3com Powerware Prestige Series User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual
powerware
®
Prestige Series
3000 VA, 200-240V
Installation and Operators Manual for IBM Applications
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonic standards and EU directives:
Harmonic Standards: EN 50091-1-1 and EN 50091-2
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC
Declaration of Conformity, contact:
Powerware Corporation
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452 661
Fax: +358-9-452 665 68
Class A EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment
Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
EN50091-2
Some configurations are classified under EN50091-2 as “Class-A UPS for Unrestricted Sales Distribution.” For these
configurations, the following applies:
WARNING This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference, in
which case, the user may be required to take additional measures.
Powerware, PowerPass, Powercare, OnliNet, and OnliSafe are registered trademarks of Powerware Corporation.
IBM and AS/400 are registered trademarks of International Business Machines Corp.
Novell is a registered trademark of Novell, Inc.
3Com is a registered trademark of 3Com Corporation.
Copyright 1997-2000 Powerware Corporation, Raleigh, North Carolina, USA. All rights reserved. No part of this
document may be reproduced in any way without the express written approval of Powerware Corporation.
QUICK INSTALL
UPS with PPDM Quick Installation
1 If you are connecting the UPS to an AS/400, the QUPSDLYTIM system value for the UPS
Monitoring feature should be set. See “UPS Monitoring” on page 52 for instructions.
2
Battery
Cabinet
UPS
Cabinet
PowerPass
Distribution
Module
(PPDM,)
3
Bypass Switch
(NORMAL Position)
Quick Install
4
Battery
Breaker
I
O
ON
OFF
I
O
ON
OFF
5
6 The UPS output voltage is factory-configured for 230V. If you need to change the output
voltage, see “UPS with PPDM Startup” on page 42.
7 For the AS/400 interface, plug the AS/400 communications cable into the serial port on the
UPS rear panel. Plug the other end of the cable into the J14 connector or the connector
labeled “UPS” on your AS/400.
8
i
Powerware
®
PrestigeSeries Installationand Operator’sManualfor IBM Applications (3000 VA)Uncontrolled Copy
TABLE OF CONTENTS
1 Introduction 1....................................................
UPSModelandBattery Configurations 2..............................................
LoadRequirements 2.........................................................
Approximate BatteryTimes 3....................................................
SpecialSymbols 5..............................................................
2 Safety Warnings 7.................................................
3 Installation 35.....................................................
Unpacking andInspection 35.......................................................
UPSand BatteryCabinetStorage 35...............................................
UPSwithPowerPassDistributionModuleInstallation 35...................................
UPSwithPPDMStartup 42......................................................
REPOInstallation 44...........................................................
Troubleshooting Tips 46...........................................................
4 UPS Operation 47..................................................
UPSFrontPanel 47..............................................................
Operating Modes 48.............................................................
NormalMode 48.............................................................
BypassMode 49.............................................................
BatteryMode 49.............................................................
Diagnostics 50.................................................................
BatteryTeston Demand 50......................................................
BatteryStart 50................................................................
UPSShutdown 51...............................................................
Changing theOutputVoltage 51.....................................................
UPSMonitoring 52..............................................................
Usingthe PPDM 53..............................................................
Disconnecting theUPS 53.......................................................
Reconnecting the UPS 55.......................................................
5 Communication 57.................................................
InitialCommunicationsSettings 57...................................................
FrontPanel CommunicationsAccess 58...............................................
UPSSerialCommunicationsMenu 60.................................................
PowerManagementSoftware 63....................................................
Table of Contents
ii
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
UPSCommunicationsInterface Port 64................................................
CommunicationsMode Reference Chart 65.............................................
6 Specifications 67..................................................
3000 VAModelSpecification with PPDM 67............................................
Prestige 3000UPSPhysical Specifications 67...........................................
Prestige 3000UPSTechnical Specifications 68..........................................
Part Numbers 69................................................................
Base Equipment 69...........................................................
StandardAccessories 69........................................................
OptionalAccessories 70........................................................
Manuals 70.................................................................
7 Troubleshooting 71.................................................
Resetting theUPS 73............................................................
Silencing theAlarm 73...........................................................
8 AS/400 Service 75..................................................
Index 81.........................................................
1
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
CHAPTER 1
INTRODUCTION
Congratulations on the purchase of your Powerware Prestige Series
uninterruptible power system (UPS). The Prestige UPS meets the
toughest measures of superior design and manufacturing, including
ISO 9001. You now own the most reliable power protection available.
The Prestige 3000 provides a steady, well-regulated power supply for
your computing and communications equipment, while protecting it
from the frequent irregularities that are inherent in commercially
available power. Voltage spikes, power surges, brownouts, and power
failures have the potential to corrupt critical data, destroy unsaved work
sessions, and in some instances, damage expensive hardware.
With the Prestige 3000, you can safely eliminate the effects of electrical
line disturbances and guard the integrity of your systems and
equipment. The PowerPass
Distribution Module (PPDM) has a
Maintenance Bypass feature that supplies power to your equipment even
when the UPS electronics are removed for maintenance or upgrades.
Figure 1 shows the Prestige 3000 UPS.
Figure 1.Prestige 3000 UPS
Introduction
2
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
UPS Model and Battery Configurations
This UPS is designed to work with single-phase, three-wire, AC power
sources. There are two important considerations when selecting the UPS
model and battery configuration to properly safeguard your equipment:
Load requirements
Battery times
Load Requirements
The load is the equipment to be protected by the UPS. Select the UPS
model that meets the power consumption requirements of the load in
volt-amperes (VA). The total load VA should not exceed the UPS VA
rating. To determine the total load requirements:
1. Obtain the load ratings from either the nameplate or operator’s
manual of the equipment to be protected by the UPS. The
ratings are listed in either watts (W), amperes or amperes
max (A), or volt-amperes.
2. If the rating is in watts, multiply by 1.4 to obtain the VA
requirement (this is the typical relationship between watts and
volt-ampere ratings in most computing equipment). However,
in some new computing equipment, the power supply is
power-factor corrected and the watts rating equals the VA
requirement.Check with the manufacturer to determine
applicability.
If the rating is in amperes or amperes max, multiply by the
input voltage to obtain the VA requirement.
NOTE FortheloadratingsofAS/400modelsandattachabledevices,seeChapter9of
“AS/400PhysicalPlanning Reference,”SC41-5109.
3. Add all of the resultant VA ratings together to obtain the total
load requirements of the equipment to be protected (see
Figure 2). If the load consists of the power-factor corrected
supplies, it is recommended to use total watts for the load
requirements.
Introduction
3
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
3 COMPUTERS 3 MONITORS EXTERNAL
MODEM
3x200WATTSx1.4=840VA 3x1AMPx240=720VA 50VA
840 VA + 720 VA + 50 VA = 1610 VA (Total Load Requirements)
200 WATTS
EACH
1AMP
EACH AT 240V 50 VA
Figure 2. Volt-Amperes Calculation Example
If the total load requirements of the equipment exceeds the capacity of
the UPS, you must either reduce the number of pieces of equipment, or
use a UPS witha larger load capacity.
When deciding on which pieces of equipment to remove from the UPS,
select equipment that has a lower priority for power protection.
Computers, monitors, and modems typically have a higher priority
because they could be processing or transmitting data when a power
outage occurs.
Approximate Battery Times
During a power failure, the UPS battery supplies power to your
equipment, providing time to complete computing activities prior to
UPS shutdown. The duration of this time period is directly related to the
UPS battery configuration. By adding battery cabinets, you can
customize the UPS to provide enoughbattery time for normalprocessing
activities.
To prepare for a power outage at your installation, ensure that you have
sufficient battery time available. To do this, take a few minutes to
determine your approximate battery time by completing the following
steps:
Load
Battery Time
L
o
a
d
Requirements
(VA)
UPS Model BatteryCabinets Total Battery Time
Minutes(Approximate)
Prestige 3000 (9910 EP5)
Figure 3. Determining Approximate Battery Time
Introduction
4
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
1. See Load Requirements” on page 2 for assistance in
determining the total load requirements for your UPS. Round
this number up to the next Load (VA) entry in the following
table, “Prestige 3000 with PPDM,” and enter the number in
Figure 3.
2. In Figure 3, enter the number of battery cabinets that you
have installed. Find the intersection point of the appropriate
Load (VA) and number of battery cabinets in the following
table, “Prestige 3000 with PPDM.” Enter this number in
Figure 3, Total Battery Time Minutes.
If changes take place in your installation, such as different load
parameters or changes to battery cabinet configuration, take time to
reevaluate your approximate battery time availability.
NOTE Fordetailedinformationregardingcalculationof9910UPSbatterycapacityand
run timefor your load,reference: “AS/400 PhysicalPlanning,”SA41-5109,“AS/400
AdvancedSeriesBackup andRecovery- Advanced,”SC41-4305 (see Chapter10),or
“AS/400eseries Backup andRecovery,SC41-5304(seeChapter37).
Prestige 3000 with PPDM
L
o
a
d
(
V
A
)
L
o
a
d
(
W
)
Approximate BatteryTime(inMinutes)
Load (VA) Load (W)
1Cabinet 2Cabinets 3Cabinets
600 420 36.8 88 146
800 533 27.6 66 110
1200 800 18.4 44 73
1600 1067 13.7 33 54
2000 1333 10.7 26 42
2500 1667 8.3 20 33
3000 2000 6.5 16 27
NOTE For AS/400usage,see“Base Equipment”on page69.
Introduction
5
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Special Symbols
The following common symbols may be found on the UPS:
LOAD ON - Press the button with this symbol to energize the
output receptacles (Output On).
LOAD OFF - Press the button with this symbol to de-energize
the output receptacles (Output Off).
SAFETY EARTHING TERMINAL - Indicates the primary safety
ground.
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric
shock is present and the associated warning should be
observed.
CAUTION: REFER TO OPERATORS MANUAL - Refer to your
operator’s manual for additional information.
BYPASS - Indicates bypass control switches.
INPUT BREAKER - Indicates the input breaker, which shuts
off utility power to the UPS electronics.
BATTERY BREAKER - Indicates the battery breaker, which
shuts off battery power (power transmission through the
battery cord).
BATTERY CONNECTOR - Indicates the battery connector,
which remains electrically “hot” even with the battery
breaker off. Keep covered when not in use.
OUTPUT BREAKER - Indicates an output breaker.
Introduction
6
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Thispage intentionallyleft blank.
7
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
CHAPTER 2
SAFETY WARNINGS
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.Thismanualcontainsimportant instructionsthat you
should followduring installation ofthe UPS.Pleaseread all instructionsbefore
operatingthe equipment and save thismanualfor future reference.
DANGER
ThisUPScontainsLETHAL VOLTAGES. Allrepairsand serviceshould beperformed
byAUTHORIZED SERVICE PERSONNEL ONLY.There areNO USER
SERVICEABLE PARTS insidethe UPS.
CAUTION
Batteriescanpresenta riskof electricalshockor burnfromhighshortcircuit
current.Observeproper precautions.
Proper disposalof batteriesisrequired.Refer to yourlocalcodesfor disposal
requirements.
ThisUPScontainsitsown energysource (batteries).The outputreceptaclesmay
carrylivevoltage even whenthe UPSisnot connected toan AC supply.
Neverdisposeofbatteriesinafire.Batteriesmayexplodewhenexposedtoflame.
Neveropen or mutilatebatteries.Released electrolyteisharmfulto the skin and
eyes,and maybe extremelytoxic.
Useonlythepower supplycordprovidedwith thisUPS.Thepower cordiswiredin
accordancewith NationalElectricalCode (NEC)specifications.Be sure thewall
outletto be used with theUPSiswiredin accordance with these same
specificationsinorder toavoiddamage to your equipment. Be sure that
overcurrent protectionfor theACoutletisprovided atthe time ofinstallation.Be
surethe inputplugiscompletely inserted into thewall outlet.Useasingle-phase,
three-wire,grounded AC outlet only.
Toreduce theriskof fire or electricshock,installthisUPSina temperature and
humiditycontrolled,indoorenvironment,freeofconductivecontaminants.Ambient
temperaturemust not exceed 104 F(40C).Donot operate nearwateror
excessive humidity (95% max).
Donot remove or unplug the input cord whenthe UPSisturned on.Thisremoves
the safetyground fromthe UPS andthe equipmentconnected tothe UPS.
Safety Warnings
8
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Tocomplywithinternationalstandardsandwiringregulations,thetotalequipment
connected tothe outputof thisUPSmustnot have anearth leakagecurrent
greater than 2.75 milliamperes.
The walloutlet mustbe within2 metersof theequipmentand accessible tothe
operator. Theon/offswitchon the UPS doesnot electricallyisolate theinternal
parts.Unplug theinputcordfrom thewall outlet when disconnectingthe unitfor
longperiodsof time.
Please notethat theoutput socketson theUPSare electricallylivewhenever the
UPSOutput
Onbutton ispressed,evenifthe inputcordisdisconnected.
For PowerPass systems with hardwired outputs, overcurrent protection for the
output ACcircuit(s) isto be providedbyothers.
For PowerPasssystemswithhardwiredoutputs,suitablyrated disconnectswitches
for theoutput ACcircuit(s)are tobe providedbyothers.
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER
GEM DISSE ANVISNINGER
DENNE BRUGERVEJLEDNING INDEHOLDER VIGTIGE
SIKKERHEDSANVISNINGER
FARE
DenneUPSindeholder LIVSFARLIGHØJSPÆNDING. Allereparationerog
vedligeholdelse børkunudføresaf en AUTORISERET SERVICETEKNIKER.Ingen af
UPS’ensindvendige dele kan repareresaf brugeren.
ADVARSEL
Batterierkanudgøreenfareforelektriskstødellerforbrændingerforårsagetafhøj
kortslutningsspænding.Dekorrekte forholdsregler børoverholdes.
Korrektbortskaffelseafbatteriererpåkrævet.Overholdgældendelokalereglerfor
bortskaffelsesprocedurer.
DenneUPSindeholder egenenergiforsyning (batterier).Udgangsnetstikkene kan
ledestrøm,selvnår UPS’en ikkeer tilsaten AC-energikilde.
Skaf dig aldrig afmedbatterierneved atbrændedem.Batteriernekaneksplodere
vedåben ild.
Safety Warnings
9
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Batterierne bør aldrig åbneseller skilles ad. Elektrolyt, der slipper ud,er skadelig
for hudog øjneog kan væreoverordentliggiftig.
Brugkunden netledning,somblevleveretmedUPS’en.Denne netledninger
tilsluttet ifølgespecifikationerne forNEC (NationalElectricalCode).Sørgfor,at
stikket,somskalbrugestilUPS’en,ertilsluttetifølgedesamme specifikationerfor
at undgåskadepå dit udstyr.Sørgfor,at derer overstrømsbeskyttelse på
AC-stikketpå monteringstidspunktet.Sørgfor,at stikketer sat helt indi
stikkontakten.Brug enenfaset,-treledetAC-kilde,somer jordet.
Installér denneUPSi ettemperatur- ogfugtighedskontrolleretindendørsmiljø, frit
for ledende forureningsstoffer forat formindske risikoenfor brandog elektrisk
stød.Rumtemperaturen måikkeoverstige40°C. UPS’enbør ikke betjenesnær
vandellerhøjfugtighed (maksimalt 95%).
Netledningen må ikkefjernesog stikketikketrækkesud,mensUPS’en er
tændt.Dettefjernersikkerhedsjordenfra UPS’enog fra detudstyr,der ersattil.
Ioverensstemmelsemedinternationalenormerogbestemmelserforel-installation
det udstyr,der erforbundet tiludgangen afdenne UPS,tilsammen ikke
overskride en jordafdelingsspænding på mere end 2,75 milliampere.
Stikkontakten må højstre 2meterfra udstyretog tilgængelig for brugeren.
UPS’ensafbryderkontakt isolerer ikke elektriskde indvendigedele.Tkderfor
stikket udaf kontakten,hvisenheden erslukket ilangtidad gangen.
Bemærkvenligst,at stikkontakterne påUPS’en erstrømførende,når knappenUPS
Output
On” er trykket ned, selvom indgangsnedledningen ikke ertilsluttet.
Med hensyn til Bypass-systemer med direkte forbundne udgange,skal
overstrømsbeskyttelsenfor AC-kredsen(e) komme andetstedsfra.
Med hensyn til Bypass-systemer med direkte forbundne udgange,skal
afbryderkontaktertilAC-kredsløbetmedpassenderkeeffektkommeandetsteds
fra.
Safety Warnings
10
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES
BEWAAR DEZE INSTRUCTIES
DEZEHANDLEIDING BEVAT BELANGRIJKE
VEILIGHEIDSINSTRUCTIES
GEVAAR
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Allereparatiesen
onderhoud dienen UITSLUITENDDOOR ERKEND SERVICEPERSONEELte worden
uitgevoerd.Er bevinden zich GEEN ONDERDELEN in deUPSdieDOOR DE GEBRUIKER
kunnenworden GEREPAREERD.
OPGELET
Batterijenkunnengevaarvoor elektrische schokof brandwondenveroorzaken als
gevolg van unhoge kortsluitstroom.Volg dedesbetreffendeaanwijzingenop.
Debatterijenmoetenopdejuistewijzewordenopgeruimd.Raadpleeghiervooruw
plaatselijke voorschriften.
Deze UPS bevat zijneigenenergiebron (batterijen).Deuitgangsaansluitingen
kunnenonderspanningstaanwanneerdeUPSnietopeenwisselstroomvoedingis
aangesloten.
Nooitbatterijeninhet vuurgooien.Debatterijenkunnenontploffen.
Nooitbatterijenopenenofbeschadigen.Vrijkomendelektrolytisschadelijkvoor de
huiden ogen,en kan uiterstgiftig zijn.
Uitsluitendhet elektriciteitssnoergebruiken datbijdeze UPS wordtgeleverd.Het
snoerisvolgensdespecificatiesvandeIEC(InternationalElectricalCode)bedraad.
Controleer ofwandcontactdoos waarop de UPS wordtaangesloten,volgensdeze
zelfde specificatiesisbedraad teneinde schade aan uwapparatuur tevoorkomen.
Controleer ofhet wandcontactdoosvoldoende isafgezeherd.Controleerof de
voedingsstekker goedinhet stopcontactisgestoken.Gebruikuitsluitendeen
enkelfasig geaardwandcontactdoosmet randaarde.
Teneinde dekansop brandof elektrischeschokte verminderen dientdeze UPS in
een gebouwmet temperatuur- en vochtigheidregelingte wordengeïnstalleerd,
waargeengeleidendeverontreinigingenaanwezigzijn.Deomgevingstemperatuur
mag 40 Cnietoverschrijden.Nietgebruikenindebuurtvanwaterofbijzeerhoge
vochtigheid (max.95%).
Safety Warnings
11
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Verwijderde ingangsnoernietof haalde stekker van deingangsnoer erniet uit
terwijldeUPSaanstaat.HierdoorzoudeUPSenuwaangeslotenapparatuurgeen
aardebeveiliging meer hebben.
Omaan deinternationalenormen enbedradingsvoorschriftente voldoenmagde
geheleapparatuur dieop deuitgang van dezeUPSisaangesloten,geen
aardlekstroom van meer dan 2,75 milliampère hebben.
Dehoofdvoedingcontactdoosmoet zich op minderdan 2metervande apparatuur
bevinden enmakkelijk bereikbaarzijn voor degebruiker.Deaan/uit-schakelaar op
de UPSbiedtgeen elektrische isolatie voor deinwendige onderdelen.Destekker
uitde voedingcontactdooshalenwanneerhet apparaatvoor lange tijdnietwordt
gebruikt.
Neemer notavandat de uitgangaansluitpunten opde UPS altijdonder stroom
staanwanneer debelastingschakelaar( )wordtingedrukt,ongeachtde
aanwezigheidvande voeding.
Voor Bypass systemen met vast-bedrade uitgangen,moetde
overstroombeveiliging voor wisselstroom uitgangcircuit(s)door derdenworden
geleverd.
Voor BypassModulesystemen met vast-bedrade uitgangen,moetende juiste
hoofdschakelaarsvoorwisselstroom uitgangcircuit(s)door derdenworden
geleverd.
Tärkeitä turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI
SÄILYTÄ NÄMÄ OHJEET
TÄMÄ OPAS SISÄLTÄÄ TÄRKEITÄ TURVAOHJEITA
VAARA
Tämä UPSsisältää HENGENVAARALLISIAJÄNNITTEITÄ.Kaikkikorjaukset ja huollot
on jätettäväVAIN VALTUUTETUNHUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä
MITÄÄNYTTÄJÄN HUOLLETTAVIAOSIA.
VARO
Akustosaattaaaiheuttaa sähköiskun taisyttyä tuleen,josakusto kytketään
oikosulkuun.Noudata asianmukaisiaohjeita.
Akustotäytyy hävittääsäädösten mukaisellatavalla.Noudata paikallisia
äräyksiä.
Safety Warnings
12
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Tämä UPSsisältää omanenergialähteen(akuston).Ulostuloliittimissä voi olla
jännite,kunUPSeioleliitettynä verkkojännitteeseen.
Älä koskaan heitä akkujatuleen.Ne voivaträjähtää.
Älä avaa tairiko akkuja.Paljastunutelektrolyyttion vahingollinen iholle ja silmille
ja voi olla erittäin myrkyllistä.
Käytä vain tämän UPS-laitteen mukana toimitettua virtakaapelia,joka onkytketty
kansallisten määysten mukaisesti. Varmista, että UPS-laitteen kanssa ytetty
pistorasia onjohdotettunäidensamojen määritysten mukaisesti,jottalaitteet
eivät vahingoittuisi.Varmista myös,että asennuksen yhteydessävaihtovirran
pistorasiavarustetaanylivirtasuojauksella.Työnnäkosketinkokonaanpistorasiaan.
ytä pelkästään yksivaihteista, kolmijohtoista, maadoitettua verkkopistorasiaa.
VähentääksesitulipalonjasähköiskunvaaraaasennatämäUPSsisätiloihin,joissa
lämpötila jakosteuson säädettävissä jajoissaeiole virtaajohtavia
epäpuhtauksia.Ympäristönlämpötilaeisaaylittää40 C.Älä käytähellä vetja
vältä kosteita tiloja (95 % maksimi).
Älä poistataiirrota sisääntulojohtoa,kunUPSon kytkettynä.Tämä poistaa
turvamaadoituksen UPS-laitteesta jasiihenliitetystä laitteistosta.
Kansainväliset normit jajohdotusmääräykset vaativat, et kaikkien tämän
UPS-laitteen ulostulokytkentöjenyhteinen maavuotovirta eiylitä
2,75 milliampeeria (mA).
Päävirtapistokkeen täytyyolla2 m:n säteellä laitteistosta jakäyttäjän saatavilla.
UPS-laitteen virtakytkin eierota sisäosia verkkojännitteestä. Irrota
sisääntulopistoke,joskytket laitteen poiskäytöstäpitkähköksiajaksi.
Otamyöshuomioon,että UPS-laitteen ulostuloliittimissä onjänniteainakun
painetaanUPSinlähtöteho PÄÄL-painiketta( ),riippumatta siitä,onko
tulokaapelikytkettynä taiei.
Tämänlaitteen mukana eitoimitetalähdönylivirtasuojausta kiinteänasennuksen
ohitusjärjestelmissä.
Tämänlaitteen mukana eitoimitetalähdönjohdonsuojakatkaisijoita jakeluja
vartenkiinteän asennuksen ohitusjärjestelmissä.
Safety Warnings
13
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES
CONSERVER CES INSTRUCTIONS
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ
IMPORTANTES
DANGER!
Cetonduleurcontient desTENSIONSMORTELLES.Toute opérationd’entretien etde
réparationdoit êtreEXCLUSIVEMENTCONFIÉE AUN PERSONNELQUALIFIÉ AGRÉÉ.
AUCUNE PIÈCE RÉPARABLEPARL’UTILISATEURne setrouve dansl’onduleur.
ATTENTION!
Lesbatteriespeuventprésenterunrisquededéchargeélectriqueoudebrûlurepar
descourts-circuitsde haute intensité.Prendre lesprécautionsnécessaires.
Unemise au rebutréglementaire desbatteriesest obligatoire.Consulter les
règlementsen vigueurdansvotrelocalité.
Cetonduleurrenfermesapropre source d’énergie(batteries).Lesprisesde sortie
peuventêtre soustension même lorsque l’onduleur n’estpasbranché sur le
secteur.
Ne jamais jeter lesbatteriesau feu.L’exposition auxflammesrisque delesfaire
exploser.
Ne jamais ouvrirou mutiler desbatteries.L’électrolytedégagé est nuisibleà la
peau etaux yeuxet peuts’avérer extrêmementtoxique.
Utiliser uniquement le cordon d’alimentationfourniavecl’onduleur.Ce cordon est
câblé conformémentauxspécificationsdu Codeélectrique international(CEI).
S’assurerque leblage de laprise secteur devantêtre utiliséeavecl’onduleurest
luiaussiconforme àcesspécificationspour éviter d’endommagerlematériel.
S’assurer que la prisesecteur est protégéecontrelessurchargesau momentde
l’installation. S’assurer que la prise d’entrée est insérée à fond dans la prise
secteur.Utiliser uniquementuneprisesecteuràtroisfils,monophaséeetmise àla
terre.
Pour réduire lesrisquesd’incendie etde décharge électrique,installer l’onduleur
uniquement àl’inrieur, dansun lieudépourvude matériauxconducteurs,où la
températureetl’humidiambiantessontcontrôlées.Latempératureambiantene
doitpasdépasser40
°
C. Ne pasutiliser àproximid’eauou dansuneatmosphère
excessivement humide(95% maximum).
Safety Warnings
14
Powerware
®
PrestigeSeries Installationand Operator’sManual forIBMApplications(3000 VA)Uncontrolled Copy
Ne pasretirerlecordon dalimentationlorsque l’onduleur est soustension sous
peinede supprimer la mise à la terre del’onduleuret dumatérielconnecté.
Afin d’être conforme auxnormeset règlementsinternationauxde câblage,le
courantde fuiteà la terrede la totalitédu matérielbranché sur la sortiede
l’onduleurne doit pasdépasser 2,75 mA.
Laprisesecteur doit se trouver àmoinsde 2m du matérielet êtreaccessible à
l’utilisateur. L’interrupteur de ON/OFF (marche/arrêt) de l’onduleur n’assure pas
l’isolation électrique des pièces internes. Débrancher le cordon d’alimentation de
laprisesecteur encasde déconnexion del’appareilpendant unepériode
prolongée.
Noter quelesprisesde sortiede l’onduleursontsoustension lorsqueOutput
On
buttonestenfoncé,mêmesile cordon d’alimentationestdébranché delaprise
secteur.
Pour lessystèmes de bypass dos de sortie à bornier, la protection contre les
surintensitésdescircuitsde sortie decourant alternatifestà seprocurerauprès
d’unautre fournisseur.
Pourlessystèmes de bypass dotés desortie àbornier,lesinterrupteursadaptésau
circuit decourantalternatifsontà seprocurerauprès d’un autrefournisseur.
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGENANLEITUNGEN
AUFBEWAHREN.DIESES HANDBUCH ENTHÄLT WICHTIGE
SICHERHEITSANWEISUNGEN.
WARNUNG
Die USV führt lebensgefährlicheSpannungen.AlleReparatur-und Wartungsarbeiten
solltennur von Kundendienstfachleutendurchgeführtwerden.Die USVenthältkeine
vomBenutzerzu wartenden Komponente
VORSICHT!
Batterien können aufgrund deshohen KurzschlußstromsElektroschocksoder
Verbrennungen verursachen.Die entsprechendenVorsichtsmaßnahmensind
unbedingtzu beachten.
Die Batterien müssen ordnungsgemäß entsorgtwerden.Hierbei sind die örtlichen
Bestimmungen zubeachten.en.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92

3com Powerware Prestige Series User manual

Category
Uninterruptible power supplies (UPSs)
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI