR-F860-00090 or lower, the surrounding air
temperature must be -10 to +30°C for the SLD rating (-10 to
+40°C for the LD rating) (non-freezing). Otherwise the inverter
may be damaged.
For the FR-F860-00170 to 01080, the surrounding air
temperature must be -10 to +40°C (non-freezing). Otherwise the
inverter may be damaged.
For the FR-F860-01440 or higher, the surrounding air
temperature must be -10 to +40°C for the SLD rating (-10 to
+50°C for the LD rating) (non-freezing). Otherwise the inverter
may be damaged.
The ambient humidity must be 95%RH or less (non-
condensing). Otherwise the inverter may be damaged. (Refer to
page 23 for details.)
2
Safety Instructions
 2.9 m/s
2
or less for the FR-F860-02890 or higher.
CAUTION
Transportation and installation
The storage temperature (applicable for a short time, e.g. during
transit) must be between -20 and +65°C. Otherwise the inverter
may be damaged.
The inverter must be used indoors (without corrosive gas,
flammable gas, oil mist, dust and dirt etc.) Otherwise the inverter
may be damaged.
This product must be used at an altitude of 2500 m or less, with
5.9 m/s
2
or less vibration at 10 to 55 Hz (directions of X, Y, Z
axes). Otherwise the inverter may be damaged. (For the
installation at an altitude above 1000 m, consider a 3% reduction
in the rated current per 500 m increase in altitude.)
If halogen-based materials (fluorine, chlorine, bromine, iodine,
etc.) infiltrate into a Mitsubishi Electric product, the product will
be damaged. Halogen-based materials are often included in
fumigant, which is used to sterilize or disinfest wooden
packages. When packaging, prevent residual fumigant
components from being infiltrated into Mitsubishi Electric
products, or use an alternative sterilization or disinfection
method (heat disinfection, etc.) for packaging. Sterilization of
disinfection of wooden package should also be performed before
packaging the product.
Wiring
Do not install a power factor correction capacitor or surge
suppressor/capacitor type filter on the inverter output side.
These devices on the inverter output side may be overheated or
burn out.
The output side terminals (terminals U, V, and W) must be
connected correctly. Otherwise the motor will rotate inversely.
PM motor terminals (U, V, W) hold high-voltage while the PM
motor is running even after the power is turned OFF. Before
wiring, the PM motor must be confirmed to be stopped.
Otherwise you may get an electric shock.
Never connect a PM motor to the commercial power supply.
Applying the commercial power supply to input terminals (U, V,
W) of a PM motor will burn the PM motor. The PM motor must
be connected with the output terminals (U, V, W) of the inverter.
Test operation
Before starting operation, each parameter must be confirmed
and adjusted. A failure to do so may cause some machines to
make unexpected motions.
WARNING
Usage
Stay away from the equipment after using the retry function in
this product as the equipment will restart suddenly after the
output shutoff of this product.
Since pressing the STOP/RESET key may not stop output
depending on the function setting status, separate circuit and
switch that make an emergency stop (power OFF, mechanical
brake operation for emergency stop, etc.) must be provided.
OFF status of the start signal must be confirmed before resetting
the inverter fault. Resetting inverter fault with the start signal ON
restarts the motor suddenly.
Do not use a PM motor for an application where the PM motor is
driven by its load and runs at a speed higher than the maximum
motor speed.
Use this inverter only with three-phase induction motors or with a
PM motor. Connection of any other electrical equipment to the
inverter output may damage the equipment.
Do not modify the equipment.
Do not perform parts removal which is not instructed in this
manual. Doing so may lead to fault or damage of the product.
CAUTION
Usage
The electronic thermal relay function does not guarantee
protection of the motor from overheating. It is recommended to
install both an external thermal and PTC thermistor for overheat
protection.
Do not use a magnetic contactor on the inverter input for
frequent starting/stopping of the inverter. Doing so may shorten
the life of this product.
The effect of electromagnetic interference must be reduced by
using a noise filter or by other means. Otherwise nearby
electronic equipment may be affected.
Appropriate measures must be taken to suppress harmonics.
Otherwise power supply harmonics from the inverter may heat/
damage the power factor correction capacitor and generator.
When driving a 600 V class motor by the inverter, the motor must
be an insulation-enhanced motor or measures must be taken to
suppress surge voltage. Surge voltage attributable to the wiring
constants may occur at the motor terminals, deteriorating the
insulation of the motor.
When parameter clear or all parameter clear is performed, the
required parameters must be set again before starting
operations because all parameters return to their initial values.
The inverter can be easily set for high-speed operation. Before
changing its setting, the performances of the motor and machine
must be fully examined.
Stop status cannot be hold by the inverter's brake function. In
addition to the inverter’s brake function, a holding device must
be installed to ensure safety.
Before running an inverter which had been stored for a long
period, inspection and test operation must be performed.
Static electricity in your body must be discharged before you
touch the product.
Only one PM motor can be connected to an inverter.
A PM motor must be used under PM motor control. Do not use a
synchronous motor, induction motor, or synchronous induction
motor.
Do not connect a PM motor in the induction motor control
settings (initial settings). Do not use an induction motor in the
PM motor control settings. It will cause a failure.
In the system with a PM motor, the inverter power must be
turned ON before closing the contacts of the contactor at the
output side.
When the emergency drive operation is performed, the operation
is continued or the retry is repeated even when a fault occurs,
which may damage or burn the inverter and motor. Before
restarting the normal operation after using the emergency drive
function, make sure that the inverter and motor have no fault.
Emergency stop
A safety backup such as an emergency brake must be provided
for devices or equipment in a system to prevent hazardous
conditions in case of failure of this product or an external device
controlling this product.
When the breaker on the inverter input side trips, the wiring must
be checked for fault (short circuit), and internal parts of the
inverter for a damage, etc. The cause of the trip must be
identified and removed before turning ON the power of the
breaker.
When a protective function activates, take an appropriate
corrective action, then reset the inverter, and resume the
operation.
Maintenance, inspection and parts replacement
Do not carry out a megger (insulation resistance) test on the
control circuit of the inverter. It will cause a failure.
Disposal
The inverter must be treated as industrial waste.
General instruction
For clarity, illustrations in this Instruction Manual may be drawn
with covers or safety guards removed. Ensure all covers and
safety guards are properly installed prior to starting operation.
For details on the PM motor, refer to the Instruction Manual of
the PM motor.
CONTENTS
3
1 INTRODUCTION 9
1.1 Product checking and accessories 10
1.2 Component names 11
1.3 Operation steps 12
1.4 About the related manuals 13
2 INSTALLATION AND WIRING 15
2.1 Peripheral devices 16
2.1.1 Inverter and peripheral devices ......................................................................................................................16
2.1.2 Peripheral devices ..........................................................................................................................................18
2.2 Removal and reinstallation of the front covers 20
2.3 Installation of the inverter and enclosure design 23
2.3.1 Inverter installation environment.....................................................................................................................23
2.3.2 Amount of heat generated by the inverter ......................................................................................................25
2.3.3 Cooling system types for inverter enclosure...................................................................................................26
2.3.4 Inverter installation..........................................................................................................................................27
2.3.5 Protruding the heat sink through a panel........................................................................................................29
2.4 Terminal connection diagrams 31
2.5 Main circuit terminals 33
2.5.1 Details on the main circuit terminals...............................................................................................................33
2.5.2 Terminal layout of the main circuit terminals, wiring of power supply and the motor......................................34
2.5.3 Applicable cables and the wiring length..........................................................................................................36
2.5.4 Earthing (grounding) precautions ...................................................................................................................39
2.6 Control circuit 40
2.6.1 Details on the control circuit terminals............................................................................................................40
2.6.2 Control logic (sink/source) change .................................................................................................................44
2.6.3 Wiring of control circuit ...................................................................................................................................46
2.6.4 Wiring precautions..........................................................................................................................................48
2.6.5 When using separate power supplies for the control circuit and the main circuit ...........................................49
2.6.6 When supplying 24 V external power to the control circuit.............................................................................51
2.7 Communication connectors and terminals 53
2.7.1 PU connector..................................................................................................................................................53
2.7.2 USB connector................................................................................................................................................55
2.7.3 RS-485 terminal block ....................................................................................................................................56
2.8 Connection of stand-alone option units 57
2.8.1 Connection of the DC reactor .........................................................................................................................57
3 PRECAUTIONS FOR USE OF THE INVERTER 59
3.1 Electro-magnetic interference (EMI) and leakage currents 60
3.1.1 Leakage currents and countermeasures ........................................................................................................60
CONTENTS
4
CONTENTS
3.1.2 Countermeasures against inverter-generated EMI ........................................................................................ 61
3.2 Power supply harmonics 63
3.2.1 Power supply harmonics ................................................................................................................................ 63
3.3 Installation of a reactor 63
3.4 Power-OFF and magnetic contactor (MC) 64
3.5 Countermeasures against deterioration of the 600 V class motor insulation 65
3.6 Checklist before starting operation 66
3.7 Failsafe system which uses the inverter 69
4 BASIC OPERATION 71
4.1 Frequently-used parameters (simple mode parameters) 72
4.1.1 Simple mode parameter list............................................................................................................................ 72
4.2 Basic operation procedure (PU operation) 74
4.2.1 Operating at a set frequency (example: operating at 30 Hz).......................................................................... 74
4.2.2 Setting the frequency by switches (multi-speed setting) ................................................................................ 75
4.2.3 Setting the frequency with analog signals (voltage input) .............................................................................. 76
4.2.4 Using an analog signal (current input) to give a frequency command ........................................................... 77
4.3 Basic operation procedure (External operation) 78
4.3.1 Using the frequency set by the operation panel ............................................................................................. 78
4.3.2 Setting the frequency by switches (multi-speed setting) (Pr.4 to Pr.6)........................................................... 79
4.3.3 Setting the frequency with analog signals (voltage input) .............................................................................. 80
4.3.4 Changing the frequency (60 Hz, initial value) at the maximum voltage input (5 V, initial value) .................... 81
4.3.5 Using an analog signal (current input) to give a frequency command ........................................................... 82
4.3.6 Changing the frequency (60 Hz, initial value) at the maximum current input (at 20 mA, initial value) ........... 83
4.4 Basic operation procedure (JOG operation) 84
4.4.1 Performing JOG operation using external signals.......................................................................................... 84
4.4.2 JOG operation from the operation panel........................................................................................................ 85
5 PARAMETERS 87
5.1 Parameter List 88
5.1.1 Parameter list (by parameter number) ........................................................................................................... 88
5.1.2 Parameter list (by function group) ................................................................................................................ 108
5.2 Control method 115
5.2.1 Changing the control method ....................................................................................................................... 117
5.2.2 Selecting the Advanced magnetic flux vector control .................................................................................. 121
5.2.3 Selecting the PM motor control ................................................................................................................... 123
5.3 Speed control under PM motor control 125
5.3.1 Setting procedure of PM motor control ........................................................................................................ 125
5.3.2 Performing high-accuracy, fast-response control (gain adjustment for PM motor control) ......................... 126
5.3.3 Troubleshooting in the speed control .......................................................................................................... 128
5.3.4 Torque detection filter .................................................................................................................................. 129
CONTENTS
5
5.4 (E) Environment setting parameters 130
5.4.1 Real time clock function................................................................................................................................131
5.4.2 Reset selection / disconnected PU detection / PU stop selection ................................................................133
5.4.3 PU display language selection......................................................................................................................136
5.4.4 Buzzer control...............................................................................................................................................136
5.4.5 PU contrast adjustment ................................................................................................................................136
5.4.6 Direct setting.................................................................................................................................................137
5.4.7 Resetting USB host errors ............................................................................................................................137
5.4.8 Multiple rating setting....................................................................................................................................138
5.4.9 Parameter write selection .............................................................................................................................139
5.4.10 Password function ........................................................................................................................................141
5.4.11 Free parameter.............................................................................................................................................143
5.4.12 Setting multiple parameters as a batch ........................................................................................................143
5.4.13 Extended parameter display and user group function ..................................................................................147
5.4.14 Parameter copy alarm release......................................................................................................................148
5.4.15 PWM carrier frequency and Soft-PWM control.............................................................................................149
5.4.16 Inverter parts life display...............................................................................................................................150
5.4.17 Maintenance timer alarm ..............................................................................................................................154
5.4.18 Current average value monitor signal...........................................................................................................155
5.5 (F) Setting of acceleration/deceleration time and acceleration/deceleration pattern 157
5.5.1 Setting the acceleration and deceleration time.............................................................................................157
5.5.2 Acceleration/deceleration pattern .................................................................................................................161
5.5.3 Remote setting function................................................................................................................................164
5.5.4 Starting frequency and start-time hold function ...........................................................................................167
5.5.5 Minimum motor speed frequency ................................................................................................................168
5.6 (D) Operation command and frequency command 169
5.6.1 Operation mode selection.............................................................................................................................170
5.6.2 Startup in Network operation mode at power-ON.........................................................................................179
5.6.3 Start command source and frequency command source during communication operation .........................180
5.6.4 Reverse rotation prevention selection ..........................................................................................................187
5.6.5 Frequency setting via pulse train input .........................................................................................................188
5.6.6 JOG operation ..............................................................................................................................................190
5.6.7 Operation by multi-speed setting..................................................................................................................192
5.7 (H) Protective function parameter 194
5.7.1 Motor overheat protection (electronic thermal O/L relay) .............................................................................195
5.7.2 Cooling fan operation selection ....................................................................................................................202
5.7.3 Earth (ground) fault detection at start ..........................................................................................................203
5.7.4 Initiating a protective function .......................................................................................................................203
5.7.5 I/O phase loss protection selection...............................................................................................................204
5.7.6 Retry function................................................................................................................................................205
5.7.7 Emergency drive (Fire mode) .......................................................................................................................207
5.7.8 Limiting the output frequency (maximum/minimum frequency) ....................................................................214
5.7.9 Avoiding the mechanical resonance points (frequency jump) ......................................................................215
5.7.10 Stall prevention operation.............................................................................................................................217
5.7.11 Load characteristics fault detection ..............................................................................................................224
5.7.12 Motor overspeeding detection .....................................................................................................................228
5.8 (M) Monitor display and monitor output signal 229
5.8.1 Speed display and rotations per minute setting............................................................................................230
5.8.2 Monitor indicator selection using operation panel or via communication......................................................232
5.8.3 Monitor display selection for terminals CA and AM ......................................................................................241
5.8.4 Adjustment of terminal CA and terminal AM.................................................................................................245
5.8.5 Energy saving monitor..................................................................................................................................247
5.8.6 Output terminal function selection ................................................................................................................252
5.8.7 Output frequency detection...........................................................................................................................259
5.8.8 Output current detection function..................................................................................................................261
6
CONTENTS
5.8.9 Output torque detection ............................................................................................................................... 263
5.8.10 Remote output function ................................................................................................................................ 263
5.8.11 Analog remote output function ..................................................................................................................... 265
5.8.12 Fault code output selection .......................................................................................................................... 267
5.8.13 Pulse train output of output power................................................................................................................ 268
5.8.14 Detection of control circuit temperature........................................................................................................ 269
5.9 (T) Multi-Function Input Terminal Parameters 270
5.9.1 Analog input selection .................................................................................................................................. 271
5.9.2 Analog input terminal (terminal 1, 4) function assignment ........................................................................... 275
5.9.3 Analog input compensation .......................................................................................................................... 276
5.9.4 Analog input responsiveness and noise elimination..................................................................................... 278
5.9.5 Frequency setting voltage (current) bias and gain ....................................................................................... 280
5.9.6 Bias and gain for voltage (current) setting of stall prevention operation level ............................................. 285
5.9.7 Checking of current input on analog input terminal ...................................................................................... 289
5.9.8 Input terminal function selection................................................................................................................... 293
5.9.9 Inverter output shutoff signal ........................................................................................................................ 296
5.9.10 Selecting operation condition of the second function selection signal (RT) ................................................. 297
5.9.11 Start signal operation selection .................................................................................................................... 299
5.10 (C) Motor constant parameters 301
5.10.1 Applied motor ............................................................................................................................................... 301
5.10.2 Offline auto tuning ....................................................................................................................................... 304
5.10.3 Offline auto tuning for a PM motor (motor constants tuning) ....................................................................... 314
5.10.4 Online auto tuning ....................................................................................................................................... 322
5.11 (A) Application parameters 325
5.11.1 Electronic bypass function ........................................................................................................................... 326
5.11.2 Self power management .............................................................................................................................. 334
5.11.3 Start count monitor ....................................................................................................................................... 337
5.11.4 Traverse function.......................................................................................................................................... 338
5.11.5 Cleaning function.......................................................................................................................................... 340
5.11.6 PID control.................................................................................................................................................... 343
5.11.7 PID gain tuning............................................................................................................................................. 361
5.11.8 Changing the display increment of the numerical values used in PID control.............................................. 366
5.11.9 PID pre-charge function ............................................................................................................................... 369
5.11.10 Multi-pump function (Advanced PID function) .............................................................................................. 373
5.11.11 PID control enhanced functions ................................................................................................................... 382
5.11.12 Automatic restart after instantaneous power failure/flying start with an induction motor ............................. 390
5.11.13 Offline auto tuning for a frequency search .................................................................................................. 396
5.11.14 Power failure time deceleration-to-stop function .......................................................................................... 400
5.11.15 PLC function................................................................................................................................................. 405
5.11.16 Trace function............................................................................................................................................... 407
5.12 (N) Operation via communication and its settings 414
5.12.1 Wiring and configuration of PU connector.................................................................................................... 414
5.12.2 Wiring and configuration of RS-485 terminals.............................................................................................. 416
5.12.3 Initial setting of operation via communication............................................................................................... 419
5.12.4 Initial settings and specifications of RS-485 communication........................................................................ 424
5.12.5 Mitsubishi inverter protocol (computer link communication)......................................................................... 426
5.12.6 MODBUS RTU communication specification ............................................................................................... 441
5.12.7 BACnet MS/TP protocol ............................................................................................................................... 457
5.12.8 USB device communication ......................................................................................................................... 469
5.12.9 Automatic connection with GOT................................................................................................................... 470
5.12.10 Backup/restore ............................................................................................................................................. 471
5.13 (G) Control parameters 473
5.13.1 Manual torque boost .................................................................................................................................... 474
5.13.2 Base frequency, voltage .............................................................................................................................. 475
5.13.3 Load pattern selection ................................................................................................................................. 477
CONTENTS
7
5.13.4 Excitation current low-speed scaling factor .................................................................................................478
5.13.5 Energy saving control ..................................................................................................................................479
5.13.6 Adjustable 5 points V/F ................................................................................................................................480
5.13.7 DC injection brake ........................................................................................................................................481
5.13.8 Output stop function......................................................................................................................................483
5.13.9 Stop selection ...............................................................................................................................................485
5.13.10 DC feeding mode..........................................................................................................................................486
5.13.11 Regeneration avoidance function .................................................................................................................491
5.13.12 Increased magnetic excitation deceleration .................................................................................................494
5.13.13 Slip compensation .......................................................................................................................................495
5.13.14 Speed smoothing control .............................................................................................................................496
6 PROTECTIVE FUNCTIONS 497
6.1 Inverter fault and alarm indications 498
6.2 Reset method for the protective functions 498
6.3 The list of fault displays 499
6.4 Causes and corrective actions 501
6.5 Check first when you have a trouble 518
6.5.1 Motor does not start......................................................................................................................................518
6.5.2 Motor or machine is making abnormal acoustic noise..................................................................................520
6.5.3 Inverter generates abnormal noise ...............................................................................................................520
6.5.4 Motor generates heat abnormally .................................................................................................................521
6.5.5 Motor rotates in the opposite direction..........................................................................................................521
6.5.6 Speed greatly differs from the setting ...........................................................................................................521
6.5.7 Acceleration/deceleration is not smooth .......................................................................................................522
6.5.8 Speed varies during operation......................................................................................................................522
6.5.9 Operation mode is not changed properly......................................................................................................523
6.5.10 Operation panel display is not operating ......................................................................................................523
6.5.11 Motor current is too large..............................................................................................................................523
6.5.12 Speed does not accelerate ...........................................................................................................................524
6.5.13 Unable to write parameter setting.................................................................................................................525
6.5.14 Power lamp is not lit......................................................................................................................................525
7 PRECAUTIONS FOR MAINTENANCE AND
INSPECTION 527
7.1 Inspection item 528
7.1.1 Daily inspection.............................................................................................................................................528
7.1.2 Periodic inspection........................................................................................................................................528
7.1.3 Daily and periodic inspection ........................................................................................................................529
7.1.4 Checking the inverter module and the converter module .............................................................................531
7.1.5 Cleaning........................................................................................................................................................531
7.1.6 Replacement of parts....................................................................................................................................532
7.1.7 Removal and reinstallation of the control circuit terminal block ....................................................................536
7.2 Measurement of main circuit voltages, currents and powers 538
7.2.1 Measurement of powers ...............................................................................................................................540
7.2.2 Measurement of voltages .............................................................................................................................540
7.2.3 Measurement of currents..............................................................................................................................540
8
CONTENTS
7.2.4 Measurement of inverter input power factor................................................................................................. 540
7.2.5 Measurement of converter output voltage (across terminals P and N) ........................................................540
7.2.6 Measurement of inverter output frequency................................................................................................... 540
7.2.7 Insulation resistance test using megger ....................................................................................................... 541
7.2.8 Pressure test ................................................................................................................................................ 541
8 SPECIFICATIONS 543
8.1 Inverter rating 544
8.2 Common specifications 545
8.3 Outline dimension drawings 547
8.3.1 Inverter outline dimension drawings............................................................................................................. 547
APPENDIX 551
Appendix 1 Specification comparison between PM motor control and induction motor control....... 552
Appendix 2 Parameters (functions) and instruction codes under different control methods............. 553
Appendix 3 For customers using HMS network options ........................................................................ 566
INTRODUCTION
9
1
1 INTRODUCTION
The contents described in this chapter must be read before using this
product.
Always read the instructions before using the equipment.
For the INTRODUCTION of the separated converter type, refer to the FR-
F802 (Separated Converter Type) Instruction Manual (Hardware).
1.1 Product checking and accessories.........................................10
1.2 Component names....................................................................11
1.3 Operation steps.........................................................................12
1.4 About the related manuals.......................................................13
<Abbreviations>
DU ............................................................. Operation panel (FR-LU08)
Operation panel ........................................ Operation panel (FR-LU08)
Parameter unit .......................................... Parameter unit (FR-PU07)
PU ............................................................. Operation panel and parameter unit
Inverter ...................................................... Mitsubishi Electric inverter FR-F860 series
Pr. ............................................................. Parameter number (Number assigned to function)
PU operation ............................................. Operation using the PU (operation panel/parameter unit)
External operation ..................................... Operation using the control circuit signals
Combined operation ................................. Combined operation using the PU (operation panel/parameter unit)
and External operation
<Trademarks>
Microsoft and Visual C++ are registered trademarks of Microsoft Corporation in the United States and other
countries.
MODBUS is a registered trademark of SCHNEIDER ELECTRIC USA, INC.
BACnet is a registered trademark of the ASHRAE (American Society of Heating, Refrigerating and Air-
Conditioning Engineers).
LONWORKS is a registered trademark of Echelon Corporation in the United States and other countries.
Other company and product names herein are the trademarks and registered trademarks of their respective
owners.
<Notes on descriptions in this Instruction Manual>
Connection diagrams in this Instruction Manual appear with the control logic of the input terminals as sink
logic, unless otherwise specified. (For the control logic, refer to page 44.)
Product checking and accessories
10
INTRODUCTION
1.1 Product checking and accessories
Unpack the product and check the rating plate and the capacity plate of the inverter to ensure that the model agrees with the
order and the product is intact.
Inverter model
FR-F860-00450 or lower
FR-F860-00680 or higher
Accessory
Eyebolt for hanging the inverter
How to read the SERIAL number
Capacity Eyebolt Size Quantity
FR-F860-02890, 03360 M10 2
FR-F860-04420 M12 2
Rating plate example
The SERIAL consists of one symbol, two characters indicating the production
year and month, and six characters indicating the control number. The last digit
of the production year is indicated as the Year, and the Month is indicated by 1
to 9, X (October), Y (November), or Z (December).

Symbol Year Month Control number
SERIAL
FR --F8 06 - E3
00027
Symbol Voltage class
600 V class6
- N6
Symbol Description
00027 to 00450
Inverter SLD
rated current (A)
Symbol
Circuit board coating
(conforming to IEC 60721-3-3 3C2/3S2)
UL Type 1
certification
Plated
conductor
With WithWithoutN6
CA3
Symbol Type
E3
FR --F8 06- 300680
Symbol Voltage class
600 V class6
Symbol Description
00680 to 08500 Inverter SLD rated current (A)
Symbol
Circuit board coating
(conforming to IEC 60721-3-3 3C2/3S2)
With
With
Plated conductor
With
Without
06
60
- 60
Symbol Structure, functionality
Separated converter type
2
Standard model
0
CA3
Symbol Type
3
Rating plate
Input rating
Output rating
SERIAL
Inverter model
,1387;;;;;
02'(/)5)
287387;;;;;
6(5,$/;;;;;;;;;
0$'(,1;;;;;
Country of origin
Component names
INTRODUCTION
11
1
1.2 Component names
Component names are shown below.
Symbol Name Description
Refer to
page
(a) PU connector
Connects the operation panel or the parameter unit. This connector also enables the
RS-485 communication.
53
(b) USB A connector Connects a USB memory device. 55
(c) USB mini B connector Connects a personal computer and enables communication with FR Configurator2. 55
(d) RS-485 terminals Enables RS-485, MODBUS RTU communication and BACnet communication. 56
(e)
Terminating resistor selection
switch (SW1)
Select whether or not to use the terminating resistor for RS-485 communication. 56
(f) Plug-in option connector 1
Connects a plug-in option or a communication option.
Instruction
Manual of
the option
(g) Plug-in option connector 2
(h) Plug-in option connector 3
(i)
Voltage/current input switch
(SW2)
Selects between voltage and current for the terminal 2 and 4 inputs. 271
(j) Control circuit terminal block Connects cables for the control circuit. 40
(k) Main circuit terminal block Connects cables for the main circuit. 33
(l) Charge lamp Stays ON while the power is supplied to the main circuit. 34
(m) Alarm lamp Turns ON when the protective function of the inverter is activated. 34
(n) Power lamp Stays ON while the power is supplied to the control circuit (R1/L11, S1/L21). 34
(o) Front cover (upper side)
Remove this cover for the installation of the product, installation of a plug-in
(communication) option, RS-485 terminal wiring, switching of the voltage/current input
switch, etc.
20
(p) Front cover (lower side) Remove this cover for wiring. 20
(q) Accessory cover Remove this cover for using the PU connector. 53
(r) Cooling fan Cools the inverter. (FR-F860-00061 or higher.) 533
(s)
Switches for manufacturer
setting (SW3 and SW4)
Do not change the initial setting (OFF ).
(t)
Control logic switchover jumper
connector
Changes the control logic of input signals as necessary. 44
(q)
(p)
(a)
(j)
(k)
(i)
(k)
(l)
(d)
(h)
(f)
(g)
(m)
(n)
(r)
(o)
(e)
(b)
(c)
(s)
(t)
Operation steps
12
INTRODUCTION
1.3 Operation steps
Symbol Overview Refer to page
(a) Install the inverter. 23
(b) Perform wiring for the power supply and the motor. 34
(c) Select the control method (V/F control, Advanced magnetic flux vector control, or PM motor control). 117
(d) Input the start command via communication. 414
(e) The PU gives both start and frequency commands. (PU operation mode) 74
(f)
The PU gives a start command, and inputs to terminal RH, RM, and RL give a frequency command.
(External/PU combined operation mode 2)
75
(g)
The PU gives a start command, and voltage input to terminal 2 gives a frequency command.
(External/PU combined operation mode 2)
76
(h)
The PU gives a start command, and current input to terminal 4 gives a frequency command.
(External/PU combined operation mode 2)
77
(i)
Inputs to terminal STF and STR give a start command, and the PU gives a frequency command.
(External/PU combined operation mode 1)
78
(j)
Inputs to terminal STF and STR give a start command, and inputs to terminal RH, RM, and RL give a
frequency command. (External operation mode)
79
(k)
Inputs to terminal STF and STR give a start command, and voltage input to terminal 2 gives a frequency
command. (External operation mode)
80
(l)
Inputs to terminal STF and STR give a start command, and current input to terminal 4 gives a frequency
command. (External operation mode)
82
ON
Frequency
Time
(S)
(Hz)
Start command
Frequency command
Inverter
output
frequency
Step of operation
Installation/mounting
Control method selection
Wiring of the power
supply and motor
Connect a switch, relay, etc.
to the control circuit
terminal block of the inverter
to give a start command. (External)
Start command via the PU
connector and RS-485 terminal of
the inverter and plug-in option
(Communication)
Set from the PU.
(PU)
Set from the PU.
Change of frequency
with ON/OFF switches
connected to terminals
(multi-speed setting)
(External) (External)
(PU) (External) (External) (External)
How
to give a start
to give a start
command?
How
to give a start
command?
How to
give a frequency
command?
How to
give a frequency
command?
(a)
(b)
(c)
(d)
(e) (f) (g) (h)
(i) (j) (k) (l)
Perform frequency
setting by a current
output device
(Connection across
terminals 4 and 5)
Perform frequency
setting by a voltage
output device
(Connection across
terminals 2 and 5)
Perform frequency
setting by a current
output device
(Connection across
terminals 4 and 5)
Perform frequency
setting by a voltage
output device
(Connection across
terminals 2 and 5)
How to
w
give a frequency
re
command?
m
How to
give a frequency
command?
Change frequency
with ON/OFF switches
connected to terminals
(multi-speed setting)
(External)
Start command with
on the operation panel (PU)
: Initial setting
About the related manuals
INTRODUCTION
13
1
1.4 About the related manuals
The manuals related to FR-F860 are shown below.
Manual name Manual number
FR-F860 Instruction Manual (Startup) IB-0600690ENG
FR-F862 (Separated Converter Type) Instruction Manual (Hardware) IB-0600689ENG
FR-CC2-C (Converter unit) Instruction Manual IB-0600572ENG
FR Configurator2 Instruction Manual IB-0600516ENG
PLC function programming manual IB-0600492ENG
MEMO
14
INSTALLATION AND WIRING
15
2
2 INSTALLATION AND
WIRING
This chapter explains the installation and the wiring of this product.
Always read the instructions before using the equipment.
For the INSTALLATION AND WIRING of the separated converter type,
refer to the FR-F862 (Separated Converter Type) Instruction Manual
(Hardware).
2.1 Peripheral devices ....................................................................16
2.2 Removal and reinstallation of the front covers..............................20
2.3 Installation of the inverter and enclosure design ..................23
2.4 Terminal connection diagrams ................................................31
2.5 Main circuit terminals ...............................................................33
2.6 Control circuit ...........................................................................40
2.7 Communication connectors and terminals............................53
2.8 Connection of stand-alone option units .................................57
Peripheral devices
16
INSTALLATION AND WIRING
2.1 Peripheral devices
2.1.1 Inverter and peripheral devices
Earth (Ground)
R/L1 S/L2 T/L3
P1P/+
: Install these options as required.
UVW
IM connection
PM connection
(c) Molded case circuit
breaker (MCCB) or
earth leakage current
breaker (ELB), fuse
(e) AC reactor (f) DC reactor
(i) Noise filter
UVW
(k) Contactor
Example) No-fuse
switch
(DSN type)
(l) PM motor
(g) Noise filter
(d) Magnetic contactor (MC)
(a) Inverter
(b) Three-phase AC power supply
(h) USB connector
USB host
(A connector)
USB device
(Mini B connector)
Communication
status indicator
(LED)(USB host)
Earth
(Ground)
Earth
(Ground)
USB
Personal computer
(FR Configurator2)
(j) Induction
motor
Earth (Ground)
Earth (Ground)
Peripheral devices
INSTALLATION AND WIRING
17
2
NOTE
To prevent an electric shock, always earth (ground) the motor and inverter.
Do not install a power factor correction capacitor or surge suppressor or capacitor type filter on the inverter's output side.
Doing so will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices is
connected, immediately remove it. When installing a molded case circuit breaker on the output side of the inverter, contact
the manufacturer of the molded case circuit breaker.
Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. Refer to page 61 for countermeasures.
For details of options and peripheral devices, refer to the respective Instruction Manual.
A PM motor cannot be driven by the commercial power supply.
A PM motor is a motor with permanent magnets embedded inside. High voltage is generated at the motor terminals while the
motor is running. Before closing the contactor at the output side, make sure that the inverter power is ON and the motor is
stopped.
Symbol Name Overview
Refer
to page
(a) Inverter (FR-F860)
The life of the inverter is influenced by the surrounding air temperature.
The surrounding air temperature should be as low as possible within the
permissible range. This must be noted especially when the inverter is
installed in an enclosure.
Incorrect wiring may lead to damage of the inverter. The control signal
lines must be kept fully away from the main circuit lines to protect them
from noise.
23, 31
(b) Three-phase AC power supply Must be within the permissible power supply specifications of the inverter. 544
(c)
Molded case circuit breaker (MCCB),
earth leakage circuit breaker (ELB), or
fuse
Must be selected carefully since an inrush current flows in the inverter at
power ON.
18
(d) Magnetic contactor (MC)
Install this to ensure safety.
Do not use this to start and stop the inverter. Doing so will shorten the life
of the inverter.
64
(e) AC reactor
Install this to suppress harmonics and to improve the power factor.
An AC reactor is required when installing the inverter near a large power
supply system (1000 kVA or more). Under such condition, the inverter
may be damaged if you do not use a reactor.
Select a reactor according to the applied motor capacity.
63
(f) DC reactor
Install this to suppress harmonics and to improve the power factor.
Select a reactor according to the applicable motor capacity.
For the FR-F860-01080 or higher, or a motor with a capacity of 75 kW or
higher, always connect a DC reactor.
When using the DC reactor with the FR-F860-00680 or lower, remove the
jumper across terminals P/+ and P1 before connecting the DC reactor to
the inverter.
63
(g) Noise filter Suppresses the noise radiated from the power supply side of the inverter. 61
(h) USB connection
A USB (Ver. 1.1) cable connects the inverter with a personal computer.
A USB memory device enables parameter copies and the trace function.
55
(i) Noise filter
Install this to reduce the electromagnetic noise generated from the
inverter. The noise filter is effective in the range from about 0.5 MHz to 5
MHz.
A wire should be wound four turns at maximum.
61
(j) Induction motor Connect a squirrel-cage induction motor.
(k)
Contactor
Example) No-fuse switch (DSN type)
Connect this for an application where a PM motor is driven by the load
even while the inverter power is OFF. Do not open or close the contactor
while the inverter is running (outputting).
(l) PM motor
A PM motor can be used. A PM motor cannot be driven by the
commercial power supply.
Peripheral devices
18
INSTALLATION AND WIRING
2.1.2 Peripheral devices
Check the model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.
Refer to the table below to prepare appropriate peripheral devices.
SLD rating (Pr.570 Multiple rating setting = "0")
NOTE
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cables and reactors according to the motor output.
When the breaker on the inverter's input side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter etc. The cause of the trip must be identified and removed before turning ON the power of the breaker.
Motor output
(kW)

Applicable
inverter model
Molded case circuit breaker (MCCB)
or
earth leakage circuit breaker (ELB)
(NF, NV type)
Input-side magnetic contactor
Power factor improving (AC or DC)
reactor
Power factor improving (AC or DC)
reactor
Without With Without With
1.5 FR-F860-00027 10 A 5 A 5 A 3 A
3.7 FR-F860-00061 15 A 10 A 11 A 7 A
5.5 FR-F860-00090 30 A 15 A 16 A 9 A
11 FR-F860-00170 50 A 30 A 27 A 17 A
22 FR-F860-00320 60 A 50 A 43 A 33 A
30 FR-F860-00450 100 A 60 A 61 A 47 A
45 FR-F860-00680 125 A 100 A 88 A 68 A
75 FR-F860-01080 150 A 133 A
110 FR-F860-01440 175 A 135 A
110 FR-F860-01670 225 A 160 A
185 FR-F860-02430 300 A 231 A
220 FR-F860-02890 350 A 266 A
260 FR-F860-03360 400 A 316 A
335 FR-F860-04420 500 A 414 A
 Assumes the use of a 4-pole standard motor with the power supply voltage of 575 VAC 50 Hz.
 Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the Instruction
Manual (Startup) or Instruction Manual (Hardware) to select an appropriate fuse or MCCB.
 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input side current as JEM 1038-AC-3 class rated
current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose motor,
select an MC regarding the rated motor current as JEM 1038-AC-3 class rated current.
MCCB INV
MCCB INV
M
M
Peripheral devices
INSTALLATION AND WIRING
19
2
LD rating (Pr.570 Multiple rating setting = "1")
NOTE
When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cables and reactors according to the motor output.
When the breaker on the inverter's input side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter etc. The cause of the trip must be identified and removed before turning ON the power of the breaker.
Motor output
(kW)

Applicable
inverter model
Molded case circuit breaker (MCCB)
or
earth leakage circuit breaker (ELB)
(NF, NV type)
Input-side magnetic contactor
Power factor improving (AC or DC)
reactor
Power factor improving (AC or DC)
reactor
Without With Without With
1.12 FR-F860-00027 10 A 5 A 5 A 3 A
2.2 FR-F860-00061 15 A 10 A 11 A 6 A
3.7 FR-F860-00090 20 A 15 A 14 A 9 A
7.5 FR-F860-00170 50 A 30 A 25 A 16 A
18.5 FR-F860-00320 60 A 40 A 36 A 27 A
30 FR-F860-00450 100 A 60 A 55 A 41 A
45 FR-F860-00680 125 A 100 A 79 A 63 A
75 FR-F860-01080 125 A 98 A
90 FR-F860-01440 175 A 127 A
110 FR-F860-01670 200 A 146 A
150 FR-F860-02430 300 A 192 A
185 FR-F860-02890 350 A 234 A
220 FR-F860-03360 400 A 282 A
300 FR-F860-04420 500 A 373 A
 Assumes the use of a 4-pole standard motor with the power supply voltage of 575 VAC 50 Hz.
 Select an MCCB according to the power supply capacity.
Install one MCCB per inverter.
For the use in the United States or Canada, refer to "Instructions for UL and cUL" in the Instruction
Manual (Startup) or Instruction Manual (Hardware) to select an appropriate fuse or MCCB.
 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during motor driving, select an MC regarding the inverter input side current as JEM 1038-AC-3 class rated
current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose motor,
select an MC regarding the rated motor current as JEM 1038-AC-3 class rated current.
MCCB INV
MCCB INV
M
M
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350
  • Page 351 351
  • Page 352 352
  • Page 353 353
  • Page 354 354
  • Page 355 355
  • Page 356 356
  • Page 357 357
  • Page 358 358
  • Page 359 359
  • Page 360 360
  • Page 361 361
  • Page 362 362
  • Page 363 363
  • Page 364 364
  • Page 365 365
  • Page 366 366
  • Page 367 367
  • Page 368 368
  • Page 369 369
  • Page 370 370
  • Page 371 371
  • Page 372 372
  • Page 373 373
  • Page 374 374
  • Page 375 375
  • Page 376 376
  • Page 377 377
  • Page 378 378
  • Page 379 379
  • Page 380 380
  • Page 381 381
  • Page 382 382
  • Page 383 383
  • Page 384 384
  • Page 385 385
  • Page 386 386
  • Page 387 387
  • Page 388 388
  • Page 389 389
  • Page 390 390
  • Page 391 391
  • Page 392 392
  • Page 393 393
  • Page 394 394
  • Page 395 395
  • Page 396 396
  • Page 397 397
  • Page 398 398
  • Page 399 399
  • Page 400 400
  • Page 401 401
  • Page 402 402
  • Page 403 403
  • Page 404 404
  • Page 405 405
  • Page 406 406
  • Page 407 407
  • Page 408 408
  • Page 409 409
  • Page 410 410
  • Page 411 411
  • Page 412 412
  • Page 413 413
  • Page 414 414
  • Page 415 415
  • Page 416 416
  • Page 417 417
  • Page 418 418
  • Page 419 419
  • Page 420 420
  • Page 421 421
  • Page 422 422
  • Page 423 423
  • Page 424 424
  • Page 425 425
  • Page 426 426
  • Page 427 427
  • Page 428 428
  • Page 429 429
  • Page 430 430
  • Page 431 431
  • Page 432 432
  • Page 433 433
  • Page 434 434
  • Page 435 435
  • Page 436 436
  • Page 437 437
  • Page 438 438
  • Page 439 439
  • Page 440 440
  • Page 441 441
  • Page 442 442
  • Page 443 443
  • Page 444 444
  • Page 445 445
  • Page 446 446
  • Page 447 447
  • Page 448 448
  • Page 449 449
  • Page 450 450
  • Page 451 451
  • Page 452 452
  • Page 453 453
  • Page 454 454
  • Page 455 455
  • Page 456 456
  • Page 457 457
  • Page 458 458
  • Page 459 459
  • Page 460 460
  • Page 461 461
  • Page 462 462
  • Page 463 463
  • Page 464 464
  • Page 465 465
  • Page 466 466
  • Page 467 467
  • Page 468 468
  • Page 469 469
  • Page 470 470
  • Page 471 471
  • Page 472 472
  • Page 473 473
  • Page 474 474
  • Page 475 475
  • Page 476 476
  • Page 477 477
  • Page 478 478
  • Page 479 479
  • Page 480 480
  • Page 481 481
  • Page 482 482
  • Page 483 483
  • Page 484 484
  • Page 485 485
  • Page 486 486
  • Page 487 487
  • Page 488 488
  • Page 489 489
  • Page 490 490
  • Page 491 491
  • Page 492 492
  • Page 493 493
  • Page 494 494
  • Page 495 495
  • Page 496 496
  • Page 497 497
  • Page 498 498
  • Page 499 499
  • Page 500 500
  • Page 501 501
  • Page 502 502
  • Page 503 503
  • Page 504 504
  • Page 505 505
  • Page 506 506
  • Page 507 507
  • Page 508 508
  • Page 509 509
  • Page 510 510
  • Page 511 511
  • Page 512 512
  • Page 513 513
  • Page 514 514
  • Page 515 515
  • Page 516 516
  • Page 517 517
  • Page 518 518
  • Page 519 519
  • Page 520 520
  • Page 521 521
  • Page 522 522
  • Page 523 523
  • Page 524 524
  • Page 525 525
  • Page 526 526
  • Page 527 527
  • Page 528 528
  • Page 529 529
  • Page 530 530
  • Page 531 531
  • Page 532 532
  • Page 533 533
  • Page 534 534
  • Page 535 535
  • Page 536 536
  • Page 537 537
  • Page 538 538
  • Page 539 539
  • Page 540 540
  • Page 541 541
  • Page 542 542
  • Page 543 543
  • Page 544 544
  • Page 545 545
  • Page 546 546
  • Page 547 547
  • Page 548 548
  • Page 549 549
  • Page 550 550
  • Page 551 551
  • Page 552 552
  • Page 553 553
  • Page 554 554
  • Page 555 555
  • Page 556 556
  • Page 557 557
  • Page 558 558
  • Page 559 559
  • Page 560 560
  • Page 561 561
  • Page 562 562
  • Page 563 563
  • Page 564 564
  • Page 565 565
  • Page 566 566
  • Page 567 567
  • Page 568 568
  • Page 569 569
  • Page 570 570
  • Page 571 571
  • Page 572 572
  • Page 573 573
  • Page 574 574
  • Page 575 575
  • Page 576 576
  • Page 577 577
  • Page 578 578
  • Page 579 579
  • Page 580 580
  • Page 581 581
  • Page 582 582
  • Page 583 583
  • Page 584 584
  • Page 585 585
  • Page 586 586
  • Page 587 587
  • Page 588 588
  • Page 589 589
  • Page 590 590