NCR 4072 Operating instructions

Category
Uninterruptible power supplies (UPSs)
Type
Operating instructions
NCR 4072
500–1400 VA
Uninterruptible Power Systems (UPS)
Site Preparation,
Installation, and Operation Manual
Class B EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device,
pursuant to part 15 of the F CC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in
a particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
Consult the dealer or an experienced radio/TV technician for help.
ICES-003
This Class B Interference Causing Equipment meets all requirements of the Canadian Interference
Causing Equipment Regulations ICES-003.
Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel
brouilleur du Canada.
ECopyright 2001–2005 NCR Corporation, Dayton, Ohio. All rights reserved. No part of this document may
be reproduced in any way without the express written approval of NCR Corporation.
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU
directives:
Harmonized Standards: IEC 62040-1-1 and IEC 62040-2; IEC 60950 Third Edition
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage
limits
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of
the EC Declaration of Conformity, contact:
Loren Schide
NCR
1611 South Main Street
Dayton, OH 45479
Phone: 937-445-5305
Special Symbols
The following are examples of symbols used on the UPS to alert you to important
information:
Risk of Electric Shock
Do Not Open Cover
CAUTION
CAUTION To reduce the risk of electric shock,
Do not remove cover (or back)
No user-serviceable parts inside
Refer servicing to the factory
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the
associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual
for additional information, such as important operating and maintenance instructions.
SAFETY EARTHING TERMINAL - Indicates the primary safety ground.
LOAD ON/OFF - Press the button with this symbol to energize the output receptacles
(
µ indicator illuminates) or to de -energize t he output receptacles (µ indicator is
off).
RJ-45 RECEPTACLE - For 230V units only: this receptacle provides network interface
connections. Do not plug telephone or telecommunications equipment into this
receptacle.
This symbol indicates that you should not discard the UPS or the UPS batteries in the
trash. The UPS may contain sealed, lead-acid batteries. Batteries must be recycled.
i
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Table of Contents
1 NCR 4072 One of the Best! 1.................................
2 Safety Warnings 3............................................
3 Installation 17.................................................
Inspecting the Equipment 17.................................................
UPS Internal Battery Connection 18...........................................
Installing the UPS 20........................................................
UPS Rear Panels 22.........................................................
4Operation 27..................................................
Turning the UPS On 27......................................................
Starting the UPS on Battery 27.............................................
Turning the UPS Off 27.....................................................
Standby Mode 28..........................................................
UPS Front Panel 28.........................................................
Initiating the Self-Test 28....................................................
5 Additional UPS Features 29.....................................
Voltage Configuration 29....................................................
Communication Options 30..................................................
USB Port 30.............................................................
DB-9 Communication Port 31..............................................
Network Transient Protector 32..............................................
6 UPS Maintenance 33...........................................
UPS and Battery Care 33....................................................
Storing the UPS and Batteries 33...........................................
Replacing Batteries 34......................................................
Testing New Batteries 37....................................................
Recycling the Used Battery 38................................................
Table of Contents
ii
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
7 Specifications 39..............................................
8 Troubleshooting 43............................................
Audible Alarms and UPS Conditions 43........................................
Silencing an Audible Alarm 44.............................................
Site Wiring Fault (120V Models Only) 44.....................................
Service and Support 47.....................................................
1
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Chapter 1 NCR 4072 One of the Best!
The NCR 4072 uninterruptible power system (UPS) pr otects your
sensitive electronic equipment from basic power problems such as power
failures, power sags, power surges, brownouts, and line noise.
Power outages can occur when you least expect it and power quality can
be erratic. These power problems have the potential to corrupt critical
data, destroy unsaved work sessions, and damage hardware causing
hours of lost productivity and expensive repairs.
With the NCR 4072 UPS , you can safely eliminate the effects of power
disturbances and guard the integrity of your equipment. The NCR 4072
UPS’s flexibility to handle an array of network devices makes it the
perfect choice to protect your LANs, servers, workstations, and other
electrical equipment.
Figure 1. The NCR 4072 UPS
NCR 4072 One of the Best!
2
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Providing outstanding performance and reliability, the NCR 4072 UPS’s
unique benefits include the following:
Battery Save technology doubles battery service life, optimizes
recharge time, and provides a warning before the end of useful
battery life.
Buck and Boost voltage regulation ensures consistent voltage to your
load by correcting voltage fluctuations.
Hot-swappable batteries simplify maintenance by allowing you to
replace batteries safely without powering down the critical load.
Start-on-battery capability allows you to power up the UPS even if
utility power is not available.
Two standard communication options with a USB port and DB-9 serial
port.
Network Transient Protector guards your network communications
equipment from surges. Low voltage models can also protect
modems, fax machines, or other telecommunications equipment.
The NCR 4072 UPS is backed by worldwide agency approvals.
3
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Chapter 2 Safety Warnings
Read the following precautions before you install the UPS.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during
installation and maintenance of the UPS and batteries. Please read all
instructions before operating the equipment and save this manual for future
reference.
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be
performed by AUTHORIZED SERVICE PERSONNEL ONLY.ThereareNO USER
SERVICEABLE PARTS inside the UPS.
WARNING
This UPS contains its own energy source (batteries). The output receptacles
may carry live voltage even when the UPS is not connected to an AC supply.
For 220–240V models, the o utput receptacles may remain electrically live. If
the input power source in your application is wired line-to-neutral (as in
most European applications), the voltage to the output receptacles is 0V.
With line-to-line input wiring, the voltage to the output receptacles is
110–120V (measured from line-to-ground or line-to-neutral, depending on
the UPS wiring).
Do not remove or unplug the input cord when the UPS is turned on. This
removes the safety ground from the UPS and the equipment connected to
the UPS.
To reduce the risk of fire or electric shock, install this UPS in a temperature
and humidity controlled, indoor environment, free of conductive
contaminants. Ambient temperature must not exceed 40°C (104°F). Do not
operate near water or excessive humidity (95% max).
To comply with international standards and wiring regulations, the total
equipment connected to the output of this UPS must not have an earth
leakage current greater than 1.5 milliamperes.
Safety Warnings
4
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
CAUTION
The wall outlet must be within 2 meters of the equipment and accessible to
the operator.
Batteries can present a risk of electrical shock or burn from high
short-circuit current. The following precautions should be observed:
1) Remove watches, rings, or other metal objects; 2) Use tools with insulated
handles; 3) Do not lay tools or metal parts on top of batteries; 4) Disconnect
charging source prior to connecting or disconnecting battery terminals.
Proper disposal of batteries is required. Refer to your local codes for
disposal requirements.
Never dispose of batteries in a fire. Batteries may explode when exposed to
flame.
Never open or mutilate batteries. Released electrolyte is harmful to the skin
and eyes, and may be extremely toxic.
Replace batteries with the same number and type of batteries as originally
installed in the UPS.
17
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Chapter 3 Installation
This section explains:
Equipment inspection
UPS installation
UPS rear panels
Inspecting the Equipment
If any equipment has b een damaged during shipment, keep the shipping
cartons and packing materials for the carrier or p lace of purchase and
file a claim for shipping damage. If you discover damage after
acceptance, file a claim for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with
the carrier within 15 days of receipt of the equipment; 2) Send a copy of
the damage claim within 15 days to Customer Service.
NOTE Check the battery recharge date on the shipping carton label. If
the date has expired and the batteries were never recharged, do not use
the UPS. Contact Customer Service.
Installation
18
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
UPS Internal Battery Connection
Use the following procedure to ensure proper b attery operation before
installing the UPS:
1. Verify that the UPS is off and unplugged.
2. Remove the UPS front panel.
Figure 2. Removing the Front Panel
3. Slide up and remove the metal battery cover.
1400 VA500–1000 VA
Figure 3. Removing the Battery Cover
Installation
19
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
4. Remove the protective label from the internal battery
connector.
Figure 4. Removing the Protective Label
5. Connect the red wire to the () battery connector.
NOTE A small amount of arcing may occur when connecting the
batteries. This is normal and does not damage the unit or present any
safety concern.
Figure 5. Connecting the Red Wire
6. Reinstall the metal battery cover.
Figure 6. Reinstalling the Battery Cover
Installation
20
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
7. Reinstall the UPS front panel.
Figure 7. Reinstalling the Front Panel
8. If the UPS requires any type of transportation in the future,
disconnect the UPS internal battery connector using the above
steps in reverse order.
Installing the UPS
The following steps explain how to install the UPS. Figure 8 shows a
typical installation only. See “UPS Rear Panels” on page 22 for the rear
panel of each model.
1. If you are installing power management software, connect your
computer to the USB port or UPS communication port using the
supplied cable (see page 30).
NOTE If you need to change the factory-set defaults for the output voltage
or input voltage range, see “Voltage Configuration” on page 29 before
installing the UPS.
2. On 230V models, plug the detachable power cord into the input
connector on the UPS rear panel.
Installation
21
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Press the ON button
(on the front panel)
1
Connect communication
cable from computer to
UPS (optional)
Connect UPS to power
2
&
3
4
Connect eq uipment to UPS
5
This is a typical setup;
your setup may vary.
NOTE
Figure 8. Typical UPS Installation (120V Model Shown)
3. Plug the UPS power cord into a power outlet.
Verify that the circuit has an upstream overcurrent protection of
15A for 120V models or 10A for 230V models.
4. Plug the equipment to be protected into the UPS output
receptacles.
NOTE DO NOT protect laser printers with the UPS because of the
exceptionally high power requirements of the heating elements.
5. Press and hold the button until you hear the UPS beep
(approximately two seconds).
The
µ
indicator illuminates indicating that power is available
from the UPS output receptacles. The UPS conducts a self-test
and enters Normal mode.
If the alarm beeps or a UPS alarm indicator stays on, see Table 9
on page 44.
NOTE The batteries charge to 90% capacity in approximately 3 hours.
However, it is recommended that the batteries charge for 6 to 24 hours
after installation or long-term storage.
Installation
22
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
UPS Rear Panels
This section shows the rear panels of the NCR 4072 UPS models.
Communication Port
Four 5-15 Receptacles
6-ft Power Cord
with 5-15 Plug
DIP Switches
Network Transient
Protector
Site Wiring Fault
Indicator
USB Port
Input Overcurrent
Protector
Figure 9. 500 VA, 120V Rear Panel
Four 5-15 Receptacles
6-ft Power Cord
with 5-15 Plug
Network Transient
Protector
Fan
Communication Port
DIP Switches
Site Wiring Fault
Indicator
USB Port
Input Overcurrent
Protector
Figure 10. 750 VA, 120V Rear Panel
Installation
23
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Network Transient
Protector
Two 5-15 Receptacles
Four 5-15 Receptacles
6-ft Power Cord
with 5-15 Plug
Fan
Communication Port
DIP Switches
Site Wiring Fault
Indicator
USB Port
Input Overcurrent
Protector
Figure 11. 1000 VA, 120V Rear Panel
Six 5-15 Receptacles
6-ft Power Cord
with 5-15 Plug
Network Transient
Protector
Fan
Communication Port
DIP Switches
Site Wiring Fault
Indicator
USB Port
Input Overcurrent
Protector
Figure 12. 1400 VA, 120V Rear Panel
Installation
24
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Communication Port
Four 10A, IEC-320
Receptacles
DIP Switches
Network Transient
Protector
10A, IEC-320
Input Connector
USB Port
Figure 13. 500 VA, 230V Rear Panel
Four 10A, IEC-320
Receptacles
DIP Switches
Network Transient
Protector
10A, IEC-320
Input Connector
Fan
Communication Port
USB Port
Figure 14. 750 VA, 230V Rear Panel
Installation
25
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
Two 10A, IEC -320
Receptacles
Four 10A, IEC-320
Receptacles
10A, IEC-320
Input Connector
Fan
DIP Switches
Network Transient
Protector
Communication Port
USB Port
Figure 15. 1000 VA, 230V Rear Panel
Six 10A, IEC-320
Receptacles
Fan
10A, IEC-320
Input
Connector
DIP Switches
Network Transient
Protector
Communication Port
USB Port
Figure 16. 1400 VA, 230V Rear Panel
Installation
26
NCR 4072 UPS Site Preparation, Installation, and Operation Manual S 05147374 Rev C Uncontrolled Copy
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

NCR 4072 Operating instructions

Category
Uninterruptible power supplies (UPSs)
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI