Powerware 9 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

This manual is also suitable for

powerware
®
9
Prestige Series
User’s Guide
600 VA - 1800 VA
www.powerware.com
02/20/2001
FCC Statement
The Powerware 9 Prestige Series UPS configurations vary. Some configurations may or may not be classified by the
Federal Communications Commission (FCC). If your Prestige unit is classified by these standards, the corresponding
information applies:
Class A
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause interference to radio
communications. Operation of this equipment in a residential area is likely to cause interference in which case the user
will be required to correct the interference at his own expense.
Class B
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a residential installation. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
European EMC Statement
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these
configurations, the following applies:
WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
EC Declaration of Conformity
Units that are labeled with a CE mark comply with the following EU directives:
73/23/EEC Council Directive on equipment designed for use within certain voltage limits.
93/68/EEC Amending Directive 73/23/EEC.
89/336/EEC Council Directive relating to electromagnetic compatibility.
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC
Declaration of Conformity, contact:
Powerware Corporation
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452661
Fax: +358-9-452-66395
Powerware, PowerPass, Powercare, OnliNet, and OnliSafe are registered trademarks of Powerware Corporation.
IBM and AS/400 are registered trademarks of International Business Machines Corp.
Novell is a registered trademark of Novell, Inc.
3Com is a registered trademark of 3Com Corporation.
Copyright 1993-99 Powerware Corporation, Raleigh, North Carolina, U.S.A. All rights reserved. No part of this
document may be reproduced in any way without the express written approval of Powerware Corporation.
120V MODEL QUICK INSTALLATION
1
2
230V MODEL QUICK INSTALLATION
NOTE For208, 220,or 240Vmodels, followthe instructionsfor changing theoutput voltage on
page 32.
1
2
i
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
TABLE OF CONTENTS
1 Introduction 1....................................................
UPSModeland BatteryConfigurations 2..............................................
LoadRequirements 2.........................................................
BatteryTimes 3.............................................................
Special Symbols 7..............................................................
2 Safety Warnings 9.................................................
Sikkerhedsanvisninger 10.........................................................
BelangrijkeVeiligheidsinstructies 12..................................................
TarkeitaTurvaohjeita 13..........................................................
Consignes desécuri 15..........................................................
Sicherheitswarnungen 16.........................................................
18................................................
Avvisi di sicurezza 20.............................................................
ViktigSikkerhetsinformasion 21.....................................................
Regulamentosde Segurança 23.....................................................
Предупреждения по мерам безопасности 24...................................
Advertenciasde Seguridad 26......................................................
Säkerhetsföreskrifter 27..........................................................
3 Installation 29.....................................................
Unpacking andInspection 29.......................................................
UPSand BatteryCabinet Storage 29...............................................
UPSand BatteryCabinet Installation 29...............................................
UPSStartup for120V Models 31..................................................
UPSStartup for208V-240VModels 32..............................................
Troubleshooting Tips 34...........................................................
4 UPS Operation 35..................................................
UPSFrontPanel 35..............................................................
Operating Modes 36.............................................................
NormalMode 36.............................................................
Bypass Mode 37.............................................................
BatteryMode 37.............................................................
Table of Contents
ii
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Diagnostics 38.................................................................
BatteryTeston Demand 38......................................................
BatteryStart 39................................................................
UPSShutdown 39...............................................................
Changingthe Output Voltage 39.....................................................
Usingthe PowerPass 40..........................................................
UsingMaintenanceBypass 41....................................................
5 Communication 45.................................................
InitialCommunicationsSettings 45...................................................
FrontPanel CommunicationsAccess 46...............................................
UPSSerialCommunicationsMenu 48.................................................
PowerManagement Software 51....................................................
UPSCommunicationsInterfacePort 52................................................
Communications Mode ReferenceChart 53.............................................
6 Specifications 55..................................................
Prestige UPS ModelSpecifications 55................................................
Prestige UPS PhysicalSpecifications 56...............................................
Prestige UPS TechnicalSpecifications 56..............................................
7 Troubleshooting 57.................................................
Resetting the UPS 59............................................................
