ROOTECH Accura 2300/2350 User guide

Category
Measuring, testing & control
Type
User guide
Distribution Panel Digital Power Meter
Accura 2300 front
Accura 2300 rear
Accura 2300-RS485 rear
Three-phase Power Measuring Module/ Terminal Block
Single-phase Power Measuring Module/ Terminal Block
TM-3P-105
Accura 2350-1P-250A-105
TM-1P-105
TM-3P-90
Accura 2350-1P-125A-60
TM-1P-60
TM-3P-75L
Accura 2350-1P-100A-50
TM-1P-50L
TM-3P-75
Accura 2350-1P-60A-50
TM-1P-50
Accura 2350-1P-50A-35
Accura 2350-1P-30A-35
Accura 2350-1PSH-50A-35
Accura 2350-1PSH-30A-35
Split-core Three-phase
Power Measuring Module
Split-core Single-phase
Power Measuring Module
Split-core Single-phase Single-hole
Power Measuring Module
Accura 2350-3PSC-250A-105
Accura 2350-1PSC-250A-105
Accura 2350-1PSCSH-800A
Accura 2350-3PSC-125A-90
Accura 2350-1PSC-125A-60
Accura 2350-1PSCSH-630A
Accura 2350-3PSC-60A-75
Accura 2350-1PSC-60A-50
Accura 2350-1PSCSH-400A
Accura 2350-3PSC-CT5A-90
Special-purpose Modules
Accura 2350-GAS
Accura 2350-GW
Accura 2350-TEMP
Accura TSEN
Accura 2350-TEMPS
Accura 2350-DO
Accura 2350-IDC
Accura 2350-VDC
Accura 2350-DCM-50V-80A
Accura 2350-DCM-500V-80A
Accura 2300/2350 User Guide
Notice
2011 Rootech Inc. All Rights Reserved
Page 5
Notice
Symbols
Caution
Indicates the presence of dangerous voltage which can cause severe injury or death if
proper precautions are not followed.
Caution
Alerts users of the presence of hazards which can cause injury to persons, property
damage or damage to the device if proper precautions are not followed.
Note
Indicates major instructions for the installation, operation, and maintenance of the
product.
Indicates alternative voltage or current.
Indicates direct voltage or current.
Installation Considerations
The installation, operation, and maintenance of the product should be performed only by qualified,
competent personnel that have received appropriate training for high voltage and current devices.
Caution
If hazardous voltages are mishandled while installing and operating the product in the field, it can
cause serious injury or death.
This device must be installed and serviced only by qualified personnel who have in-depth knowledge
of installing, commissioning and operating the device and have had appropriate training. He or she
should have read and understood the various safety measures and warnings stated in the
instructions.
Before carrying out any work on the device, switch off the power supply to the device.
Always use an appropriate voltage detection device to confirm the absence of voltage.
Always power the device with the correct rated voltage.
Install the device in a suitable electrical cabinet by following recommended installation instructions.
Failure to take these precautions could cause serious injuries or death.
Notice
Accura 2300/2350 User Guide
Page 6
2011 Rootech Inc. All Rights Reserved
Caution
Observe the following instructions, or it may cause permanent damage to the product.
To ensure that the device operates correctly, make sure that:
The device is correctly installed.
The auxiliary power supply voltage indicated on the product is observed: AC 85 265 V, DC 100
300 V.
About the Manual
Rootech Inc. reserves the right to make changes in the product specifications shown in this User Guide
without prior notice. We recommend that customers should obtain the latest information on product
specifications and the manual before making orders.
In the absence of written agreements, Rootech, Inc. assumes no liability for applications assistance,
customers system design, or infringement of patents or copyrights induced by third parties arising
from the use of the products described herein.
We endeavor to provide accurate information in the document. However, we are not responsible for any
errors which may appear here and reserves the right to make changes without prior notice.
Limitation of Liability
Where applicable law allows and does not prohibit or restrict such limitation, Rootech, Inc’s liability for
this product shall be limited to the amount actually paid by customers for the product.
Accura 2300/2350 User Guide
Warranty
2011 Rootech Inc. All Rights Reserved
Page 7
Warranty
Rootech Inc. provides warrants for two years from the product receipt date only to the original
purchaser of the products and software that are sold or licensed by the company.
To obtain warranty service, the purchased products should be free from serious defects in material and
workmanship.
The software is provided in an up-to-date version, thus we do not offer any warranty for the software
product.
In order to make a product claim under the warranties described above, the original purchaser should
immediately contact Rootech headquarters. Upon receiving claims, Rootech will check out the product
either at where the purchaser is or at the company after receiving the product from the customer, who
is responsible for the cost of shipping the product. After inspecting the product, we will provide repair
or replacement services for the product.
Rootech will decide at its discretion whether to repair or replace it or give a refund for the product for
when the warranty period for the product expired or issues related to the product are not applicable
for warranty terms and conditions.
Limitation of Warranty
The Warranty does not apply to uninterrupted or error-free operation of the product or cover normal
wear and tear of the product or costs caused by the removal, installation, or troubleshooting of the
customer's electrical systems.
Defects caused by any of the following factors are not covered under the warranty.
Improper use (alteration, accident, misuse, abuse) or failure to act in accordance with installation,
operation or maintenance instructions
Unauthorized modifications, changes or repair attempts
Failure to comply with applicable safety standards & regulations
Damages coming from when transporting or storing the product
Damages caused by the force majeure event, including fire, flood, earthquakes, storm damage,
overvoltage & lightning
If the original identification marks (trade-mark, serial number, etc.) have been defaced, altered, or
removed.
Warranty
Accura 2300/2350 User Guide
Page 8
2011 Rootech Inc. All Rights Reserved
Rootech shall not be liable for any other claims except the claims made by customers, including the
original purchaser, his employees, agents, or contractors for any loss, damage, or expense incurred
related to the purchased product when the above warranty terms and conditions are not fulfilled.
Any technical assistance with system design provided by Rootech's personnel or representatives shall be
deemed to be a suggestion. The original purchaser is responsible for determining the feasibility of such
suggestions and should conduct tests to prove their feasibility.
It is the original purchasers responsibility to determine the suitability of the product and associated
documentation. The original purchaser should acknowledge that 100% up time is not realizable because
of possible hardware or software defects. The original purchaser should recognize that such defects and
failures may cause inaccuracies or malfunctions.
No agency, corporate entity, or employee of Rootech or other companies has authority to amend,
modify or extend the terms and conditions of this warranty in any way without express written
authorization from Rootech, Inc.
Standards Compliance
Energy-usage Monitor
E522977
MSIP-REM-RTE-ACCURA2300
Accura 2300/2350 User Guide
Revision History
2011 Rootech Inc. All Rights Reserved
Page 9
Revision History
The following versions of Accura 2300/2350 User Guide have been released.
Revision
Date
Description
Revision 2.00
February 14, 2022
Release of the User Guide for the device with the HW revision number
higher than 100.00
Changed voltage sampling information to 512 samples/cycle
Added contents on the 1P2F measurement of the 3P power measuring
module
Added contents on the demand sync mode
Added contents on connection between external ZCTs and Accura 2350
modules
Added contents on the power event log
Revision 2.01
September 27, 2022
Changed some of the terms used in the document to achieve
consistency
Contents
Accura 2300/2350 User Guide
Page 10
2011 Rootech Inc. All Rights Reserved
Contents
Chapter 1
Introduction ..................................................................................................................................................... 18
Overview .................................................................................................................................................................................................................. 18
Applications ........................................................................................................................................................................................................... 22
Product Information .......................................................................................................................................................................................... 23
Distribution Panel Digital Meter/Power Measuring Module .............................................................................................. 23
Special-purpose Modules..................................................................................................................................................................... 25
Installation Example ................................................................................................................................................................................ 26
Product Features ....................................................................................................................................................................................... 29
Chapter 2
Installation ....................................................................................................................................................... 34
Installation Conditions ...................................................................................................................................................................................... 34
Before Installation ............................................................................................................................................................................................... 35
Product Appearance ............................................................................................................................................................................... 35
Components ................................................................................................................................................................................................ 37
Dimensions .................................................................................................................................................................................................. 40
Installation Example ................................................................................................................................................................................ 47
Step 1: Installing the Product ....................................................................................................................................................................... 49
Mounting Accura 2300 on the Panel ............................................................................................................................................. 49
Mounting Accura 2350-3P Power Measuring Modules on the Panel ........................................................................... 50
Mounting Accura 2350-1P Power Measuring Module on the Panel ............................................................................. 57
Mounting Accura 2350-3PSC Power Measuring Module on the Panel ....................................................................... 64
Mounting Accura 2350-1PSC Power Measuring Module on the Panel ....................................................................... 69
Mounting Accura 2350-1PSCSH Power Measuring Module on the Panel ................................................................. 74
Step 2: Wiring Accura 2300 ........................................................................................................................................................................... 78
Voltage Wiring of Accura 2300 ......................................................................................................................................................... 78
Digital Input/Output Wiring of Accura 2300 ............................................................................................................................. 84
Step 3: Through-hole Current Wiring of Accura 2350 ..................................................................................................................... 87
Through-hole Wiring of Accura 2350-3P/3PSC Modules .................................................................................................... 87
Through-hole Wiring of Accura 2350-1P/1PSH/1PSC Modules ....................................................................................... 91
Through-hole Wiring of Accura 2350-1PSCSH Modules ..................................................................................................... 93
Step 4: Connecting Accura 2350 with External ZCTs ........................................................................................................................ 96
Step 5: Connecting Accura 2300 with Accura 2350 .......................................................................................................................... 98
Step 6: Connecting Accura 2300 Devices for External Communication ...............................................................................100
Ethernet Communication ....................................................................................................................................................................100
RS-485 Communication(Option) .....................................................................................................................................................102
Step 7: Accura 2300 Power Supply and Ground Wiring ...............................................................................................................104
Power Supply Wiring ............................................................................................................................................................................104
Ground Wiring .........................................................................................................................................................................................104
Accura 2300/2350 User Guide
Contents
2011 Rootech Inc. All Rights Reserved
Page 11
Chapter 3
Accura 2350 Operation/Setup .................................................................................................................... 105
Operation Mode .....................................................................................................................................................................................105
Button Operation ....................................................................................................................................................................................105
Accura 2350-3P/3PSC .....................................................................................................................................................................................106
Applied Model .........................................................................................................................................................................................106
Front View ..................................................................................................................................................................................................106
Display Mode ...........................................................................................................................................................................................107
Setup Mode...............................................................................................................................................................................................109
Accura 2350-1P/1PSC .....................................................................................................................................................................................123
Applied Model .........................................................................................................................................................................................123
Front View ..................................................................................................................................................................................................123
Display Mode ...........................................................................................................................................................................................124
Setup Mode...............................................................................................................................................................................................124
Accura 2350-1PSCSH ......................................................................................................................................................................................133
Applied Model .........................................................................................................................................................................................133
Front View ..................................................................................................................................................................................................133
Display Mode ...........................................................................................................................................................................................134
Setup Mode...............................................................................................................................................................................................134
Chapter 4
Accura 2300 Operation/Setup .................................................................................................................... 145
Device Configuration ......................................................................................................................................................................................145
Operation Modes ...................................................................................................................................................................................145
LED Display ................................................................................................................................................................................................145
Button Operation ....................................................................................................................................................................................146
Display Mode ......................................................................................................................................................................................................148
Front View ..................................................................................................................................................................................................148
Selecting the ID of Accura 2350 Module...................................................................................................................................150
Full Display Screen .................................................................................................................................................................................152
Measurement of Voltage/Current/Power/Energy ...................................................................................................................153
Measurement of Voltage/Frequency ............................................................................................................................................153
Measurement of Current ....................................................................................................................................................................154
Measurement of Power/Power Factor ..........................................................................................................................................154
Measurement of Demand ..................................................................................................................................................................155
Measurement of Active Energy .......................................................................................................................................................155
Measurement of Leakage Current .................................................................................................................................................156
Ethernet Information ............................................................................................................................................................................156
Temperature/Date & Time .................................................................................................................................................................158
Setup Mode .........................................................................................................................................................................................................159
Full Screen in Setup Mode ................................................................................................................................................................160
Measurement Setup ..............................................................................................................................................................................161
Event Setup ...............................................................................................................................................................................................167
Accura 2350 Module ID Setup ........................................................................................................................................................177
Contents
Accura 2300/2350 User Guide
Page 12
2011 Rootech Inc. All Rights Reserved
Accura 2350-1P Device Group Setup...........................................................................................................................................181
Ethernet Communication Setup ......................................................................................................................................................185
RS-485 Communication Setup ........................................................................................................................................................188
Reset Configuration ...............................................................................................................................................................................190
Digital Input/Output Setup ...............................................................................................................................................................192
Display Setup ............................................................................................................................................................................................197
Information ................................................................................................................................................................................................200
Event Log Mode ................................................................................................................................................................................................202
Start Event and End Event .................................................................................................................................................................202
Providing Notifications for Start Events......................................................................................................................................202
Clearing Event Notifications..............................................................................................................................................................202
Button Operation ....................................................................................................................................................................................203
Event Log Number .................................................................................................................................................................................204
Event Timestamp ....................................................................................................................................................................................204
Dip Event Log ...........................................................................................................................................................................................205
Swell Event Log .......................................................................................................................................................................................205
Fuse Fail Event Log ................................................................................................................................................................................206
Temperature Event Log .......................................................................................................................................................................207
Current Event Log ..................................................................................................................................................................................207
Leakage Current Event Log ...............................................................................................................................................................208
Demand Current Event Log...............................................................................................................................................................208
No Event Log ............................................................................................................................................................................................209
Necessary Steps for Device Setup ...........................................................................................................................................................210
Step 1: Setup for the Voltage Wiring of Accura 2300 and PT Rating .........................................................................210
Step 2: Automatic Assignment of Accura 2350 Module IDs and Update of IDs ..................................................211
Step 3: Accura 2300 Ethernet Setup .............................................................................................................................................214
Step 3-1 IP, Subnet Mask, and Gateway Setup .......................................................................................................................214
Chapter 5
Measurements ............................................................................................................................................... 215
General Measurement ....................................................................................................................................................................................215
Measurement Event .........................................................................................................................................................................................217
Voltage Wiring ....................................................................................................................................................................................................218
3-Phase 4-Wire Connection ..............................................................................................................................................................218
3-Phase 3-Wire Connection ..............................................................................................................................................................219
1-Phase 3-Wire Connection ..............................................................................................................................................................221
1-Phase 2-Wire Connection ..............................................................................................................................................................222
Measurement of Voltage Dips(Sags)/Swells ........................................................................................................................................223
Leakage Current Measurement ..................................................................................................................................................................224
Residual Voltage Measurement .................................................................................................................................................................224
Residual Current Measurement .................................................................................................................................................................224
Measurement of Power Per Phase ...........................................................................................................................................................225
Three-phase Power Measurement ...........................................................................................................................................................226
Accura 2300/2350 User Guide
Contents
2011 Rootech Inc. All Rights Reserved
Page 13
Power Factor(PF) Measurement .................................................................................................................................................................227
Phase Angle Measurement(Lead/Lag) ....................................................................................................................................................228
Demand Measurement...................................................................................................................................................................................229
Voltage Harmonics ...........................................................................................................................................................................................231
Current Harmonics ...........................................................................................................................................................................................231
Unbalance(NEMA MG1) .................................................................................................................................................................................232
Negative-Sequence/Zero-Sequence Unbalance ................................................................................................................................233
Aggregation .........................................................................................................................................................................................................234
Appendix A
Specifications ............................................................................................................................................. 237
Appendix B
Standards Compliance .............................................................................................................................. 247
IEC 62053-22:2020 Static Meters for AC Active Energy (Classes 0.1S, 0.2S and 0.5S) .......................................250
IEC 62053-24:2020 Static Meters for Fundamental Reactive Energy (Classes 0.5S, 1S, 1, 2 and 3) ............250
Appendix C
Accuracy/Reliability ................................................................................................................................... 251
Accuracy ......................................................................................................................................................................................................251
Reliability .....................................................................................................................................................................................................252
Appendix D
Line-to-neutral Voltage for Common Main Supply Systems .................................................................... 253
Wiring Modes ...........................................................................................................................................................................................253
Appendix E
Ordering Information ................................................................................................................................ 254
Figures
Accura 2300/2350 User Guide
Page 14
2011 Rootech Inc. All Rights Reserved
Figures
Fig 1.1 Through-hole Type Current Sensing Structure of Accura 2350-3P/1P Module ....................................... 20
Fig 1.2 Accura 2350 Module Compatible with MCCBs/ELBs .............................................................................................. 20
Fig 1.3 Installation of Accura 2350-3PSC Module ................................................................................................................... 21
Fig 1.4 Installation Example of Accura 2300/2350 Modules .............................................................................................. 26
Fig 1.5 Installation Example of Split-core Power Measuring Modules .......................................................................... 27
Fig 2.1 Accura 2300 Front .................................................................................................................................................................... 35
Fig 2.2 Accura 2300 Side ...................................................................................................................................................................... 35
Fig 2.3 Accura 2300 Rear...................................................................................................................................................................... 35
Fig 2.4 Accura 2350-3P/1P Power Measuring Modules ....................................................................................................... 36
Fig 2.5 Accura 2350-3PSC/1PSC/1PSCSH Split-core Power Measuring Modules ................................................... 36
Fig 2.6 Accura 2300 Components .................................................................................................................................................... 37
Fig 2.7 Accura 2350-3P Components ............................................................................................................................................ 37
Fig 2.8 Accura 2350-1P Components ............................................................................................................................................ 37
Fig 2.9 Accura 2350-1PSH Components ...................................................................................................................................... 38
Fig 2.10 Accura 2350-3PSC Components .................................................................................................................................... 38
Fig 2.11 Accura 2350-1PSC Components .................................................................................................................................... 38
Fig 2.12 Accura 2350-1PSCSH Components .............................................................................................................................. 39
Fig 2.13 TM-3P Components ............................................................................................................................................................. 39
Fig 2.14 TM-1P Components ............................................................................................................................................................. 39
Fig 2.15 Accura 2300 Front Dimensions ....................................................................................................................................... 40
Fig 2.16 Accura 2300 Side Dimensions ......................................................................................................................................... 40
Fig 2.17 Accura 2300 Rear Dimensions ........................................................................................................................................ 40
Fig 2.18 Accura 2350-3P Module Dimensions .......................................................................................................................... 41
Fig 2.19 TM-3P Terminal Block Dimensions ............................................................................................................................... 41
Fig 2.20 Accura 2350-1P Module Dimensions .......................................................................................................................... 42
Fig 2.21 Accura 2350-1PSH Module Dimensions .................................................................................................................... 42
Fig 2.22 TM-1P Terminal Block Dimensions ............................................................................................................................... 43
Fig 2.23 Accura 2350-3PSC Module Dimensions ..................................................................................................................... 44
Fig 2.24 Accura 2350-1PSC Module Dimensions ..................................................................................................................... 45
Fig 2.25 Accura 2350-1PSCSH Module Dimensions ............................................................................................................... 45
Fig 2.26 Installation Diagram of Accura 2300/2350-3P/1P Power Measuring Modules ...................................... 47
Fig 2.27 Installation Diagram of Accura 2300/2350 Split-core Power Measuring Modules .............................. 48
Fig 2.28 Mounting Accura 2300 on the Panel .......................................................................................................................... 49
Fig 2.29 Mounting Accura 2350-3P Power Measuring Module on the Panel .......................................................... 50
Accura 2300/2350 User Guide
Figures
2011 Rootech Inc. All Rights Reserved
Page 15
Fig 2.30 Mounting Accura 2350-3P Module on the Panel through Mounting Holes .......................................... 51
Fig 2.31 Mounting the Mounting Plate/Terminal Block for Accura 2350-3P on the Panel ............................... 55
Fig 2.32 Mounting Accura 2350-1P Module on the Panel(Load Located on the Right Side) .......................... 57
Fig 2.33 Mounting Accura 2350-1P Module on the Panel through Mounting Holes .......................................... 58
Fig 2.34 Mounting the Mounting Plate/Terminal Block for Accura 2350-1P on the Panel ............................... 62
Fig 2.35 Mounting Accura 2350-3PSC Module on the Panel (New Installation) .................................................... 64
Fig 2.36 Mounting Accura 2350-3PSC Module on the Panel through Mounting Holes..................................... 65
Fig 2.37 Mounting the Mounting Plate for Accura 2350-3PSC Module on the Panel ......................................... 67
Fig 2.38 Mounting Accura 2350-3PSC Module on the Panel(Installation) ................................................................. 68
Fig 2.39 Mounting Accura 2350-1PSC Module on the Panel (New Installation) .................................................... 69
Fig 2.40 Mounting Accura 2350-1PSC Module on the Panel through Mounting Holes..................................... 70
Fig 2.41 Mounting the Mounting Plate for Accura 2350-1PSC Module on the Panel ......................................... 72
Fig 2.42 Mounting Accura 2350-1PSC Module in the Existing Panel ........................................................................... 73
Fig 2.43 Mounting Accura 2350-1PSCSH Module on the Panel (New Installation) .............................................. 74
Fig 2.44 Mounting Accura 2350-1PSCSH Module on the Panel through Mounting Holes............................... 75
Fig 2.45 Mounting the Mounting Plate for Accura 2350-1PSCSH Module on the Panel ................................... 76
Fig 2.46 Mounting Accura 2350-1PSCSH Module on the Panel (Retrofit Installation) ........................................ 77
Fig 2.47 Voltage Wiring of Accura 2300....................................................................................................................................... 78
Fig 2.48 3-phase 4-wire, Direct Connection ............................................................................................................................... 80
Fig 2.49 3-phase 4-wire Connection 3 PTs ................................................................................................................................. 80
Fig 2.50 3-phase 3-wire, Direct Connection ............................................................................................................................... 81
Fig 2.51 Three-phase 3-wire Connection with 2 PTs ............................................................................................................. 81
Fig 2.52 Single-phase 3-wire, Direct Connection ..................................................................................................................... 82
Fig 2.53 Single-phase 3-wire Connection with 2 PTs ............................................................................................................ 82
Fig 2.54 Single-phase 2-wire, Direct Connection ..................................................................................................................... 83
Fig 2.55 Single-phase 2-wire Connection with 1 PT .............................................................................................................. 83
Fig 2.56 Digital Input/Output Channels on Accura 2300 .................................................................................................... 84
Fig 2.57 Digital Input .............................................................................................................................................................................. 85
Fig 2.58 Application of DC Relay ..................................................................................................................................................... 86
Fig 2.59 Application of AC Relay ...................................................................................................................................................... 86
Fig 2.60 3P4W/3P3W Through-hole Wiring ............................................................................................................................... 88
Fig 2.61 3P4W/3P3W Through-hole Wiring with 3 CTs ....................................................................................................... 88
Fig 2.62 3P3W Through-hole Wiring with 2 CTs ...................................................................................................................... 89
Fig 2.64 Single-phase Line-to-neutral Through-hole Wiring ............................................................................................. 92
Fig 2.65 Single-phase Line-to-line Through-hole Wiring .................................................................................................... 92
Fig 2.66 Grouping Three Accura 2350-1PSCSH Modules in 3P4W/3P3W Mode .................................................... 94
Figures
Accura 2300/2350 User Guide
Page 16
2011 Rootech Inc. All Rights Reserved
Fig 2.67 Grouping Two Accura 2350-1PSCSH Modules in 3P3W Mode ..................................................................... 94
Fig 2.68 Single-phase Line-to-neutral Through-hole Wiring of Single-hole Module ........................................... 95
Fig 2.69 Single-phase Line-to-line Through-hole Wiring of Single-hole Module .................................................. 95
Fig 2.70 Connecting the Cable for Connection with the ZCT with the External ZCT ........................................... 96
Fig 2.71 Connecting Accura 2350 Module with the External ZCT .................................................................................. 97
Fig 2.72 Example of Connecting Accura 2300 to Accura 2350 for Dedicated Communication ...................... 98
Fig 2.73 Ethernet Communication Port on Accura 2300 .............................................................................................100
Fig 2.74 Connecting Accura 2300 Devices via Ethernet Communication .................................................................101
Fig 2.75 RS-485 Communication Port on Accura 2300 (Option) ...................................................................................102
Fig 2.76 Connecting Accura 2300 Devices via RS-485 Communication ....................................................................103
Fig 2.73 Accura 2300 Power Supply Wiring .............................................................................................................................104
Fig 4.1 Accura 2300 Front View ......................................................................................................................................................145
Fig 4.2 Screen in Display Mode ......................................................................................................................................................146
Fig 4.3 Screen in Setup Mode .........................................................................................................................................................146
Fig 4.4 Screen in Event Log Mode ................................................................................................................................................147
Fig 4.5 Accura 2300 Front View ......................................................................................................................................................148
Fig 4.6 Temperature Sensor on Accura 2300 ...........................................................................................................................150
Fig 4.7 Selecting the ID of Accura 2350 Module ...................................................................................................................150
Fig 4.8 Voltage/Current/Power/Energy Display Screen .......................................................................................................153
Fig 4.9 Voltage/Current/Power/Energy Display Screen for Each Phase ......................................................................153
Fig 4.10 Line-to-line Voltage Display Screen ...........................................................................................................................154
Fig 4.11 Phase Current Display Screen........................................................................................................................................154
Fig 4.12 Active Power Display Screen ..........................................................................................................................................155
Fig 4.13 Active Power Demand Display Screen ......................................................................................................................155
Fig 4.14 Net Energy Display Screen ..............................................................................................................................................156
Fig 4.15 Leakage Current Display Screen...................................................................................................................................156
Fig 4.16 Ethernet Connection Status Display Screen ...........................................................................................................157
Fig 4.17 Temperature Display Screen ...........................................................................................................................................158
Fig 4.18 3-phase 4-wire Connection(3P4W): Setup for PT Primary VL12 & Secondary V12 Values ................161
Fig 4.19 3-phase 3-wire Connection(3P3W): Setup for PT Primary VL12 & Secondary V12 Values ...............162
Fig 4.20 1-phase 3-wire Connection(1P3W): Setup for PT Primary VL12 & Secondary V13 Values ................162
Fig 4.21 1-phase 2-wire Connection(1P2W): Setup for PT Primary VL1 & Secondary V1N Values .................162
Fig 4.22 Dip Event Setup(3-phase 4-wire) .................................................................................................................................168
Fig 4.23 Dip Event Setup(3-phase 3-wire) .................................................................................................................................168
Fig 4.24 Swell Event Setup(3-phase 4-wire) .............................................................................................................................170
Fig 4.25 Swell Event Setup(3-phase 3-wire) .............................................................................................................................170
Accura 2300/2350 User Guide
Figures
2011 Rootech Inc. All Rights Reserved
Page 17
Fig 4.26 Dip(Sag) Event Notification Screen.............................................................................................................................202
Fig 4.27 Swell Event Notification Screen ....................................................................................................................................202
Fig 4.28 Example of Event Log Number .....................................................................................................................................204
Fig 5.1 3P4W Connection with 3 PTs and 3 CTs ....................................................................................................................218
Fig 5.2 3P3W Connection with 2 PTs and 3 CTs ....................................................................................................................219
Fig 5.3 1P3W Connection with 2 PTs and 2 CTs ....................................................................................................................221
Fig 5.4 1P2W Connection with 1 PT and 1 CT ........................................................................................................................222
Fig 5.5 Calculation of 1-cycle RMS Voltage Refreshed Each Half Cycle ....................................................................223
Fig 5.6 Voltage Dip(Sag) Detection ...............................................................................................................................................223
Fig 5.7 Vector Sum for the Total Apparent Power ................................................................................................................226
Fig 5.8 Arithmetic Sum for the Total Apparent Power ........................................................................................................227
Fig 5.9 PF Sign and Phase Angle(Lead/Lag) .............................................................................................................................228
Fig 5.10 Demand Calculation ...........................................................................................................................................................229
Fig 5.11 Predicted Demand Calculation .....................................................................................................................................230
Fig 5.12 Hourly Auto Sync .................................................................................................................................................................230
Fig 5.13 Manual Sync ...........................................................................................................................................................................231
Fig 5.14 Symmetrical Components................................................................................................................................................233
Fig 5.15 Aggregation Process ..........................................................................................................................................................234
Chapter 1 Introduction
Accura 2300/2350 User Guide
Page 18
2011 Rootech Inc. All Rights Reserved
Chapter 1
Introduction
Overview
Paradigm Shift in Energy Management
When energy costs were low, energy management mainly focused on controlling the total energy
supply to all loads using switchgear panels, including incoming feeders and ABS panels for stable
power supply. However, carbon pricing policies have been implemented since 2015, and energy costs
have sharply increased. This has resulted in a rapidly growing need to manage energy usage on
individual branch loads in distribution panels at various industrial facilities, manufacturing plants, IDC
centers, etc.
Limits in Applying Digital Power Meters Used in Switchgear Panels to Distribution Panels
Installing digital power meters used in existing switchgear panels at distribution panels entails
limitations, such as narrow installation space, electrical hazards arising from the voltage and current
wiring process, and high installation costs. It makes it difficult for energy managers to access energy
data on individual branch loads and devise practical energy efficiency measures for each branch load.
Power Meters Specialized for Managing Major Branch Loads
The distribution panel digital power meter product line includes Accura 2300 installed on the front of
distribution panels(including MCC panels) and Accura 2350 installed at individual branch loads inside
distribution panels. Accura 2300 collects power data from multiple Accura 2350 modules via internal
communication and displays measurement data for each branch load. This enables energy managers to
check power data on individual branch loads in distribution panels, which were unavailable with the
existing digital power meters installed at switchgear panels.
Accurate Measurements: ±0.2 %/±0.5 %1 of Reading(Voltage/Current) and Class 0.5S/Class 0.2S 2
(Active Energy)
Due to greenhouse gas emission regulations, it has recently become essential to establish enterprise-
wide energy management systems for efficient energy usage at sites such as plants, manufacturing
factories, and buildings. A key factor determining the reliability of energy management systems is the
measurement accuracy of meters. Accura 2300/2350 perform accurate voltage/current measurements
with ±0.2/±0.5 %1 of reading accuracy. It also meets IEC 62053-22 Class 0.5S/Class 0.2S2 standards for
active energy measurement. Thus, this allows for accurate analysis and diagnosis of various problems in
energy management at power facilities.
1.Accura 2350-3PSC/1PSC modules have ±0.5 % of reading accuracy for current measurement, and the maximum
accuracy error of ±1 % may occur according to the position of the holes
cables pass through.
2. Accura 2350-1PSCSH modules meet IEC 62053-22 Class 0.2S standards for active energy measurement.
Accura 2300/2350 User Guide
Chapter 1 Introduction
2011 Rootech Inc. All Rights Reserved
Page 19
A Variety of Data including Dip(Sag)/Swell Available for Power Quality Analysis
Accura 2300/2350 provide a variety of data, including dips(sags), swells and harmonics(up to 40th
order), crest factor, K-factor, and unbalance for power quality analysis. It allows energy managers to
easily identify changes in power quality in various distribution panels at power facilities, enabling
effective power quality management.
Maximum/Minimum/Average Values Available within an Aggregation Interval
Accura 2300/2350 calculate the average of the data collected every 0.5 seconds based on the data
measured over one cycle for various parameters, including voltage, current, and power. Based on this
data, it also provides the maximum/minimum/average values for various aggregation intervals, including
1 second, 5 seconds, 1 minute, 5 minutes, 1 hour and 6 hours. A measurement interval longer than 0.5
seconds refers to an aggregation interval.
Via communication, Accura 2300/2350 provide not only the average value for the 0.5-second interval
but also the maximum/minimum/average values for each aggregation interval and timestamped data
for the max/min values. Since it includes measurement data that change instantaneously during
aggregation intervals, it allows for accurate trend analysis of voltage, current and power quality.
Proven Safety and Reliability with CE/UL Certifications
The internal and external structures(product and circuit design) of Accura 2300/2350 meet safety and
reliability requirements for CE(EN 61326-1, EN 61326-2-1, EN 61010-1) and UL(UL 61010-1 3rd edition,
IEC 61010-2-030) standards.
Through-hole Type Structure for Easier and Safer Installation
Accura 2350-3P/1P power measuring modules feature the through-hole type current sensing structure
that does not require electrical contact with cables or busbars. Therefore, it ensures safety from
electrical accidents, as well as easy installations. The TM-3P terminal block also allows for easier
electrical wiring.
Chapter 1 Introduction
Accura 2300/2350 User Guide
Page 20
2011 Rootech Inc. All Rights Reserved
Fig 1.1 Through-hole Type Current Sensing Structure of Accura 2350-3P/1P Module
Compatible with MCCBs/ELBs with Various Ratings
Accura 2350-3P/1P power measuring modules are compatible with MCCBs/ ELBs with a range of current
ratings since they have identical installation dimensions and wiring hole positions. Thus, when installing
the products, it is possible to integrate them into the existing MCCBs/ELBs in distribution panels.
Fig 1.2 Accura 2350 Module Compatible with MCCBs/ELBs
Split-core Structure Enabling Device Installation on Live Wires (Applicable for Split-core Modules)
Accura 2350-3PSC/1PSC/1PSCSH modules feature the split-core structure. It allows for the easy
installation of the products on live wires without the need to cut off power.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256

ROOTECH Accura 2300/2350 User guide

Category
Measuring, testing & control
Type
User guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI