Frick Quantum LX Evaporator Operating instructions

Category
Thermostats
Type
Operating instructions
OPERATION – SERVICE
(SESSION LEVEL 2)
FRICK QUANTUM™ LX
EVAPORATOR
CONTROL PANEL
VERSION 3.0x
Form S90-612 O (MARCH 2008)
File: SERVICE MANUAL - SECTION 90
Replaces: NOTHING
Dist: 3, 3a, 3b, 3c
OPERATION - SERVICE
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 2 OPERATION - SERVICE
Table of Contents
TYPICAL SYSTEM CONFIGURATION ................................................................................................4
CONNECTING A COMPUTER DIRECTLY TO A QUANTUM™ LX CONTROL PANEL ....................4
OVERVIEW OF OPERATOR INTERFACES........................................................................................5
Operator Access ...........................................................................................................................5
To Change Setpoints ....................................................................................................................5
Keys And Key Functions...............................................................................................................6
Menu Structure .............................................................................................................................7
GRAPHIC SCREENS...............................................................................................................................8
OPERATING STATUS..........................................................................................................................8
ZONE OVERVIEW OPERATING STATUS.........................................................................................10
USER DEFINED OPERATING STAUS SCREEN ..............................................................................11
MODE SETUP SCREEN.....................................................................................................................12
SAFETIES...........................................................................................................................................13
Current Safeties ..........................................................................................................................13
Safety History..............................................................................................................................14
SYSTEM STATUS ..............................................................................................................................15
Trending Setup ...........................................................................................................................15
Real Time Trending ....................................................................................................................16
History Trending..........................................................................................................................17
Real Time Data Log ....................................................................................................................18
History Data Log .........................................................................................................................19
SETPOINTS ........................................................................................................................................20
Cooling (Mode 1) ........................................................................................................................20
Heating (Mode 1) ........................................................................................................................22
Heating Timers............................................................................................................................23
Mode Schedule ...........................................................................................................................24
Defrost Setpoints ........................................................................................................................25
Defrost Schedule ........................................................................................................................26
Safety Setpoints..........................................................................................................................27
PID Setup....................................................................................................................................28
Auxiliaries....................................................................................................................................30
Analog Input Safeties – Page 1.......................................................................................30
Analog Input Safeties – Page 2.......................................................................................31
Digital Input Configuration...............................................................................................32
Digital Output Configuration ............................................................................................33
Panel...........................................................................................................................................34
CALIBRATION....................................................................................................................................35
Analog Inputs ..............................................................................................................................35
Analog Output Calibration...........................................................................................................36
Auxiliaries....................................................................................................................................37
Page 1.............................................................................................................................37
Page 2.............................................................................................................................38
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION - SERVICE Page 3
CONFIGURATION ..............................................................................................................................39
Global Zone Configuration ..........................................................................................................39
Current Zone Configuration.........................................................................................................40
Defrost Group Setup ...................................................................................................................41
Temperature Configuration .........................................................................................................42
Communications .........................................................................................................................43
Ethernet.......................................................................................................................................45
Security .......................................................................................................................................47
SESSION.............................................................................................................................................48
SERVICE .............................................................................................................................................49
Communications Log ..................................................................................................................49
Communications Loop Back Test ...............................................................................................50
Diagnostics..................................................................................................................................51
Software Maintenance ................................................................................................................52
ABOUT ................................................................................................................................................54
MISCELLANEOUS SCREENS............................................................................................................55
Alpha ...........................................................................................................................................55
Alarms/Shutdowns Messages ..........................................................................................................56
Index....................................................................................................................................................57
Warning
The Quantum™ has the capability of being modified by the user/owner in order to obtain different performance characteristics.
Any modification to the standard default settings may have a severe negative impact on the operation and performance of the
equipment. Any modification to these control settings is the sole responsibility of the user/owner and Frick disclaims any
liability for the consequences of these modifications. It is possible that the modification of these settings may cause improper
operation and performance that results in property damage, personal injury or death. It is the responsibility of the user/owner to
evaluate and assess the consequences of their actions prior to modifying the controls for this unit.
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 4 OPERATION - SERVICE
TYPICAL SYSTEM CONFIGURATION
A typical Evaporator system may control as few as one
zone, or up to thirty zones. Each Evaporator system
operates independently of one another yet they may all be
inter-connected via a common Ethernet connection. A
system may include the Quantum™ Evaporator LX
Interface Panel, Zone Controller, an Ethernet Hub or
Switch, and a computer with Web Browser.
Each of these zone controllers is connected to a
Quantum™ LX Interface Panel. The Interface Panel can
then be connected to an HMI or a remote computer:
CONNECTING A COMPUTER DIRECTLY TO A QUANTUM™ LX CONTROL PANEL
Especially for the purpose of maintenance, if you wish to
connect directly to a single panel from a computer
(desktop or laptop), you can avoid the switch and use a
crossover Cat-5 cable:
Refer to the following pictorial and color code table to
construct a crossover cable:
Both Ends of a crossover-cable
CAT-5 Ethernet cable color codes
1 – White w/orange stripe 5 – White w/blue stripe
2 – Orange w/white stripe 6 – Green w/white stripe
3 – White w/green stripe 7 – White w/brown stripe
4 – Blue w/white stripe 8 – Brown w/white stripe
1 2 3 4 5 6 7 8
Left (Not
Crossed)
3 6 1 4 5 278
Right (Crossed)
Ethernet Port
Quantum™ LX
Evaporator
Controller
Desktop or
laptop
Computer
Cross-over
CAT-5 Cable
All network cables
are Pin-to-Pin CAT-
5
Cab
l
es
Computer or
HMI
Ethernet Hub or
Switch
Zone
Controller
Zone
Controller
Zone
Controller
Zone
Controller
Zone
Controller
Zone
Controller
Zone
Controller
Quantum™ LX
Evaporator
Interface Panel
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION - SERVICE Page 5
OVERVIEW OF OPERATOR INTERFACES
Web Browser
The web browser interface can be viewed from any
desktop or laptop computer, which has access to the
network that an Evaporator Controller is attached to. To
change screens, setpoints, etc., you simply use a mouse
and the keyboard to view and change data.
All Evaporator screens that are shown will have several buttons
on the right hand side of the screen. Most screens will have
three buttons, and one setpoint box. The three buttons are:
[Menu] – Clicking on this button will cause the main
menu to appear on the left side of the screen. Clicking
a second time will cause the menu to disappear.
[Start Refresh] [Stop Refresh] – This button(s) appears
immediately below the [Menu] button. This is actually a
toggle button, as it changes function from Start Refresh to
Stop Refresh each time it is clicked on. When the button
shows as Start Refresh, a setpoint box will appear below it,
with a time value displayed. The time value determines how
often the display screen will refresh, or update its values. This
time value is defaulted to 5 seconds, which means that the
display will update all values shown every 5 seconds.
Depending on the network connection speed, this updating
may interfere with your ability to change data setpoints,
because the screen will refresh while you are entering the
data. To solve this, simply toggle the Refresh Button. By
pressing [Stop Refresh], screen refreshing will terminate,
and the time setpoint box will reappear. In this state, the
particular screen that you are viewing will never update the
displayed values. Changing to another screen will show the
most recent values on the new screen, and then will not
update again. So in the Stop Refresh state, screens will only
be updated when new screens are accessed. This feature
should not be used when monitoring data.
One screen that DOES NOT have these buttons is:
Software Maintenance – To leave this screen,
click on [Exit] button. Note: Using the [Exit]
button takes several seconds, and it will force the
password level back to zero.
OPERATOR ACCESS
Operator access to this system is through various screens. A
screen is the physical representation of data on the display. Each
screen has a title area. The title is descriptive of the screen. The
current date and time is shown in this title area. The day of the
week, Sunday (Sun.) through Saturday (Sat.) is displayed. The
month of the year from January (Jan.) to December (Dec.) is
displayed. The day of the month from 1 to 31 and the year from
0001 to 9999 is displayed. The time displayed is the current time in
24 hours (military) format. The hours, minutes and seconds are
displayed.
Some screens are for informational purposes only, and
cannot be modified. These screens typically show analog
values such as temperature and humidity, which are
strictly functions of an associated sensor, and as such,
cannot be modified. Other screens show setpoint values
which can be changed, in order modify the units operating
characteristics. For easier viewing, related information is
separated into boxes. Sometimes selections are hidden
when that the feature is unavailable.
TO CHANGE SETPOINTS
The setpoints define the operation and limits of each air
unit. These setpoints can be change by operators in the
field. These setpoints are stored on the compact Flash
card.
NOTE: Setpoints are not lost after power is interrupted.
However, we suggest that a list of Setpoints be recorded
and stored safely to facilitate reentry, in case there is a need
to return to the original settings.
1. The data entry fields are identified by a black box
with a white interior. The data is shown in black text.
When on a screen that has adjustable setpoints, tab
to the setpoint box that you wish to modify (or select
it on a web browser). Once the data field has been
selected, the background turns blue, and the text
turns white.
2. The current value of that setpoint is shown. Use
the keypad to enter the new value. Typing a new
value will completely erase the old value.
3. Press the keypad [ENTER] key to input the new
data in the data entry field and to move to the
next data entry field.
4. If the data entered into the setpoint box is valid,
then once you have pressed the keyboard [ENTER]
key, the [SUBMIT] box in the lower left hand side of
the viewing screen will turn from a grey background,
to a red background. After all the setpoint changes
on this screen have been entered, press the
[SUBMIT] button to save the setpoint changes to
memory.
5. If the value is out of bounds, an error message
box displays the proper range of values. Press
the [OK] button to acknowledge the error
message. Re-enter a correct value.
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 6 OPERATION - SERVICE
KEYS AND KEY FUNCTIONS
The following is a list of the labeled keypad keys and the actions that occur when they are pressed:
Key Function
NUMERALS [0] - [9] - The numerical
keys are used to enter a value in a data
field. These keys may also be used to
enter text and special characters. Refer
to the section entitled MISCELLENEOUS
Screens – Alpha for additional
Information.
DECIMAL [.] - This key is used when
entering a decimal value in a data field.
This key may also be used to enter
special characters. Refer to the section
entitled MISCELLENEOUS Screens –
Alpha for additional Information.
[+/-] - When changing a value in a data
field, this key toggles the value between
negative and positive. This key may also
be used to enter special characters.
Refer to the section entitled
MISCELLENEOUS Screens – Alpha for
additional Information.
[BACKSPACE] - Pressing this key will
cause the current location of the cursor to
backup one position per key depression.
When changing a value in a data field,
this key will delete the selected
character.
Key Function
[UP ARROW] - Provides upward
navigation within the MAIN MENU
window.
[TAB] - When in the mode of changing
setpoints, pressing this key will cause the
cursor to jump to the next data entry field.
[LEFT ARROW] - When in the mode of
changing setpoints, this key is used to go
to the previous data entry field. When the
MAIN MENU is shown, pressing this key
will cancel the window.
[DOWN ARROW] - Provides downward
navigation within the MAIN MENU
window.
[RIGHT ARROW] - When in the mode of
changing a data entry field, this key is
used to go to the next character.
[ENTER] - When changing data in a data
entry field, this key will accept the
change. This key is also used to select
items on Menu Windows.
[SUBMIT] - After changing a setpoint
value, Use this key to enter (submit) the
change.
[MENU] - Shows the MAIN MENU
window. This window shows the main
selections for accessing information,
setup of options, and setpoint entry.
7
8
9
4
5
6
1
2
3
0
+
-
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION - SERVICE Page 7
MENU STRUCTURE
The above graphic represents the menu structure, or tree,
of the Evaporator Quantum™ LX screens. Refer to this
tree when accessing the various screens. Please note that
this list shows all screens and that certain screens may not
be available as shown here, depending upon the enabled
options.
Trending …
Event Log
Current
History
Cooling …
Heating …
Mode Schedule
Defrost …
Safety
PID Setup
Auxiliaries …
Panel
Analog Inputs
Analog Outputs
Auxiliaries …
Global Zone Configuration
Current Zone Configuration
Defrost Group Setup
Control Temperature
Communications
Ethernet
Security
Communications Log
Communications Loop Back Test
Diagnostics
Software Maintenance
Home
Zone Overview
User Defined
Modes
Safeties …
System Status …
Setpoints …
Calibration …
Configuration …
Session
Service …
Help
About
Trending Setup
Real Time Trending
History Trending
Real Time Data Log
History Data Log
Mode 1
Mode 2
Mode 3
Mode 4
Defrost Setpoints
Defrost Schedule
Analog Inputs …
Digital Inputs
Digital Outputs
Mode 1
Mode 2
Mode 3
Mode 4
Heating Timers
Page 1
Pa
g
e 2
Page 1
Pa
g
e 2
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 8 OPERATION - SERVICE
GRAPHIC SCREENS
OPERATING STATUS
The most important information about the selected zone is
displayed here:
ZONE SELECTED – This setpoint box allows the user
to enter the ID number of the Evaporator zone that
they wish to view on this screen. When a different
zone number is entered and submitted, the screen
data will be updated with the information from that
zone. This same setpoint box appears on many of the
screens.
DATE - The actual date will be displayed in this box.
The date must first be set correctly on the
Configuration screen. The primary use of the date
feature is to provide a date stamp for Warnings and
Shutdowns. Refer to the section entitled Setting the
Date and Time for further information.
TIME - The actual time will be displayed in this box.
The time must first be set correctly on the
Configuration screen. The time will also need to be
adjusted for those locations which observe Daylight
Savings Time. The primary use of the time feature is
to provide a time stamp for Warnings and Shutdowns.
Refer to the section entitled Setting the Date and
Time for further information.
SCREEN TITLE - Each screen will have a title. The
Quantum™ LX manuals will extensively refer to
screens by these names. When referred to in these
manuals, screen names will be shown in bold italic
print, such as Operating Status.
MODE OF OPERATION – Shows the current settings
for Active Mode and Mode Control:
Active Mode – Will show one of the following:
Off
Mode 1
Mode 2
Mode 3
Mode 4
Mode Control – Will display one of the following:
Off
Manual
Automatic.
ALARM STATUS - The alarm status is displayed in
the box below the Mode of Operation box. The status
box is blank if there are no alarms present.
If a warning or shutdown condition exists, the name of
the condition will be shown in red letters.
OPERATIONAL STATUS BOX - Shows the present
operating status of the zone:
Off – The zone is not being actively controlled,
which means that all outputs are off unless
Suction is set to always on the Current Zone
Configuration screen.
Cooling – The zone is in a temperature control
mode and the liquid valve is open because the
control temperature equals or exceeds the liquid
on setpoint. The suction valve open.
Mode of
Operation
Alarm Status
Operational
Values
Setpoint
Value
Actual
Value
Zone
Selected
Date
Operational
Status Box
Defrost
Settings
Graphic
Simulation
Analog
Values
Screen Title
Time
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION – SERVICE Page 9
Satisfied - The zone is in a temperature control
mode and the liquid valve is closed because the
control temperature is less than or equals the
liquid off setpoint. During this time, the suction
valve is typically open.
Defrost – The zone is going through a defrost
cycle.
Heating - The zone is in a temperature control
mode and is using hot gas to provide heating.
SETPOINT VALUE – This is the temperature setpoint
maintained by the controller.
ACTUAL VALUE – The actual reading of the
temperature that was chosen as the control input.
OPERATIONAL VALUES
Liquid – This line will show whether the Liquid
Valve is Open or Closed or if a modulating valve,
the percentage it is open.
Suction – This line will show whether the Liquid
Valve is Open or Closed or if a modulating valve,
the percentage it is open.
Fan - This line will show whether the Fan is On or
Off or if a variable speed fan, the percentage of
the speed.
Refrig Counter - This message shows the length
of time in minutes that the liquid valve has been
opened (cooling) since the last defrost. The
counter is reset during defrost. If liquid override is
enabled and defrost has been scheduled, then
defrost will only initiate when the refrigeration
counter is greater than the counter setpoint. The
counter can help to indicate if enough ice has
built up to receive a defrost.
ANALOG READINGS BOX - The following analog
input readings may be displayed. They are shown if
they are enabled:
Return Air Temperature
Humidity (%)
Ammonia
DEFROST STATUS BOX -
Stage – The following stages of defrost are
possible if they are enabled:
Off – Defrost not active
Pump out
Soft Hot gas
Hot gas
Bleed
Fan Delay
Stage Time Remaining – The time in minutes
until the current defrost stage is completed.
Initiated by – If in defrost, the method used to
initiate the defrost is shown:
Defrost button – The operator pressed
the defrost key at the panel.
Defrost schedule – The Defrost
schedule has the current time entered
for defrost.
Digital input – The demand defrost
digital input was enabled to be used as
a signal for initiating defrost and was
energized.
Liquid Counter - Liquid Timer is
enabled and the refrigeration counter is
greater than the counter setpoint.
EVAPORATOR I/O STATUS BOX:
The present operating status of the Inputs and Outputs are
shown. One of the following messages is shown:
On – The controlled device is on.
Open – Valve is open.
Off - The controlled device is off.
Closed – Valve is closed.
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 10 OPERATION - SERVICE
ZONE OVERVIEW OPERATING STATUS
ACCESSING:
DESCRIPTION: The purpose of this screen is to allow the user to view all of the units that have been configured on this
controller.
This screen is provided to allow the user to view basic
information about all Evaporator units (up to 30) that are
configured on this system. The following columns have
been provided:
ID – The ID number of a zone, which is set by the
dipswitches of the I/O boards in the remote panel(s).
NAME – The name that has been assigned to the
zone (default is ZONE #1, 2, etc.)
STATUS – The current status of the particular zone
(OFF, COOLING, etc).
TEMP – The Control temperature.
Operating Values… Zone Overview
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION – SERVICE Page 11
USER DEFINED OPERATING STAUS SCREEN
ACCESSING:
DESCRIPTION: The purpose of this screen is to allow the user to select additional analog channels to be more readily
viewable. Since the main Operating Status (Home) screen is capable of only showing a limited number of pre-assigned
analog values, it may be desirable for the user to have a method of viewing additional information that they can select, on a
common screen. They may even select values that are already being displayed on the Operating Status screen, as well as
values that are not shown there.
This screen is provided to allow the user to view up to 20
different analog channels of their choosing.
Notice at the top of this screen is a setpoint entry box,
where a particular zone number can be entered. When a
different zone number is entered and submitted, the
screen data will be updated with the information from that
zone. This same setpoint box appears on many of the
screens.
As an example of how this screen works, assume that in
addition to the data that is shown on the Operating Status
screen, the user would like to monitor the Return Air
Temperature, Ammonia and Humidity, all on the same
screen (this one). Notice that Return Air Temperature and
Humidity are already shown on the Operating Status
(Home) screen, but the Ammonia is not shown. In order to
set this screen up to show these three values, the user would
highlight the Enable User Defined Channel 1 (or whatever
channel they wish to use), by using the keypad to tab it. Once
the box is highlighted, press the [Enter] key to show a drop
down menu. Use the tab or arrow keys to scroll through the
list. When the selection that you want to use has been
highlighted, press the [Enter] key to select it. Once selected,
a value will appear to the right of the list, which corresponds
to the analog value for that channel. Press the [Submit] key
to accept any changes.
The following selections may be shown on this screen:
Control Temperature
Ammonia
Humidity
Auxiliary Analog 1 - 10
Operating Values… User Defined
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 12 OPERATION - SERVICE
MODE SETUP SCREEN
ACCESSING:
DESCRIPTION: The purpose of this screen is to allow the user to view and set the various modes for each of the zones.
A Zone setpoint box appears at the top right corner of this
screen. Set the value within this box to the zone number
that you wish to view/modify.
This screen uses the following pull-down menus:
Zone On/Off
Off – Not controlling or defrosting.
On – Maintaining temperature, or defrosting.
Mode Control
Manual – The operator has the mode to
Manuel by selecting Active Mode.
Automatic – Active Mode has been set by
Mode Schedule.
Active Mode
Mode 1
Mode 2
Mode 3
Mode 4
A [Start Defrost] pushbutton is also located on this
page that allows the selected unit to begin Defrosting
if the Zone On/Off is set to On.
Modes
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION – SERVICE Page 13
SAFETIES - Current Safeties
ACCESSING:
DESCRIPTION: The Current Safeties screen shows the Warnings and Shutdowns that have recently occurred. When a
warning or shutdown is triggered, a blue descriptive message shows on this screen. The date and time of the warning or
shutdown occurrence is shown to the right of its description. The most recent message will appear on the top line of the screen
with the oldest appearing at the bottom. When a Warning or Shutdown is logged to this screen, it will also be logged to the
Safety History screen.
The following Current Safeties screen key is provided:
[Clear Safeties] - Selecting this key will clear all warnings
and/or shutdowns from this screen. This will also place a
date/time stamp for the corresponding entry on the Safety
History screen showing that the particular Warning or
Shutdown was cleared. Clearing the entry on the Current
Safeties screen, will not clear it from the Safety History
screen.
To resume normal operation it will be necessary to go
through the following steps:
1. Correct the condition(s) causing the warning.
2. Press the [ALARM SILENCE] key to turn off the
warning device. (This action may precede
correcting the condition(s) causing the warning).
Or, go to step 3.
3. To clear the Warnings/Shutdowns screen and
turn off any warning device, press the [Clear
Safeties] key.
4. If the conditions causing the warning have not
been corrected or a new fault has occurred, a
new WARNING or SHUTDOWN message will
appear. The Safety History screen keeps a
record of the warnings and shutdowns. This
information will help troubleshoot persistent
operational problems.
Refer to the Warnings/Shutdowns Message section for a
list of all the possible conditions.
Safeties… Current
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 14 OPERATION - SERVICE
SAFETIES - Safety History
ACCESSING:
DESCRIPTION: The Safety History screen shows the warnings and shutdowns that have recently occurred. When a warning
or shutdown is triggered, a blue descriptive message shows on this screen. The date and time of the warning or shutdown
occurrence is shown to the right of its description, followed by the date and time that the safety was cleared. The most recent
message will appear on the top line of the screen with the oldest appearing at the bottom.
It is possible to view the conditions that are shown on the
Operating Status screen at the exact moment that a
warning/shutdown occurred. Use the tab key to select
(highlight) a warning or shutdown and then press [Enter]
to view its associated Freeze (Operating Status) screen.
Freeze Screen Description
This Freeze screen provides a snapshot of the values
that were current at the time of the latest
warning/shutdown. The information on the Freeze
screen can help the user to identify the cause of the
fault. The Freeze screen has the same appearance
and contains the same information as the Operating
Status screen. (For a description of the information
presented by the Freeze screen, refer to the
Operating Status screen). This data is saved during
a power outage.
Safeties History
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION – SERVICE Page 15
SYSTEM STATUS - Trending - Trending Setup
ACCESSING:
DESCRIPTION: This is the Trending Setup screen. Up to eight channels can be monitored in real time trending, and up to
eight channels monitored in history trending.
Real Time Trending - is a method by which the user can
set the Quantum™ LX to map analog inputs to a graphic
chart format. These analog input values are stored at a
specific interval over a corresponding period of time. The
graphed values will scroll across the screen from left to
right, at a speed that is determined by the recording
interval. Two individual data points can be viewed on the
Real Time Data Log screen. A total of 900 values are
stored. Trending data is lost upon power cycle.
The following setpoints are provided:
Real Time Recording Interval – The time interval
that defines how often the real time trending data
values are updated. This value may be set for any
time duration between 1.0 second and 86,400.0
seconds (24 hours).
History Trending - is a method by which the user can set
the Quantum™ LX to record analog inputs to a graphic
chart format. This feature is similar to Real Time trending,
except that the data is not lost at power cycle. The events
that occur will scroll across the screen, at a speed that is
determined by the recording interval. A total of 2000
values are stored.
History Recording Interval – The time interval that
defines how often the history trending data values are
updated. This value may be set for any time duration
between 1.0 minute and 60.0 minutes (1 hour).
To program this screen with the data you wish to trend,
highlight the Enable Real Time Trend Channel 1 (or
whatever channel you wish to use), by using the tab key.
Once the box has been selected, a drop down menu will
appear for that channel. On the right hand side of the drop
down box will be an arrow. Selecting the arrow will to
cause all the possible settings for the channel to appear.
Use the tab key to scroll through the list. When the
selection that you want to use appears, press the [Enter]
key to select it. Once selected, the value for this channel
will be automatically trended and shown on the Real Time
Trending graph (or History Trending Graph), as well as on
the Real Time Trending Data Log (Or History Trending
Data Log).
The following screen command keys are provided:
ZONE #1-30 - Return Air Temperature
ZONE #1-30 – Ammonia
ZONE #1-30 – Humidity
When in Remote Mode (not at the panel), the following key
is provided:
Download Data Trending Files - Pressing this key
initiates a download of the Real Time and History data
files. These files can then be imported into a database
such as Excel™. To use this feature, simply plug a
USB compatible device into the USB port of the
Quantum™ LX. This device can be a USB cable that
is connected directly to a personal computer, or a
USB Flash Drive. When monitoring remotely using a
System Status… Trending… Trending Setup
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 16 OPERATION - SERVICE
personal computer, and this button is selected, a
window will appear on the computer screen, showing
two files:
Realtimexx.csv
Historyxx.csv
The xx in both of these files will be replaced with the
ID number of the Quantum™ LX. When the files
appear in the screen window, simply right click on
either file, and select from the menu “Save Target
As…”, and save the files to a convenient location. By
using Windows Explorer™, you can then double click
on the file, and it will automatically open the file in
Microsoft Excel™.
When using a USB Flash Drive, simply click on the
button, and the files will be saved to the Flash Drive.
You may then take the Flash Drive and plug it into the
USB port of a personal computer. The files may then
be opened from the Flash Drive.
SYSTEM STATUS – Trending - Real Time Trending
ACCESSING:
DESCRIPTION: This is the Real Time Trending screen. This screen will display in a graphical chart format the data values
selected on the Real Time Trending Setup screen. Each of the selected channels will be shown at the bottom of the screen,
each in a different color. The color data values displayed in the chart correspond to the matching color of the trending
channels at the bottom of the screen.
A total of 900 Realtime events can be trended. Realtime
events are lost upon each power cycle. The following are
the possible data channels that may be shown here:
ZONE #1-30 - Return Air Temperature
ZONE #1-30 – Ammonia
ZONE #1-30 – Humidity
System Status… Trending… Real Time Trending
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION – SERVICE Page 17
SYSTEM STATUS – Trending – History Trending
ACCESSING:
DESCRIPTION: This is the History Trending screen. This screen will display in a graphical chart format the data values
selected on the History Trending Setup screen. Each of the selected channels will be shown at the bottom of the screen,
each in a different color. The color data values displayed in the chart correspond to the matching color of the trending
channels at the bottom of the screen.
History trending can save up to 2000 values for each
selected channel. History data is stored in Flash memory.
Flash memory is non-volatile and all information is
retained even if the power to the panel is lost. The interval
at which the data is saved can be adjusted.
The following are the possible data channels that may be
shown here:
ZONE #1-30 - Return Air Temperature
ZONE #1-30 – Ammonia
ZONE #1-30 – Humidity
S
y
stem Status … Trendin
g
Histor
y
Trendin
g
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 18 OPERATION - SERVICE
SYSTEM STATUS - Trending – Real Time Data Log
ACCESSING:
DESCRIPTION: This screen will display in a tabular format, the numerical data values selected on the Real Time
Trending Setup screen. Each trending channel will be listed at the bottom of the screen in a specific color that matches
all data associated with that channel.
The following are the possible data channels that may be
shown here:
ZONE #1-30 - Return Air Temperature
ZONE #1-30 – Ammonia
ZONE #1-30 – Humidity
Up to eight of these data selections may be activated at
any one time. If eight items are selected, and you wish to
view one more, you will first need to de-activate one that is
already chosen first.
S
y
stem Status … Trendin
g
Real Time Data Lo
FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL S90-612 O (MAR 08)
OPERATION – SERVICE Page 19
SYSTEM STATUS - Trending – History Data Log
ACCESSING:
DESCRIPTION: This screen will display in a tabular format, the numerical data values selected on the History Trending
Setup screen. Each trending channel will be listed at the bottom of the screen in a specific color that matches all data
associated with that channel.
The following data channels may be shown here:
ZONE #1-30 - Return Air Temperature
ZONE #1-30 – Ammonia
ZONE #1-30 – Humidity
System Status… Trending… History Data Log
S90-612 O (MAR 08) FRICK® QUANTUM™ LX EVAPORATOR CONTROL PANEL
Page 20 OPERATION - SERVICE
SETPOINTS – Cooling (Mode 1)
ACCESSING:
DESCRIPTION: This screen allows for the setup of the Mode 1 Cooling. In addition to this screen, there is also Mode 2, 3
and 4 Cooling Modes.
Cooling Control Setpoints are used to maintain
temperature. When a zone is cooling, the control
temperature determines whether the liquid valve is open or
closed, based upon the Liquid On and Liquid Off
setpoints. Suction operations are based on the
configuration specified on the Current Zone Configuration
screen. If Suction has been set to Always, then the
Suction valve will remain open at all times, otherwise the
Suction will only open when the Liquid valve is open.
This screen provides setpoint boxes to allow for the
configuration of Cooling Mode 1:
Liquid
Digital Control
On - If the control temperature equals or
exceeds this setpoint, the output for the
liquid valve will be energized or turned on to
open a liquid valve and therefore provide
cooling.
Off - If the control temperature is less than or
equal to this setpoint, the output for the liquid
valve will be de-energized or turned off to
close a liquid valve and therefore prevent
further cooling.
Analog Control
Setpoint – The value that the unit will
attempt to maintain temperature to.
Proportional Band – The temperature
range over which the PID control will be
managing liquid cooling (provided Integration
Time is not set to zero, in which case it will
be strictly proportional). If the Setpoint is 40
degrees and the Proportional Band is 2
degrees, the PI control will set the output to
Liquid Min if the temperature is below 40
degrees (Setpoint). When the temperature is
between 40 and 42 degrees (Setpoint plus
Proportional Band) the PI control will be
increasing the output in a manner to bring
the liquid temperature toward the setpoint).
Above 42 degrees the output will be set to
Liquid Max.
Integration Time – The Integral component
works to push the Control Input toward the
Control Setpoint by tracking the difference
between the Control Input and the Control
Setpoint over time.
Maximum – This is the maximum percent of
the analog output signal.
Minimum – This is the minimum percent of
the analog output signal.
Setpoints… Cooling… Cooling Mode 1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60