Silencingthe Alarm 59...........................................................
Service andSupport 60...........................................................
Index 61.........................................................
1
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
CHAPTER 1
INTRODUCTION
Congratulations on the purchase of your Powerware 9 Prestige Series
uninterruptible power system (UPS). The Prestige UPS meets the
toughest measures of superior design and manufacturing, including
ISO 9001. You now own the most reliable power protection available.
The Prestige provides a steady, well-regulated power supply for your
computingand communications equipment, while protecting it from the
frequent irregularities that are inherent in commercially available power.
Voltage spikes,power surges, brownouts, and power failures have the
potential to corrupt critical data, destroy unsaved work sessions, and in
some instances, damage expensive hardware.
With the Prestige, you can safely eliminate the effects of electrical line
disturbances and guard the integrity of your systems and equipment.
The optional PowerPass
has a Maintenance Bypass feature that supplies
power to your equipment even when the UPS electronics are removed
for maintenance or upgrades. Figure 1 shows the Prestige UPS.
Figure1.PrestigeUPS
Introduction
2
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
UPS Model and Battery Configurations
This UPS is designed to work with single-phase, three-wire, AC power
sources. There are two important considerations when selecting the UPS
model and battery configuration to properly safeguard your equipment:
Load requirements
Battery times
Load Requirements
The load is the equipment to be protected by the UPS.Select the UPS
model that meets the power consumption requirements of the load in
volt-amperes (VA). The total load VA should not exceed the UPS VA
rating. To determine the total load requirements:
1. Obtain the load ratings from either the nameplate oroperator’s
manual of the equipment to be protected by the UPS. The
ratings are listed in either watts (W), amperes or amperes
max (A), or volt-amperes.
2. If the rating is in watts, multiply by 1.4 to obtain the VA
requirement (this is the typical relationship betweenwatts and
volt-ampere ratings in most computing equipment). However,
in some new computing equipment, the power supply is
power-factor corrected and the watts rating equals the VA
requirement. Check with the manufacturer to determine
applicability.
If the rating is in amperes or amperes max,multiply by the
input voltage to obtain the VA requirement.
Introduction
3
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
3. Add all of the resultant VA ratings together to obtain the total
load requirements of the equipment to be protected (see
Figure 2).If the load consists of the power-factor corrected
supplies, it is recommended to use total watts for the load
requirements.
COMPUTER MONITOR EXTERNAL
MODEM
100 WATTS x 1.4 = 140 VA
2AMPERESx120=240VA
50 VA
140 VA + 240 VA + 50 VA = 430 VA (Total Load Requirements)
100WATTS 2AMPS 50VA
or 1 AMPERE x 240 = 240 VA
Figure 2. Volt-Amperes Calculation Example
If the total load requirements of the equipment exceeds the capacity of
the UPS, you must either reduce the number of pieces of equipment, or
use a UPS with a larger load capacity.
When deciding on which pieces of equipment to remove from the UPS,
select equipment that has a lower priority for power protection.
Computers, monitors, and modems typically have a higher priority
because they could be processing or transmitting data when a power
outage occurs.
Battery Times
During a power failure, the UPS battery supplies power to your
equipment, providing time to complete computing activities prior to
UPS shutdown. The duration of this time period is directly related to the
UPS battery configuration. By adding battery cabinets (EXT models
only), you can customize the UPS to provide enough battery time for
normal processing activities.
The rating label on the UPS rear panel shows the model number. Model
numbers with a “P2” are EXT units; numbers with “HV” are high
voltage units (208 - 240V models). The following tables show the
average battery times by product model.
Introduction
4
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Prestige 600 - 1500 VA, 120V Models
Load
(
V
A
)
a
t
Load
InternalUPS Batteries(Rounded to theNearestMinute)
(VA) at
.7 PF*
L
o
a
d
(W)
650 800 1000 750 EXT 1000 EXT 1250 EXT 1500 EXT
200 140 37 37 37 68 68 68 68
400 280 22 22 22 32 32 32 32
600 420 12 12 12 20 20 20 20
800 560 8 8 15 14 14 14
1000 700 6 11 11 11
1250 875 8 8
1500 1050 6
Load
L
o
a
d
ExternalBatteryCabinetConfigurationsforEXT Models
L
o
a
d
(VA) at
.7 PF*
Load
(W)
1/2
Cabinet
1
Cabinet
11/2
Cabinets
2
Cabinets
21/2
Cabinets
3
Cabinets
31/2
Cabinets
4
Cabinets
200 140 143 216 290 364 438 513 589 663
400 280 69 115 158 198 239 280 320 362
600 420 43 73 105 137 165 194 221 249
750 525 33 56 80 106 134 156 178 202
1000 700 23 39 57 75 95 114 135 151
1250 875 17 30 42 56 70 86 102 118
1500 1050 14 23 32 43 55 67 78 91
Typical Power Factor (PF); 750 VA, 525W
Introduction
5
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Prestige 600 - 1250 VA, 208 -240V Models
Load
(
V
A
)
L
o
a
d
InternalUPS Batteries(Rounded to theNearestMinute)
(VA)
at
.7 PF*
Load
(W)
600 800 1000
800
EXT
1000
EXT
1250
EXT
200 140 33 33 33 56 56 56
400 280 21 21 21 29 29 29
600 420 11 11 11 19 19 19
800 560 7 7 13 13 13
1000 700 6 10 10
1250 875 8
Load
(
V
A
)
L
o
a
d
ExternalBatteryCabinetConfigurationsforEXT Models
(
VA
)
at
.7 PF*
Load
(W)
1/2
Cabinet
1
Cabinet
11/2
Cabinets
2
Cabinets
21/2
Cabinets
3
Cabinets
31/2
Cabinets
4
Cabinets
200 140 133 203 274 346 418 491 564 637
400 280 70 117 159 201 243 285 328 371
600 420 46 76 110 141 171 200 230 260
800 560 33 55 79 105 132 153 176 199
1000 700 25 42 61 81 102 124 147 161
1250 875 19 32 46 61 77 94 111 129
Typical Power Factor (PF)
Introduction
6
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Prestige 1500 - 1800 VA, 208 -240V Models
Load
UPS with External BatteryCabinetConfigurations(Roundedto the NearestMinute)
L
o
a
d
(VA)
at
.7 PF*
Load
(W)
Internal
UPS
Battery
1/2
Cabinet
1
Cabinet
11/2
Cabinets
2
Cabinets
21/2
Cabinets
3
Cabinets
31/2
Cabinets
4
Cabinets
200 140 59 128 194 260 327 393 460 527 595
400 280 29 64 107 149 186 224 263 302 339
600 420 19 42 71 102 135 161 189 217 244
800 560 14 32 52 76 100 125 148 169 191
1000 700 11 24 41 59 77 98 119 138 156
1250 900 8 19 32 45 59 76 92 108 125
1500 1050 7 14 25 36 48 60 73 86 101
1800 1200 5 12 20 29 38 48 59 69 80
Typical Power Factor (PF)
Introduction
7
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Special Symbols
The following common symbols may be found on the UPS:
LOAD ON - Press the button with this symbol to energize the
output receptacles (Output On).
LOAD OFF - Press the button with this symbol to de-energize
the output receptacles (Output Off).
SAFETY EARTHING TERMINAL - Indicates the primary safety
ground.
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric
shock is present and the associated warning should be
observed.
CAUTION: REFER TO OPERATORS MANUAL - Refer to your
operator’s manual for additional information.
This symbol indicates that the UPS batteries should not be
discarded in the trash. The UPS contains sealed lead
batteries and must be disposed of properly. For battery
replacement or removal, call your
Local Distributor or the
Help Desk at one of the telephone numbers on page 60.
Introduction
8
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
9
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
CHAPTER 2
SAFETY WARNINGS
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.Thismanualcontainsimportant instructionsthat you
should followduring installation of theUPS.Pleaseread all instructionsbefore
operatingthe equipment and save thismanual forfuture reference.
DANGER
ThisUPScontainsLETHAL VOLTAGES.Allrepairsand service should beperformed
byAUTHORIZED SERVICE PERSONNEL ONLY. Thereare NO USER
SERVICEABLE PARTS inside theUPS.
CAUTION
Batteriescan present a riskof electricalshockor burnfrom highshortcircuit
current.Observeproper precautions.
Proper disposalof batteriesisrequired.Refer to your localcodesfor disposal
requirements.
ThisUPScontainsitsown energysource (batteries).The outputreceptaclesmay
carrylivevoltageeven when theUPS is not connected toan ACsupply.
Neverdisposeofbatteriesinafire.Batteriesmayexplodewhenexposedtoflame.
Neveropen or mutilatebatteries. Released electrolyte isharmfulto the skin and
eyes,and maybe extremelytoxic.
Useonlythepower supplycord providedwith thisUPS.Thepower cordiswiredin
accordancewithNationalElectricalCode (NEC) specifications. Be sure thewall
outletto be used with the UPS iswiredin accordance with these same
specificationsin orderto avoid damageto yourequipment.Besure that
overcurrent protectionfor the AC outlet isprovidedat the time ofinstallation. Be
surethe inputplug iscompletelyinserted intothe walloutlet.Useasingle-phase,
three-wire,grounded ACoutlet only.
To reducethe riskof fireor electricshock,installthisUPSina temperature and
humiditycontrolled,indoorenvironment,freeofconductivecontaminants.Ambient
temperature mustnot exceed 104 F(40C).Donot operate nearwater or
excessive humidity (95% max).
Safety Warnings
10
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Donot remove orunplug theinput cord whenthe UPSisturned on.This removes
the safetyground from theUPSand the equipment connected tothe UPS.
Tocomplywithinternationalstandardsandwiringregulations,thetotalequipment
connected tothe output ofthisUPSmustnot havean earth leakagecurrent
greater than 2.75 milliamperes.
The wall outlet must bewithin 2 metersof the equipment andaccessible tothe
operator. Theon/off switch on theUPSdoes notelectrically isolatethe internal
parts.Unplug theinput cord fromthe walloutlet when disconnecting the unit for
longperiodsof time.
Please notethat the outputsocketson the UPS areelectrically livewhenever the
UPSOutput
Onbutton ispressed,evenif theinput cord isdisconnected.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER
GEM DISSE ANVISNINGER
DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE
SIKKERHEDSANVISNINGER
FARE
DenneUPSindeholderLIVSFARLIGHØJSPÆNDING.Alle reparationer og
vedligeholdelse børkun udføresaf enAUTORISERET SERVICETEKNIKER.Ingenaf
UPS’ens indvendige delekanrepareres afbrugeren.
ADVARSEL
Batterierkanudgøreenfareforelektriskstødellerforbrændingerforårsagetafhøj
kortslutningsspænding.De korrekteforholdsregler børoverholdes.
Korrektbortskaffelseaf batteriererpåkrævet.Overholdgældendelokalereglerfor
bortskaffelsesprocedurer.
DenneUPSindeholderegen energiforsyning (batterier).Udgangsnetstikkenekan
ledestrøm,selvnår UPS’en ikke er tilsat en AC-energikilde.
Skafdigaldrigaf med batteriernevedat brænde dem.Batterierne kaneksplodere
vedåben ild.
Batteriernebør aldrig åbnesellerskilles ad. Elektrolyt, der slipper ud,er skadelig
for hudog øjneog kanværeoverordentlig giftig.
Safety Warnings
11
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Brug kun den netledning,somblevleveretmed UPS’en.Denne netledninger
tilsluttet ifølge specifikationernefor NEC(NationalElectricalCode).Sørgfor, at
stikket,somskalbrugestilUPS’en,ertilsluttetifølgedesammespecifikationerfor
at undgåskadepå ditudstyr.Sørg for,at der eroverstrømsbeskyttelse på
AC-stikket på monteringstidspunktet.Sørg for,at stikket ersat helt indi
stikkontakten.Brug enenfaset,-treledetAC-kilde, som er jordet.
Installér denneUPS iet temperatur- ogfugtighedskontrolleret indendørsmiljø, frit
for ledende forureningsstoffer forat formindske risikoenfor brand ogelektrisk
stød.Rumtemperaturen måikke overstige 40°C.UPS’enbør ikkebetjenesnær
vandellerhøj fugtighed (maksimalt95%).
Netledningen måikke fjernesog stikket må ikke trækkesud, mensUPS’ener
tændt.Dettefjerner sikkerhedsjordenfra UPS’en ogfra det udstyr,der er sat til.
Ioverensstemmelsemedinternationalenormerogbestemmelserforel-installation
må detudstyr,der er forbundettiludgangen afdenne UPS,tilsammenikke
overskride en jordafdelingsspænding på mere end 2,75 milliampere.
Stikkontaktenmå højst være 2 meter fraudstyretog tilgængeligfor brugeren.
UPS’ens afbryderkontakt isolerer ikkeelektriskde indvendigedele.Trækderfor
stikket udaf kontakten,hvisenheden erslukketi lang tid adgangen.
Bemærkvenligst,at stikkontakterne på UPS’en erstrømførende,når knappenUPS
Output
On” er trykket ned, selvomindgangsnedledningen ikke er tilsluttet.
Safety Warnings
12
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
BEWAAR DEZEINSTRUCTIES
DEZEHANDLEIDING BEVAT BELANGRIJKE
VEILIGHEIDSINSTRUCTIES
GEVAAR
DezeUPSbevat LEVENSGEVAARLIJKEELEKTRISCHE SPANNING.Alle reparatiesen
onderhoud dienen UITSLUITENDDOOR ERKEND SERVICEPERSONEELte worden
uitgevoerd.Er bevinden zich GEEN ONDERDELENin deUPSdie DOOR DE GEBRUIKER
kunnenworden GEREPAREERD.
OPGELET
Batterijen kunnengevaar voor elektrischeschok ofbrandwonden veroorzakenals
gevolg van unhoge kortsluitstroom.Volgde desbetreffendeaanwijzingenop.
Debatterijenmoetenopdejuistewijzewordenopgeruimd.Raadpleeghiervooruw
plaatselijke voorschriften.
DezeUPSbevat zijn eigenenergiebron(batterijen).Deuitgangsaansluitingen
kunnenonderspanningstaanwanneerdeUPSnietopeenwisselstroomvoedingis
aangesloten.
Nooitbatterijenin hetvuur gooien. De batterijen kunnenontploffen.
Nooitbatterijenopenenofbeschadigen.Vrijkomendelektrolytisschadelijk voor de
huiden ogen,en kanuiterstgiftigzijn.
Uitsluitendhet elektriciteitssnoergebruiken dat bij dezeUPSwordt geleverd. Het
snoerisvolgensde specificatiesvandeIEC(InternationalElectricalCode)bedraad.
Controleerof wandcontactdooswaaropde UPSwordt aangesloten,volgensdeze
zelfdespecificatiesisbedraad teneindeschadeaan uwapparatuur tevoorkomen.
Controleerof hetwandcontactdoosvoldoendeisafgezeherd. Controleerof de
voedingsstekker goedin hetstopcontact isgestoken.Gebruikuitsluitendeen
enkelfasig geaardwandcontactdoosmet randaarde.
Teneinde dekansop brand ofelektrische schokte verminderendient deze UPS in
een gebouwmet temperatuur- en vochtigheidregeling te wordengeïnstalleerd,
waargeengeleidendeverontreinigingenaanwezigzijn.Deomgevingstemperatuur
mag 40 Cnietoverschrijden.Nietgebruikeninde buurtvanwaterofbijzeerhoge
vochtigheid (max.95%).
Safety Warnings
13
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Verwijder deingangsnoerniet ofhaalde stekkervan deingangsnoerer nietuit
terwijldeUPSaanstaat.Hierdoorzoude UPSenuwaangeslotenapparatuurgeen
aardebeveiliging meer hebben.
Omaan deinternationale normenen bedradingsvoorschriften tevoldoenmag de
geheleapparatuur dieop de uitgang van dezeUPSisaangesloten,geen
aardlekstroom van meer dan 2,75 milliampère hebben.
Dehoofdvoedingcontactdoosmoetzichop minder dan2 metervan deapparatuur
bevinden enmakkelijk bereikbaar zijnvoor degebruiker.De aan/uit-schakelaar op
de UPS biedt geen elektrische isolatie voorde inwendige onderdelen.Destekker
uitde voedingcontactdooshalen wanneerhet apparaatvoor lange tijdniet wordt
gebruikt.
Neem ernota van datde uitgangaansluitpunten opde UPSaltijd onder stroom
staanwanneer debelastingschakelaar ( )wordt ingedrukt,ongeachtde
aanwezigheidvan devoeding.
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI
SÄILYTÄ NÄMÄ OHJEET
TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
VAARA
Tämä UPS sisältää HENGENVAARALLISIAJÄNNITTEITÄ.Kaikki korjaukset jahuollot
on jätettäväVAINVALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä
MITÄÄNKÄYTTÄJÄNHUOLLETTAVIAOSIA.
VARO
Akustosaattaa aiheuttaa sähköiskuntaisyttyä tuleen, jos akusto kytketään
oikosulkuun.Noudata asianmukaisiaohjeita.
Akustotäytyyhävittää säädöstenmukaisellatavalla.Noudata paikallisia
määyksiä.
Tämä UPS sisältääoman energialähteen (akuston).Ulostuloliittimissä voi olla
jännite,kun UPS eiole liitettynä verkkojännitteeseen.
Älä koskaan heitä akkuja tuleen. Nevoivat räjähtää.
Älä avaa tairiko akkuja.Paljastunut elektrolyyttion vahingollinen iholle ja silmille
ja voi olla eritin myrkyllistä.
Safety Warnings
14
Powerware
®
9PrestigeSeriesUser’sGuide (600 VA-1800 VA) www.powerware.com
Käytävaintämän UPS-laitteen mukana toimitettua virtakaapelia,jokaon kytketty
kansallisten äräysten mukaisesti. Varmista, että UPS-laitteen kanssa ytetty
pistorasia onjohdotettu näiden samojenmääritysten mukaisesti,jotta laitteet
eivät vahingoittuisi. Varmistamyös,että asennuksen yhteydessä vaihtovirran
pistorasiavarustetaanylivirtasuojauksella.Työnnäkosketinkokonaanpistorasiaan.
Käytä pelkästään yksivaihteista, kolmijohtoista, maadoitettua verkkopistorasiaa.
Vähentääksesitulipalonjasähköiskunvaaraaasenna tämäUPSsisätiloihin,joissa
lämpötila ja kosteus onsäädettävissä jajoissaei ole virtaa johtavia
epäpuhtauksia.Ympäristönlämpötilaeisaaylittää40 C.Älä käytä lähellä vettä ja
vältä kosteita tiloja (95 % maksimi).
Älä poistatai irrota sisääntulojohtoa,kun UPS onkytkettynä. Tämä poistaa
turvamaadoituksenUPS-laitteesta jasiihenliitetystä laitteistosta.
Kansainvälisetnormit ja johdotusmääräykset vaativat, et kaikkien tämän
UPS-laitteenulostulokytkentöjen yhteinen maavuotovirta eiylitä
2,75 milliampeeria (mA).
Päävirtapistokkeen täytyyolla2 m:n säteellä laitteistosta ja käyttäjän saatavilla.
UPS-laitteen virtakytkinei erotasisäosia verkkojännitteestä. Irrota
sisääntulopistoke,joskytketlaitteenpoiskäytöstä pitkähköksiajaksi.
Otamyöshuomioon,että UPS-laitteenulostuloliittimison jännite aina kun
painetaanUPSin lähtötehoPÄÄLLÄ-painiketta ( ),riippumattasiitä,onko
tulokaapelikytkettynä taiei.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70

Powerware 9 User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI