ROOTECH Accura 2300S/2350 User guide

  • Hello! I am an AI chatbot trained to assist you with the ROOTECH Accura 2300S/2350 User guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
ACCURA 2300S/2350
Distribution Panel Digital Power Meter/Power Measuring Module
Actually makes possible enterprise energy management
User Guide[English]
Revision 1.21 2018/12/3
Distribution Panel Digital Power Meter
Accura 2300S Front
Accura 2300S Rear
Three-phase Power Measuring Module
Single-phase Power Measuring Module
Accura 2350-3P-250A-105
TM-3P-105
Accura 2350-1P-250A-105
TM-1P-105
Accura 2350-3P-125A-90
TM-3P-90
Accura 2350-1P-125A-60
TM-1P-60
Accura 2350-3P-100A-75
TM-3P-75L
Accura 2350-1P-100A-50
TM-1P-50L
Accura 2350-3P-60A-75
TM-3P-75
Accura 2350-1P-60A-50
TM-1P-50
Accura 2350-3P-CT5A-75
Accura 2350-1P-50A-35
Accura 2350-1P-30A-35
Accura 2350-1PSH-50A-35
Accura 2350-1PSH-30A-35
Split-core Three-phase
Power Measuring Module
Split-core Single-phase
Power Measuring Module
Split-core Single-phase Single-hole
Power Measuring Module
Accura 2350-3PSC-250A-105
Accura 2350-1PSC-250A-105
Accura 2350-1PSCSH-800A
Accura 2350-3PSC-125A-90
Accura 2350-1PSC-125A-60
Accura 2350-1PSCSH-630A
Accura 2350-3PSC-60A-75
Accura 2350-1PSC-60A-50
Accura 2350-1PSCSH-400A
Accura 2350-3PSC-CT5A-90
Special-purpose Module
Accura 2350-GAS
Accura 2350-GW
Accura 2350-TEMP
Accura 2350-DO
Accura 2350-IDC
Accura 2350-VDC
Accura 2350-DCM-50V-80A
Accura 2350-DCM-500V-80A
Accura 2300S/2350 User Guide
Notice
2013 Rootech Inc. All Rights Reserved
Page 5
Notice
Symbol
Caution
Indicates the presence of dangerous voltage which can cause severe injury or death to persons
if proper precautions are not followed.
Warning
Alerts the user to the presence of hazards which can cause somewhat injury to persons,
damage to property or damage to the device itself, if proper precautions are not followed.
Note
Indicates the user’s attention to installation, operating and maintenance instructions.
Indicates alternative voltage or current.
Indicates direct voltage or current.
Installation Considerations
Installation and operation of Accura 2300S/2350 should be performed only by qualified, competent
personnel that have appropriate training and experience with high voltage and current devices.
Caution
Failure to observe the following instructions may result in severe injury or death.
During normal operation of Accura 2300S/2350, hazardous voltages are present on its terminal strips of
voltages input and power.
Standard safety precautions are as followed while performing any installation or service work[removing PT
fuses, shorting CT secondaries, etc.].
Do not access to terminal strips of Accura 2300S/2350 after installation.
Warning
Observe the following instructions, or permanent damage to the meter may occur.
Notice
Accura 2300S/2350 User Guide
Page 6
2013 Rootech Inc. All Rights Reserved
Do not apply Accura 2300S/2350 to voltages and currents that exceed Input ratings of PT and CT
To use device in the other way than specified by manufacturer can cause severe damage.
Connect ground terminal to the earth ground to protect device from noise and surge.
Terminal screw torque is as followed.
- barrier-type voltage terminal: 1.35Nm[1.00 ft-lbf] max.
- barrier-type digital inputs/digital output terminal: 0.90Nm[0.66 ft.lbf] max.
About Manual
Rootech Inc. reserves the right to make changes in the device specifications shown in this User Guide without
notice. Rootech Inc. advises customers to obtain the latest specifications of device before giving orders to
confirm that the information being relied on by the customer is up to date.
In the absence of written agreement to the contrary, Rootech Inc. assumes no liability for Rootech Inc.
applications assistance, customer’s system design, or infringement of patents or copyrights of third parties by
or arising from the use of devices described herein.
The information contained in this document is believed to be accurate at the time of publication, however,
Rootech Inc. assumes no responsibility for any errors which may appear here and reserves the right to make
changes without notice.
Limitation of Liability
Where applicable law allows and does not prohibit or restrict such limitation, Rootech, Inc’s liability for
anything relating to this product shall be limited to the price paid for the product.
Accura 2300S/2350 User Guide
Warranty
2013 Rootech Inc. All Rights Reserved
Page 7
Warranty
For products and software that are sold or licensed by Rootech Inc. during the period from the date of receipt
by you until the present, Rootech warrants only to the original purchaser.
The purchased products shall be substantially free from material defects in material and workmanship by
Rootech for two years from the date receipt by you.
The software itself is provided as is without any warranty of any kind.
In order for the original purchaser to make a claim under the warranties described above, the original
purchaser must promptly contact Rootech headquarter. After receiving such notice, Rootech may either in
Rootechs sole discretion, examine the product at the original purchasers site or issue shipping instructions to
the original purchaser to return the relevant product to Rootech for examination at the original purchasers
expense, transportation charges prepaid.
If after examining the product Rootech reasonably confirms that such examined product does not meet the
warranties, then the original purchasers sole remedy and Rootechs sole obligation or liability shall be, at
Rootechs option, to repair, replace or refund the price paid for that product.
Limitation of Warranty
The Warranty does not apply to uninterrupted or error-free operation of the Product or cover normal wear and
tear of the product or costs caused by the removal, installation, or troubleshooting of the customer's electrical
systems.
The warranty claims for defects caused by any of the following factors are not covered.
Improper use(alteration, accident, misuse, abuse) or Failure to act in accordance with installation,
operation or maintenance instructions
Unauthorized modifications, changes or attempted repairs
Failure to comply with applicable safety standards & regulations
Damages when transporting or storing
Damages by force majeure, examples are(not necessarily limited): fire, flood, earthquakes, storm damage,
overvoltage & lightning
If the original identify markings(trade-mark, serial number, etc) have been defaced, altered, or removed
Rootech shall not be liable for any other claim than a claim solely for the breach of one of the above
warranties that is made in accordance with the above described procedures- made by the original purchaser,
Warranty Information
Accura 2300S/2350 User Guide
Page 8
2013 Rootech Inc. All Rights Reserved
its employees, agents, or contractors for any loss, damage, or expense incurred due to, caused by, or related
to any purchased product.
Any technical assistance provided by Rootech's personnel or representatives in system design shall be deemed
to be a proposal and not a recommendation. The responsibility for determining the feasibility of such
proposals lies with the original purchaser and should be tested by the original purchaser.
It is the original purchaser’s responsibility to determine the suitability of any product and associated
documentation for its purposes. The original purchaser acknowledges that 100% "up" time is not realizable
because of possible hardware or software defects. The original purchaser recognizes that such defects and
failures may cause inaccuracies or malfunctions.
Only the terms expressed in these limited Warranties shall apply and no distributor, corporation or other entity,
individual or employee of Rootech or any other entity is authorized to amend, modify or extend the Warranties
in any way.
Standard Compliance
Process Control Equipment
E324900
MSIP-REM-RTE-ACCURA 2300S
QMS-1347
KAB-QC-09
Accura 2300S/2350 User Guide
Revision History
2013 Rootech Inc. All Rights Reserved
Page 9
Revision History
The following versions of Accura 2300S/2350 User Guide have been released.
Revision
Date
Description
Revision 1.00
2014. 02. 14
Initial draft
Revision 1.10
2014. 12. 23
Configuration and measurement description added.
Special-purpose module description
[Accura 2350-GAS/GW/DO/VDC/IDC/TEMP] added.
Revision 1.11
2015. 05. 21
Standard compliance updated
Revision 1.12
2015. 11. 19
Speical-purpose module arrangement modified.
Revision 1.20
2016. 12. 22
Typing error corrected, bookmark added, power event added
Revision 1.21
2018. 12. 3
Certification image update
Setup and measurement contents update
Zero voltage/current are changed to residual voltage/current.
Description of error according to penetration position for split core module
Update of Accura 2350 Module Management Screen
Description of the connection number of Accura 2350 special module
Clear description of reading error
Contents
Accura 2300S/2350 User Guide
Page 10
2013 Rootech Inc. All Rights Reserved
Contents
Chapter 1 Introduction .............................................................................................................................. 17
Overview ........................................................................................................................................................ 17
Application ...................................................................................................................................................... 20
Device Lineup .................................................................................................................................................. 21
Distribution Panel Digital Meter/Power Measuring Module .......................................................................... 21
Special-Purpose Module ........................................................................................................................... 22
Installation Example ................................................................................................................................. 23
Features .................................................................................................................................................. 25
Chapter 2 Installation ............................................................................................................................... 30
Environmental Conditions ................................................................................................................................ 30
Before you begin ............................................................................................................................................. 31
Meter Overview ....................................................................................................................................... 31
Components ............................................................................................................................................ 33
Dimension ............................................................................................................................................... 35
Installation Diagram ................................................................................................................................ 42
Step 1: Mounting ............................................................................................................................................. 44
Accura 2300S Mounting ........................................................................................................................... 44
Accura 2350-3P Three-phase Power Measuring Module Mounting ............................................................. 45
Accura 2350-1P Single-phase Power Measuring Module Mounting ............................................................ 52
Accura 2350-3PSC Split-core Three-phase Power Measuring Module Mounting .......................................... 59
Accura 2350-1PSC Split-core Single-phase Power Measuring Module Mounting ......................................... 64
Accura 2350-1PSCSH Split-core Single-phase Single-hole Power Measuring Module Mounting ................... 69
Step 2: Accura 2300S Wiring ........................................................................................................................... 73
Accura 2300S Voltage Connection ............................................................................................................ 73
Accura 2300S Digital Input/Output Wiring ................................................................................................ 78
Step 3: Accura 2350 Current Through-hole Wiring ........................................................................................... 81
Accura 2350-3P[1P, 1PSH] Power Measuring Module Through-hole Wiring ................................................. 81
Accura 2350 Single-phase Single-hole Power Measuring Module Through-hole Wiring ............................... 86
Step 4: Accura 2300S/2350 Combination of Communication ........................................................................... 89
Step 5: Accura 2300S External Communication ................................................................................................ 91
Ethernet Communication .......................................................................................................................... 91
RS-485 Communication ........................................................................................................................... 93
Step 6: Accura 2300S Power Supply and Ground .............................................................................................. 94
Power Supply ........................................................................................................................................... 94
Ground Terminal ..................................................................................................................................... 94
Chapter 3 Accura 2350 Operation/Setup ................................................................................................... 95
Operation Mode ...................................................................................................................................... 95
Button Operation ..................................................................................................................................... 95
Accura 2350-3P[3PSC] Three-phase Power Measuring Module .......................................................................... 96
Accura 2300S/2350 User Guide
Contents
2013 Rootech Inc. All Rights Reserved
Page 11
Application Model .................................................................................................................................... 96
Display Mode .......................................................................................................................................... 96
Setup Mode ............................................................................................................................................. 98
Accura 2350-1P[1PSC] Single-phase Power Measuring Module ....................................................................... 106
Application Model .................................................................................................................................. 106
Display Mode ........................................................................................................................................ 106
Setup Mode ........................................................................................................................................... 107
Accura 2350-1PSCSH Split-core Single-phase Single-hole Power Measuring Module ........................................ 116
Application Model .................................................................................................................................. 116
Display Mode ........................................................................................................................................ 116
Setup Mode ........................................................................................................................................... 117
Chapter 4 Accura 2300S Operation/Setup ............................................................................................... 127
Device Configuration ..................................................................................................................................... 127
Operation Mode .................................................................................................................................... 127
LED Display ........................................................................................................................................... 127
Button Operation ................................................................................................................................... 127
Display Mode ................................................................................................................................................ 129
Front Display ......................................................................................................................................... 129
Accura 2350 Module ID Selection ........................................................................................................... 131
Display Full Screen ................................................................................................................................. 132
Voltage/Current/Power/Energy ............................................................................................................... 133
Voltage/Frequency ................................................................................................................................. 133
Current ................................................................................................................................................. 134
Power/Power Factor ................................................................................................................................ 134
Demand ................................................................................................................................................ 135
Active Energy ......................................................................................................................................... 135
Leakage Current .................................................................................................................................... 135
Ethernet Information .............................................................................................................................. 136
Temperature/Time .................................................................................................................................. 137
Setup Mode ................................................................................................................................................... 138
Setup Full Screen ................................................................................................................................... 139
Measurement Setup ............................................................................................................................... 140
Event Setup ............................................................................................................................................ 145
RS-485 Communication Setup ................................................................................................................ 155
Ethernet Communication Setup ............................................................................................................... 157
Reset ..................................................................................................................................................... 160
Display Setup ......................................................................................................................................... 161
Accura 2350 Module ID Setup ................................................................................................................ 164
Accura 2350-1P Group Device Setup ...................................................................................................... 168
Information ........................................................................................................................................... 171
Digital Input/Output Setup...................................................................................................................... 172
Event Log Mode ............................................................................................................................................. 177
Start Event and End Event ....................................................................................................................... 177
Contents
Accura 2300S/2350 User Guide
Page 12
2013 Rootech Inc. All Rights Reserved
Start Event Alarm Generation ................................................................................................................. 177
Start Event Alarm Clearing ..................................................................................................................... 177
Button Function ...................................................................................................................................... 178
Event Log Number ................................................................................................................................. 179
Event Time-stamp .................................................................................................................................. 179
Dip Event Log ........................................................................................................................................ 180
Swell Event Log ...................................................................................................................................... 180
Fuse Fail Event Log ................................................................................................................................. 181
Temperature Evnt Log ............................................................................................................................. 181
Current Event Log .................................................................................................................................. 182
Leakage Current Event Log ..................................................................................................................... 182
Demand Current Event Log .................................................................................................................... 183
No Event Log ......................................................................................................................................... 183
Required Setup Step ....................................................................................................................................... 184
Step 1: Accura 2300S Connection, PT Rating .......................................................................................... 184
Step 2: Accura 2350 Communication ID Auto-Assignment and Update .................................................... 185
Step 3: Accura 2300S Ethernet Setup ...................................................................................................... 188
Chapter 5 Measurement Description ........................................................................................................ 189
General Measurement ................................................................................................................................... 189
Measurement Event ....................................................................................................................................... 191
Measurement for Voltage Connection ............................................................................................................. 192
3-Phase 4-Wire ...................................................................................................................................... 192
3-Phase 3-Wire ...................................................................................................................................... 193
1-Phase 3-Wire ...................................................................................................................................... 195
1-Phase 2-Wire ...................................................................................................................................... 196
Dip[Sag]/Swell Measurement ......................................................................................................................... 197
Leakage Current Measurement ...................................................................................................................... 198
Residual Voltage Measurement ....................................................................................................................... 198
Residual Current Measurement ...................................................................................................................... 198
Phase Power Measurement ............................................................................................................................. 199
Three-phase Total Power Measurement ........................................................................................................... 200
Power Factor(PF) Measurement ....................................................................................................................... 201
PF Phase Angle Status Measurement ............................................................................................................... 202
Demand Measurement .................................................................................................................................. 203
Unbalance(NEMA MG1) ................................................................................................................................ 204
Sequence Unbalance ..................................................................................................................................... 205
Aggregation .................................................................................................................................................. 206
APPENDIX A Specification ........................................................................................................................ 208
APPENDIX B Standard Compliance .......................................................................................................... 213
APPENDIX C Accuracy/Reliability ............................................................................................................. 214
Accuracy................................................................................................................................................ 214
Accura 2300S/2350 User Guide
Contents
2013 Rootech Inc. All Rights Reserved
Page 13
Reliability ............................................................................................................................................... 215
APPENDIX D Ordering Information .......................................................................................................... 216
Contents
Accura 2300S/2350 User Guide
Page 14
2013 Rootech Inc. All Rights Reserved
Figures
Fig 1.1 Accura 2350-3P[1P] Through-hole Structure .................................................................................. 18
Fig 1.2 Accura 2350-3P[1P] Compatibility with MCCB/ELB in Dimension .................................................... 19
Fig 1.3 Accura 2350-3PSC[1PSC] Split-core three[single]-phase Power Measuring Module Installation ......... 19
Fig 1.4 Power Measuring Module Installation Example ............................................................................... 23
Fig 1.5 Split-core Power Measuring Module Installation Example ................................................................ 24
Fig 2.1 Accura 2300S Front ...................................................................................................................... 31
Fig 2.2 Accura 2300S Side ....................................................................................................................... 31
Fig 2.3 Accura 2300S Rear ....................................................................................................................... 31
Fig 2.4 Accura 2350-3P[1P] Power Measuring Module ............................................................................... 32
Fig 2.5 Accura 2350-3PSC[1PSC, 1PSCSH] Split-core Power Measuring Module ......................................... 32
Fig 2.6 Accura 2300S Component ............................................................................................................ 33
Fig 2.7 Accura 2350-3P Three-phase Power Measuring Module Component .............................................. 33
Fig 2.8 Accura 2350-1P Single-phase Power Measuring Module Component ............................................. 33
Fig 2.9 Accura 2350-3PSC Split-core Three-phase Power Measuring Module Component ........................... 34
Fig 2.10 Accura 2350-1PSC Split-core Single-phase Power Measuring Module Component ........................ 34
Fig 2.11 Accura 2350-1PSCSH Split-core Single-phase Single-hole Power Measuring Module Component .. 34
Fig 2.12 TM-3P Three-phase Terminal Component .................................................................................... 34
Fig 2.13 TM-1P Single-phase Terminal Component ................................................................................... 34
Fig 2.14 Accura 2300S Front Dimension ................................................................................................... 35
Fig 2.15 Accura 2300S Side Dimension .................................................................................................... 35
Fig 2.16 Accura 2300S Rear Dimension .................................................................................................... 35
Fig 2.17 Accura 2350-3P Three-phase Power Measuring Module Dimension .............................................. 36
Fig 2.18 TM-3P Three-phase Terminal Dimension ...................................................................................... 36
Fig 2.19 Accura 2350-1P Single-phase Power Measuring Module Dimension ............................................. 37
Fig 2.20 TM-1P Single-phase Terminal Dimension ..................................................................................... 37
Fig 2.21 Accura 2350-1PSH PSH Single-phase Single-hole Power Measuring Module Dimension ................ 38
Fig 2.22 Accura 2350-3PSC Split-core Three-phase Power Measuring Module Dimension ........................... 38
Fig 2.23 Accura 2350-1PSC Split-core Single-phase Power Measuring Module Dimension .......................... 39
Fig 2.24 Accura 2350-1PSCSH Split-core Single-phase Single-hole Power Measuring Module Dimension .... 40
Fig 2.25 Accura 2300S/2350-3P[1P] Power Measuring Module Installation ................................................ 42
Fig 2.26 Accura 2300S/2350-3PSC[1PSC, 1PSCSH] Split-core Power Measuring Module Installation ........... 43
Fig 2.27 Accura 2300S Mounting ............................................................................................................. 44
Fig 2.28 Accura 2350-3P Power Measuring Module Mounting ................................................................... 45
Fig 2.29 Accura 2350-3P Three-Phase Terminal Panel Perforation .............................................................. 46
Fig 2.30 Accura 2350-3P Mounting Plate / Terminal Panel Perforation ........................................................ 50
Fig 2.31 Accura 2350-1P Power Measuring Module Mounting ................................................................... 52
Fig 2.32 Accura 2350-1P Single-Phase Terminal Panel Perforation ............................................................. 53
Fig 2.33 Accura 2350-1P Mounting Plate / Terminal Panel Perforation ........................................................ 57
Fig 2.34 Accura 2350-3PSC Split-core Power Measuring Module New Installation ...................................... 59
Fig 2.35 Accura 2350-3PSC Split-core Three-phase Power Measuring Module Panel Perforation .................. 60
Fig 2.36 Accura 2350-3PSC Split-core Mounting Plate Panel Perforation ..................................................... 62
Fig 2.37 Accura 2350-3PSC Split-core Power Measuring Module Remodeling Installation ........................... 63
Accura 2300S/2350 User Guide
Contents
2013 Rootech Inc. All Rights Reserved
Page 15
Fig 2.38 Accura 2350-1PSC Split-core Power Measuring Module New Installation ...................................... 64
Fig 2.39 Accura 2350-1PSC Split-core Single-phase Power Measuring Module Panel Perforation ................. 65
Fig 2.40 Accura 2350-1PSC Split-core Mounting Plate Panel Perforation ..................................................... 67
Fig 2.41 Accura 2350-1PSC Split-core Power Measuring Module Remodeling Installation ........................... 68
Fig 2.42 Accura 2350-1PSCSH Split-core Power Measuring Module New Installation .................................. 69
Fig 2.43 Accura 2350-1PSCSH Split-core Power Measuring Module Panel Perforation ................................. 70
Fig 2.44 Accura 2350-1PSCSH Split-core Mounting Plate Panel Perforation ................................................ 71
Fig 2.45 Accura 2350-1PSCSH Split-core Power Measuring Module Remodeling Installation ....................... 72
Fig 2.46 Accura 2300S Voltage Connection .............................................................................................. 73
Fig 2.47 3-phase 4-wire, Direct Connection .............................................................................................. 74
Fig 2.48 3-phase 4-wire, 3PT Connection ................................................................................................. 74
Fig 2.49 3-phase 3-wire, Direct Connection .............................................................................................. 75
Fig 2.50 Three-phase 3-wire, 2PT Connection ........................................................................................... 75
Fig 2.51 Single-phase 3-wire, Direct Connection ....................................................................................... 76
Fig 2.52 Single-phase 3-wire, 2PT Connection .......................................................................................... 76
Fig 2.53 Single-phase 2-wire, Direct Connection ....................................................................................... 77
Fig 2.54 Single-phase 2-wire, 1PT Connection .......................................................................................... 77
Fig 2.55 Accura 2300S Digital Input/Output Channel................................................................................ 78
Fig 2.56 Digital Input ............................................................................................................................... 78
Fig 2.57 DC Relay application .................................................................................................................. 80
Fig 2.58 AC Relay application .................................................................................................................. 80
Fig 2.59 Three-phase 4-wire/3-wire, Direct Through-hole Wiring ............................................................... 83
Fig 2.60 Three-phase 4-wire/3-wire, 3CT Through-hole Wiring ................................................................. 83
Fig 2.61 Three-phase 3-wire, 2CT Through-hole Wiring ............................................................................ 84
Fig 2.62 Single-phase LN[Line-to-neutral] Through-hole Wiring ................................................................. 85
Fig 2.63 Single-phase LL[Line-to-line] Through-hole Wiring ....................................................................... 85
Fig 2.64 Three-Module Group Device for 3P4W/3P3W connection ............................................................ 87
Fig 2.65 Two-Module Group Device for 3P3W connection ......................................................................... 87
Fig 2.66 Single-phase LN[Line-to-neutral] Single-hole Module Through-hole Wiring ................................... 88
Fig 2.67 Single-phase LL[Line-to-line] Single-hole Module Through-hole Wiring ......................................... 88
Fig 2.68 Accura 2300S/2350 Combination Example of Communication .................................................... 89
Fig 2.69 Accura 2300S Ethernet communication port ................................................................................ 91
Fig 2.70 Accura 2300S Ethernet Connection ............................................................................................. 92
Fig 2.71 Accura 2300S RS-485 Communication ....................................................................................... 93
Fig 2.72 Accura 2300S RS-485 Communication connection ...................................................................... 93
Fig 2.73 Accura 2300S Power Supply ........................................................................................................ 94
Fig 4.1 Accura 2300S Front configuration ............................................................................................... 127
Fig 4.2 Screen of Display Mode .............................................................................................................. 128
Fig 4.3 Screen of Setup Mode ................................................................................................................. 128
Fig 4.4 Screen of Event Log Mode ........................................................................................................... 128
Fig 4.5 Accura 2300S Front View ............................................................................................................ 129
Fig 4.6 Accura 2300S Temperature Sensor .............................................................................................. 130
Fig 4.7 Accura 2350 Module ID Selection at upper part of LCD Screen .................................................... 131
Fig 4.8 Voltage/Current/Power/Energy Display Screen ............................................................................. 133
Contents
Accura 2300S/2350 User Guide
Page 16
2013 Rootech Inc. All Rights Reserved
Fig 4.9 Voltage/Current/Power/Energy Display Screen for each phase ...................................................... 133
Fig 4.10 Line-to-line Voltage Display Screen ............................................................................................ 133
Fig 4.11 Current Display Screen ............................................................................................................. 134
Fig 4.12 Active Power Display Screen ...................................................................................................... 134
Fig 4.13 Demand Active Power Display Screen ........................................................................................ 135
Fig 4.14 Net Energy Display Screen ........................................................................................................ 135
Fig 4.15 Leakage Current Display Screen ................................................................................................ 136
Fig 4.16 Ethernet Connection Status Display Screen ................................................................................. 136
Fig 4.17 Temperature Display Screen ...................................................................................................... 137
Fig 4.18 3-phase 4-wire connection[3P4W]: PT Primary VAB , Secondary V12 .............................................. 140
Fig 4.19 3-phase 3-wire connection[3P3W]: PT Primary VAB , Secondary V12 .............................................. 141
Fig 4.20 1-phase 3-wire connection[1P3W]: PT Primary VL12 , Secondary V13 ............................................. 141
Fig 4.21 1-phase 2-wire connection[1P2W]: PT Primary VL12 , Secondary V1N ............................................. 141
Fig 4.22 Dip Event Setup[3-phase 4-wire] ............................................................................................... 146
Fig 4.23 Dip Event Setup[3-phase 3-wire] ............................................................................................... 146
Fig 4.24 Swell Event Setup[3-phase 4-wire] ............................................................................................. 148
Fig 4.25 Swell Event Setup[3-phase 3-wire] ............................................................................................. 148
Fig 4.26 Dip[Sag] Event Alarm Display .................................................................................................... 177
Fig 4.27 Swell Event Alarm Display ......................................................................................................... 177
Fig 4.28 Event Log Number Example ...................................................................................................... 179
Fig 5.1 3PT 3CT Wiring, 3P4W Connection ............................................................................................. 192
Fig 5.2 2PT 3CT Wiring, 3P3W Connection ............................................................................................. 193
Fig 5.3 2PT 2CT Wiring, 1P3W Connection ............................................................................................. 195
Fig 5.4 1PT 1CT Wiring, 1P2W Connection ............................................................................................. 196
Fig 5.5 Half-cycle Refreshed 1-cycle RMS Calculation .............................................................................. 197
Fig 5.6 Voltage Dip[Sag] Detection ......................................................................................................... 197
Fig 5.7 Vector Sum for Total Apparent Power ........................................................................................... 200
Fig 5.8 Arithmetic Sum for Total Apparent Power ..................................................................................... 201
Fig 5.9 Power Sign and PF Phase Angle Status ......................................................................................... 202
Fig 5.10 Demand Calculation ................................................................................................................ 203
Fig 5.11 Prediction Demand Calculation ................................................................................................. 203
Fig 5.12 Symmetrical Components ......................................................................................................... 205
Fig 5.13 Aggregation Process ................................................................................................................. 206
Accura 2300S/2350 User Guide
Chapter 1 Introduction
2013 Rootech Inc. All Rights Reserved
Page 17
Chapter 1 Introduction
Overview
Energy Management Paradigm Shift from Main Load to Branch Load
In the energy low-cost era, total energy management centered on switchgear panels such as main feeder
(from feeder to ABS) for stable power supply played an important role. However, there is an increasing
demand to manage the branch load electrical energy in manufacturing plants, IDC centers, and the
distribution boards of buildings when the energy costs rise sharply and the CO2 emission reduction policy is
implemented in 2015.
Limit of Application of the existing Digital Power Meter to Distribution Panel
To apply the digital power meter which is long used in the existing switchgear panel to distribution panel has
had the limit caused by narrow space, hazardous wiring of voltage and current, and high installation cost. This
fundamentally makes it difficult for energy management supervisor to access to the energy information of
branch loads in distribution panel.
Distribution Panel Digital Power Meter only for Branch Load Management
Distribution panel digital power meter comprises both Accura 2300S[digital power meter] which is mounted
on front of distribution panel, and Accura 2350[power measuring module] which is mounted in branch loads
inside the panel. Accura 2300S collects power data from several Accura 2350s on RS-485 communication
and displays measurements of only one Accura 2350 selected on its LCD screen. This provides energy
management supervisor with the power quality information of branch loads which was impossible to identify.
Voltage ±0.2% RD/Current ±0.2%[±0.5% 1] RD Error/IEC62053-22 Class 0.5S[Class 0.2S 2] Accuracy
Recently enterprise energy management system is essential for effective energy use and preventive
management to prepare CO2 emission management in plant, data center and building. The key factor to
determine reliability of the energy management is measurement accuracy. Accura 2300S/2350 supports ±0.2%
reading error for voltage, ±0.2%[±0.5% 1] reading error for current, and conforms to IEC62053-22 class
0.5S[Class 0.2S 2] for power and energy. This makes it possible to precisely analyze and diagnose energy
management and various problems with power facilities.
1. Split-core three[single]-phase power measuring modules support ±0.5% reading error for current. And these split-core
modules can increase the maximum ± 1% reading error depending on the penetration position of power cable.
2. Split-core single-phase single-hole power measuring module meets current accuracy ± 0.2% reading error and
power/energy accuracy IEC62053-22 Class 0.2S.
Dip[Sag]/Swell[IEC61000-4-30], Power Quality
Accura 2300S provides a variety of power quality information, including dip[sag], swell and harmonic
information[up to 31th], crest factor, K-factor, and unbalance ratio. This enables the energy manager to easily
identify power quality changes in various power distribution systems in the power plant, thus realistic power
Chapter 1 Introduction
Accura 2300S/2350 User Guide
Page 18
2013 Rootech Inc. All Rights Reserved
quality management is possible. Power quality information conforms to IEC61000-4-30.
Maximum/minimum/average statistical information in aggregation interval
Accura 2300S calculates the average value for every 0.5-second interval from the cycle-unit measurement.
The maximum/minimum/average values are calculated and provided for the intervals of 1-second, 5-second,
1-minute, 5-minute, 1-hour, and 6-hour from the average value of 0.5-second intervals. Here, a
measurement interval longer than 0.5-second is referred to as an aggregation interval.
Accura 2300S is capable of measuring the maximum, minimum, and average statistical information for each
aggregation interval and time information about the maximum/minimum occurrence time[time-stamp]. This
includes information of measurement parameters that fluctuate instantaneously with respect to the
aggregation interval, thus enabling accurate trend analysis of voltage, current, and power quality.
CE/UL Safety and Reliability
The structure-framework, circuit, and fire of Accura 2300S/2350 conforms to standard CE[EN61326-1,
EN61326-2-1, EN61010-1] and UL[UL61010-1].
Safety Guarantee of Installation by Through-hole Structure
Accura 2350-3P[1P] three[single]-phase power measuring module is structured with through-hole current
sensing without any electrical contact, which guarantees safety of electrical accident and simplifies installation.
TM-3P[1P] is three[single]-phase terminal for helping wiring.
Fig 1.1 Accura 2350-3P[1P] Through-hole Structure
Integrated Installation with Various rated MCCB/ELB
The installation of Accura 2350-3P[1P] three-[single]-phase power measuring module is compatible with
various rated MCCB/ELB in dimension.
Accura 2300S/2350 User Guide
Chapter 1 Introduction
2013 Rootech Inc. All Rights Reserved
Page 19
Fig 1.2 Accura 2350-3P[1P] Compatibility with MCCB/ELB in Dimension
Live-line Installation by Split-core Structure [applied only to split-core power measuring module]
Accura 2350-3PSC[1PSC, 1PSCSH] split-core three[single]-phase power measuring module makes it possible
to install without power interruption by split-core structure.
Fig 1.3 Accura 2350-3PSC[1PSC] Split-core three[single]-phase Power Measuring Module Installation
Chapter 1 Introduction
Accura 2300S/2350 User Guide
Page 20
2013 Rootech Inc. All Rights Reserved
Application
Enterprise Energy Management
Providing energy information of branch loads in distribution panel, Accura 2300S/2350 together with Accura
3300S/3500S/3550S/3700/7500 mounted in switchgear panels truly makes it possible to realize enterprise
energy management.
CO2 Emission Management by Reduction of High Energy Cost
Accura 2300S/2350 provides power quality information which enables management of energy use, power
facility operation and high efficiency device analysis. This can be an infrastructure essential for managing of
CO2 emission, presenting analytic criterion on energy use status to energy management supervisor.
Energy Efficiency Verification of High Efficiency Device
Accura 2300S/2350 provides high accuracy energy information to determine the efficiency of high efficiency
device such as LED, lighting, motor, and power facility.
/