Frick AcuAir Quantum LX Operating instructions

Category
Thermostats
Type
Operating instructions
OPERATION – SERVICE
(SESSION LEVEL 2)
FRICK® QUANTUM™ LX
AcuAir®
CONTROL PANEL
Version 3.0x
Form 090-512 O (OCTOBER 2010)
File: SERVICE MANUAL - SECTION 90
Replaces: S90-512 O (MARCH 2008)
Dist: 3, 3a, 3b, 3c
OPERATION - SERVICE
090-512 O (OCT 10)
Page 2
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
Table of Contents
TYPICAL SYSTEM CONFIGURATION ..................................................................................................................... 4
Connecting a Computer Directly to a Panel ....................................................................................................... 4
OVERVIEW OF OPERATOR INTERFACES .............................................................................................................. 5
Web Browser .................................................................................................................................................... 5
Operator Interface Panel (Optional) .................................................................................................................. 7
Operator Access ............................................................................................................................................... 7
To Change Setpoints ......................................................................................................................................... 8
Menu Structure ................................................................................................................................................. 9
Initial Setup Procedure .................................................................................................................................... 10
GRAPHIC SCREENS .............................................................................................................................................. 11
Operating Values .......................................................................................................................................... 11
User Defined Operating Status ................................................................................................................. 12
Operating Status 2 .................................................................................................................................... 13
Desiccant Wheel ....................................................................................................................................... 15
Safeties ....................................................................................................................................................... 16
Current Safeties ........................................................................................................................................ 16
Safety History ........................................................................................................................................... 17
System Status .............................................................................................................................................. 18
Trending ................................................................................................................................................... 18
Trending Setup ................................................................................................................................... 18
Real Time Trending ............................................................................................................................ 19
History Trending ................................................................................................................................. 20
Real Time Data Log ............................................................................................................................ 21
History Data Log ................................................................................................................................. 22
Maintenance ............................................................................................................................................. 23
Event Log.................................................................................................................................................. 24
Setpoints ..................................................................................................................................................... 25
Temperature ............................................................................................................................................. 25
Cooling ............................................................................................................................................... 25
Supply Burner ..................................................................................................................................... 26
Heating ............................................................................................................................................... 12
Pre-Wheel Cooling ............................................................................................................................. 29
Dehumidification ....................................................................................................................................... 31
Desiccant Wheel – Wheel/Regen Fan ................................................................................................. 31
Desiccant Wheel – Regen Burner ....................................................................................................... 32
Supply Fan ................................................................................................................................................ 33
Defrost ..................................................................................................................................................... 35
Defrost Setpoints (Standard and Sequential Hot Gas) ........................................................................ 35
Defrost Setpoints Sequential) ............................................................................................................. 34
Defrost Schedule ................................................................................................................................ 37
Scheduling ................................................................................................................................................ 38
PID Setup
.................................................................................................................................................. 39
Page 1 ................................................................................................................................................ 39
Page 2 ................................................................................................................................................ 41
Communications ....................................................................................................................................... 42
Auxiliaries ................................................................................................................................................. 44
Analog Inputs ..................................................................................................................................... 44
Page 1 .......................................................................................................................................... 44
Page 2 .......................................................................................................................................... 45
Digital Inputs ...................................................................................................................................... 46
Digital Outputs ................................................................................................................................... 47
Panel ........................................................................................................................................................ 48
090-510 O (OCT 10)
Page 3
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
Calibration .................................................................................................................................................... 49
Temperature ............................................................................................................................................. 49
Pressure .................................................................................................................................................... 50
Miscellaneous ........................................................................................................................................... 51
Analog Outputs ......................................................................................................................................... 52
Auxiliaries ................................................................................................................................................. 54
Page 1 ................................................................................................................................................ 54
Page 2 ................................................................................................................................................ 55
Configuration ............................................................................................................................................... 56
Control ...................................................................................................................................................... 56
Page 1 ................................................................................................................................................ 56
Page 2 ................................................................................................................................................ 58
Graphics .................................................................................................................................................... 60
Ethernet .................................................................................................................................................... 61
Security..................................................................................................................................................... 63
Session ........................................................................................................................................................ 64
Service ......................................................................................................................................................... 65
Digital ....................................................................................................................................................... 65
Analog ...................................................................................................................................................... 65
Communications Log ................................................................................................................................. 66
Communications Loop-Back Test.............................................................................................................. 67
Diagnostics ............................................................................................................................................... 68
Software Maintenance .............................................................................................................................. 69
About ........................................................................................................................................................... 70
WARNINGS/SHUTDOWNS MESSAGES ................................................................................................................ 71
The AcuAir® Quantum™ LX has the capability of being modified by the user/owner in order to obtain different performance
characteristics. Any modification to the standard default settings may have a severe negative impact on the operation and
performance of the equipment. Any modification to these control settings is the sole responsibility of the user/owner and
Frick® disclaims any liability for the consequences of these modifications. It is possible that the modification of these settings
will cause improper operation and performance that result in property damage, personal injury or death. It is the responsibility
of the user/owner to evaluate and assess the consequences of their actions prior to modifying the controls for this unit.
Warnin
g
!
090-512 O (OCT 10)
Page 4
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
TYPICAL SYSTEM CONFIGURATION
A typical AcuAir® system may involve as few as one unit,
or nearly an infinite number of units. Each air-handling
unit within the AcuAir® system operates independently of
one another yet they may all be connected via a common
Ethernet connection. The three major parts of a system
include the air-handling unit with controller, an Ethernet
Hub or Switch, and a computer with Web Browser or an
Operator Interface Panel (HMI).
The purpose of the unit controller is of course to provide
control to the mechanics of the Air Handler. Each of these
controllers is connected to a Hub or Switch, and the
Hub/Switch is then connected to the Ethernet (which
allows the computer or HMI to view all units). The
Ethernet cables used in this configuration are all of the
“straight through” or pin-to-pin variety. Refer to the
following pictorial:
CONNECTING A COMPUTER DIRECTLY TO A PANEL
Especially for the purpose of maintenance, if you wish to
connect directly to a single panel from a computer
(desktop or laptop), you can avoid the switch and use a
crossover Cat-5 cable:
With a crossover cable, you can directly connect one
Ethernet device (computer) to the other (Quantum™
panel) without a Switch or Hub.
Refer to the following pictorial and color code table to
construct a crossover cable:
Both Ends of a crossover-cable
CAT-5 Ethernet cable color codes
1 – White w/orange stripe 5 – White w/blue stripe
2 – Orange w/white stripe 6 – Green w/white stripe
3 – White w/green stripe 7 – White w/brown stripe
4 – Blue w/white stripe 8 – Brown w/white stripe
1
2
3
4
5
6
7
8
Left (Not
Crossed)
3
6
1
4
5
2
7
8
Right (Crossed)
Computer or
HMI
Ethernet Hub or
Switch
Air Handler
Controllers
Ethernet
Port
All network cables
are Pin-to-Pin
CAT-5 Cables
Desktop or
laptop
Com
p
uter
Air Handler
Controller
Cross-over
CAT-5
Ethernet
Port
090-510 O (OCT 10)
Page 5
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
OVERVIEW OF OPERATOR INTERFACES
There are two possible methods of viewing and accessing
the user interface. One of these methods is in the form of
a standard Web Browser and the other is an optional
AcuAir® Operator Interface Touch screen.
Web Browser
The web browser interface can be viewed from any
desktop or laptop computer, which has access to the
network that an AcuAir® panel is attached to. To change
screens, setpoints, etc., you simply use a mouse and the
keyboard to view and change data.
All AcuAir® screens that are shown will have a several
buttons on the right hand side of the screen. Most screens
will have three buttons, and one setpoint box. The three
buttons are:
[Menu] – Clicking on this button will cause the main
menu to appear on the left side of the screen.
Clicking a second time will cause the menu to
disappear.
[Start Refresh] [Stop Refresh] – This button(s) appears
immediately below the [Menu] button. This is actually a
toggle button, as it changes function from Start Refresh
to Stop Refresh each time it is clicked on. When the
button shows as Start Refresh, a setpoint box will
appear below it, with a time value displayed. The time
value determines how often the display screen will
refresh, or update its values. This time value is
defaulted to 5 seconds, which means that the display
will update all values shown every 5 seconds.
Depending on the network connection speed, this
updating may interfere with your ability to change data
setpoints, because the screen will refresh while you are
entering the data. To solve this, simply increase the
refresh time. The other alternative is to toggle the
Refresh Button. By pressing [Stop Refresh], screen
refreshing will terminate, and the time setpoint box will
reappear. In this state, the particular screen that you
are viewing will never update the displayed values.
Changing to another screen will show the most recent
values on the new screen, and then will not update
again. So in the Stop Refresh state, screens will only be
updated when new screens are accessed. This feature
should not be used when monitoring for data. Try to
find an acceptable refresh time for the Start Refresh
state.
One screen that DOES NOT have these buttons is:
Software Maintenance
– To leave this screen,
click on [Exit] button. Note: Using the [Exit]
button takes several seconds, and it will force the
password level back to zero.
There are numerous screens that have additional
buttons to those mentioned here. These additional
buttons are self-intuitive, and as such, are not
discussed here.
090-512 O (OCT 10)
Page 6
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
AcuAir® Operator Interface Touch Screen
General Description
This optional user interface has been designed to
allow an operator to efficiently access, control and
monitor the operation of all Frick AcuAir® units from a
single access point, when all units are connected
through a common Ethernet network. The touch
screen control panel is used for graphic displays. By
touching an active area of the display, a data entry
box will appear, allowing the operator to enter
different setpoint values, via a keyboard overlay, that
will appear on the screen. The Operator Interface
panel provides a platform to easily navigate between
all networked control systems, as well as a remote
access point which is reachable from any desktop
web browser. Remote access provides users with the
ability to connect to Frick control systems from both
home and office, or any other location providing
Internet access.
Touch Screen Calibration
When the panel completes it boot sequence, the user
will be presented with a message box which requests
the user to touch the screen to enter calibration
mode. If the user touches the message box before
the 3-second timer expires, the screen will change,
presenting the user with four orange targets. These
targets permit the user to calibrate the touch screen’s
mouse pointer location. If these points are not
properly set, the mouse pointer will not appear where
the user’s finger makes contact with the screen. Once
the screen’s calibration target appear, it is best to use
a dull pointed object to touch each of the four
targets, as a finger makes contact with an area too
large to provide accurate calibration.
Browser and Keyboard
Both the browser and keyboard should appear on the
screen once the panel has finished its startup
sequence. Each panel is equipped with a program
which will restart the keyboard and browser if either
application is closed. The browser has a small icon in
the center of the top tool bar, which permits the user
to return to the panel Home Page at any time. From
the panel Home Page, the Keyboard button can be
used to restart the on-screen keyboard should it
disappear.
The keyboard can be used to enter text into any field
appearing within a web page. To enter text into a
field, simply touch the desired field in the web
browser. If the field is properly selected, a cursor
should appear within the text field. The user can also
drag his/her finger over a segment of text in the field
to “select” it. Any key strokes from the keyboard will
then replace the highlighted text.
If the keyboard fails to transmit characters into the
desired text field, there could be one of two
problems. First, be sure the text field is selected.
Typically the cursor is a good indicator that focus has
shifted to the desired text field. The second problem
involves a keyboard loss of focus. To resolve this
problem, first touch the desired text field, then touch
the [Focus] button on the bottom right-hand corner
of the keyboard, finally touch the desired text field a
second time. After this sequence, characters should
be directed to the correct location. This three-step
sequence should be used whenever the keyboard
appears unresponsive.
Keyboard Overlay
Home Page
The panel Home Page displays all the units accessible
through the Operator Interface Panel. Any configured
units will appear with an icon and a descriptive label.
If an icon is touched, the web browser will be
directed to the Quantum LX control page. To return
090-510 O (OCT 10)
Page 7
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
to the Operator Interface Panel’s Home Page simply
touch the “Home” icon on the browser’s toolbar.
Admin Home Page
The Operator Interface Panel is equipped with the
Admin Home Page to handle various configuration
functions. This area can be accessed by pressing the
Admin button on the panel’s Home Page. As user
name and password are required to access this area
(Username: admin, Password: 2staycold).
Upon entering the admin area, the user will be
presented with the list of all registered units (nothing
will be displayed here if no units are registered). If
any registered units are listed, and Edit button at the
end of each row allows the user to change the
specifications of a specific unit. A row of Admin
buttons across the top of the page allow the user to
add new units, or delete units from the list of
registered units. Each unit must have a unique name
(no two units can have the same name) and an IP
address (the IP address is not required to be unique,
so more than one link can redirect the user to the
same unit). The user can also select the type of unit
which results in an appropriate icon being displayed
on the panel Home Page where all units are listed.
Network Configuration
In the Admin area, the Network Config button can be
selected to modify the Operator Interface Panel’s
network settings. When the page is loaded, the
current network settings are displayed for the user to
view. It is possible to change the IP address, subnet
mask, and default gateway. The IP address type can
be static or dynamic; the later option requires a DHCP
server to be present. Please consult a network
administrator to modify the values correctly. It is also
possible to specify a network name, allowing access
to the Panel from a Windows network.
Finally, the web server port can be changed from the
Network Configuration page. This is traditionally set
to 80 which all web browsers understand to be the
default port. If this is changed to any other value, the
panel can only be reached from an external computer
by appending the port number to the IP address (e.g.
if the Panel’s IP address is 192.168.0.5 and the web
server port is 400, an external web browser will
access the panel through the address:
192.168.0.5:400). If this panel does not need to be
reached from an external computer, then the web
server port setting should be disregarded.
In the event the web server port or IP address
settings are changed, the panel may need to perform
a reboot before these changes take effect. This it will
do automatically, and the user will be notified when
this is about to occur.
Resetting the IP Address
In the rare occurrence that a local Air Handler loses
Ethernet communications with the Web Browser or
Operator Interface Panel, it could be that the unit has
an invalid IP address. One way that this could happen
would be if the unit has just had a program upgrade,
without the setpoints being properly saved then
restored (the IP address is stored as a setpoint to the
flash card).
In order to correct this situation, perform the
following steps:
1. Power down the failing unit.
2. Locate the processor board (located on the
inside of the top door).
3. On the processor board (the larger of the
two boards), locate and temporarily remove
LK12.
4. Power the unit up.
5. Wait for one minute to allow the processor
to fully boot.
6. Power the unit down.
7. Replace LK12.
8. Power back up. The IP address will be
automatically set to 192.168.0.105. This
address is known to work, and should solve
the problem. At this point, the unit should
show up at the Web Browser or Interface
panel (HMI). If the user wishes, they may
now go into the HMI and modify the IP
address for the unit in question to the
number that they need it to be, or they may
leave it alone.
If the above steps fail to bring the unit back into the
network, you should check the Ethernet cables, hub
or switch, Quantum™ control board, etc.
090-512 O (OCT 10)
Page 8
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
OPERATOR ACCESS
Operator access to this system is through various screens.
A screen is the physical representation of data on the
display. Icons have been used to help an operator quickly
identify functions. An icon is a small graphic symbol
representation. Each screen has a title area. The title is
descriptive of the screen. The current date and time is
shown in this title area. The day of the week, Sunday
(Sun.) through Saturday (Sat.) is displayed. The month of
the year from January (Jan.) to December (Dec.) is
displayed. The day of the month from 1 to 31 and the year
from 0001 to 9999 is displayed. The time displayed is the
current time in 24 hours (military) format. The hours,
minutes and seconds are displayed.
Some screens are for informational purposes only, and
cannot be modified. These screens typically show analog
values such as temperature and humidity, which are
strictly functions of an associated sensor, and as such,
cannot be modified. Other screens show setpoint values
that allow the operator to change, in order modify the
units operating characteristics. For easier viewing, related
information is separated into boxes. To further assist the
operator, an on-line help is provided. Sometimes
selections appear differently (a box may be dimmed) to
indicate that the feature is unavailable.
TO CHANGE SETPOINTS
The setpoints define the operation and limits of each air
unit. Adjustable setpoints are setpoints that an operator
can easily change in the field. These setpoints are stored
in EPROM (non-volatile memory).
NOTE: Adjustable Setpoints are not lost after power is
interrupted. However, we suggest that a list of Adjustable
Setpoints be recorded and stored safely to facilitate
reentry, in case there is a need to return to the original
settings.
1. The data entry fields are identified by a black box
with a white interior. The data is shown in black
text. When on a screen that has adjustable
setpoints, select the setpoint box that you wish
to modify (either by touching that box if a touch-
screen or selecting it with a mouse for a web
browser). Once the data field has been selected,
the background turns blue, and the text turns
white.
2. The current value of that setpoint is shown. Use
the keyboard to enter the new value. Typing a
new value will completely erase the old value.
3. Press the keyboard [ENTER] key to input the new
data in the data entry field and to move to the
next data entry field.
4. If the data entered into the setpoint box is valid,
then once you have pressed the keyboard
[ENTER] key, the [SUBMIT] box in the lower left
hand side of the viewing screen will turn from a
grey background, to a red background. Press the
[SUBMIT] button to load the changed setpoint to
the controller.
5. If the value is out of bounds, an error message
box displays the proper range of values. Press
the [OK] button to acknowledge the error
message. Re-enter the correct value.
When finished making any changes to the data on an
adjustable setpoint display press the [SUBMIT] key to
accept all changes.
090-510 O (OCT 10)
Page 9
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
MENU STRUCTURE
The above graphic represents the menu structure, or tree,
of the AcuAir® Quantum™ LX screens. Refer to this tree
when accessing the various screens. Please note that this
screen list is complete and that certain screens may not
be available as shown here, depending upon the enabled
options.
Home
Operating Values…
Safeties…
System Status…
Setpoints…
Calibration …
Configuration…
Session
Service …
Help
About
Page 1
Page 2
Trending …
Maintenance
Event Log
User Defined
Operating Status 2
Defrost
Desiccant Wheel
Current
History
Temperature …
Dehumidification …
Supply Air Flow
Defrost …
Scheduling
PID Setup …
Communications
Auxiliaries …
Panel
Temperature
Pressure
Miscellaneous
Analog Outputs
Auxiliaries …
Control …
Graphics
Internet
Security
Digital
Analog
Communications Log
Communications Loop Back Test
Diagnostics
Software Maintenance
Page 1
Page 2
Trending Setup
Real Time Trending
History Trending
Real Time Data Log
History Data Log
Cooling
Supply Burner
Heating
Pre-Wheel Cooling
Page 1
Page 2
Defrost Setpoints
Defrost Schedule
Page 1
Page 2
Analog Inputs …
Digital Inputs
Digital Outputs
Su
pp
l
y
Air Fan
Wheel / Regen Fan
Regen Burner
Desiccant Wheel …
090-512 O (OCT 10)
Page 10
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
INITIAL SETUP PROCEDURE
The following is a basic guide to unit setup.
1.
Configuration
is performed first. Although there
are four different
Configuration
screens, only the
Control Configuration
needs to be setup for unit
operation.
To gain access to
Control Configuration
, login to
User Level 2. The following items are setup on
the two
Control
C
onfiguration
pages:
Mode Configuration
Control Temperature
Control Source
Supply Burner
Heating
Dehumidification
Damper
Exhaust
Exhaust Control
Exhaust Fan Run Warning
Supply Fan
Room Pressure
Pre-Coil Override
Discharge Temperature
Desiccant Heat Source
Defrost
Defrost Initiation
Air Defrost
Smoke Detector – Enables or Disables
the input for a Smoke Detector. For fail-
safe operation, this input is energized
when there is no problem and de-
energized on a fault such as a fire.
Cooling – Used for temperature control.
The liquid valve is open because the
control temperature equals or exceeds
the liquid on setpoint. If the suction
valve is not a modulating valve, it is
open during cooling. During cooling, a
modulating valve regulates the suction
valve based on its setpoints.
Pre-Wheel Cooling
2.
Setpoints
are established next. Each unit must be
setup to the customer specific control features
and options to be used by a unit controller board.
This setup should not need to be changed by
operators. Setpoints are intended to be accessed
and modified only by a Factory Representative or
Distributor. Only those setpoints that will be
utilized for unit operation need be set. The
following is the list of available setpoint screens:
Temperature
Cooling
Supply Burner
Heating
Pre-Wheel Cooling
Dehumidification
Desiccant Wheel
Wheel / Regen Fan
Regen Burner
Supply Air Flow
Supply Fan
Defrost
Defrost Setpoints
Defrost Schedule
Scheduling
PID Setup
Page 1
Page 2
Communications
Auxiliaries
Analog Inputs
Page 1
Page 2
Digital Inputs
Digital Outputs
Panel
3. Calibrate the control devices. Each sensor or
transducer that is utilized by the unit must have
its operating characteristics defined. This is
where the controller is told what each devices
high and low operating ranges are, as well as
offsets. The offsets are used to fine tune the
device with reference to a known external
calibration device:
Temperature
Pressure
Miscellaneous
Auxiliaries
Analog Outputs
4. From Security Setup, establish the desired access
rights of the operators.
The panel now provides quick access to the most
important information and controls of the units and their
subsystems.
090-510 O (OCT 10)
Page 11
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
GRAPHIC SCREENS
OPERATING STATUS
The most important information about the unit is
displayed. In the middle of the screen is a diagram of an
AcuAir® air handling unit that shows the current state of
the unit. The graphic simulation shown on the screen will
vary depending upon the installed options. The following
items may be shown:
The supply fan and both exhaust fans spin.
A flame is displayed when the burner is on.
The cooling coils are colored blue when they are
on, white when they are off and red when in
defrost.
The following information is shown on this screen:
DATE - The actual date will be displayed in this box.
The date must first be set correctly on the
Configuration
screen. Once set, the date will be
automatically adjusted for at the end of each month,
much like the calendar feature of most modern
watches. The primary use of the date feature is to
provide a date stamp for Warnings and Shutdowns.
Refer to the section entitled
Setting the Date and
Time
for further information.
TIME - The actual time will be displayed in this box.
The time must first be set correctly on the
Configuration
screen. The time will also need to be
adjusted for those locations which observe Daylight
Savings Time. The primary use of the time feature is
to provide a time stamp for Warnings and Shutdowns.
Refer to the section entitled
Setting the Date and
Time
for further information.
SCREEN TITLE - This is the title for the screen that is
showing. Each screen will have a title. The
Quantum™ LX manuals will extensively refer to
screens by these names. When referred to in these
manuals, screen names will be shown in bold italic
print, such as
Operating Status
.
MODE OF OPERATION – The current mode of the
unit, either Cleanup or Process.
Process 1 and Process 2 – The unit is
maintaining optimum air conditions for
processing product.
Cleanup - The unit is modifying air
conditions to support the cleanup procedure.
PROCESS ROOM READINGS – Values related to
current mode will be shown here:
Room Air Temperature
Room Air Humidity
Room Pressure
STATUS BOX
Off – The unit is neither running nor is
starting.
Running – The unit is in a normal run
condition, air flow has been detected.
Starting - The unit has turned on but air flow
has not been detected.
SETPOINT VALUE - This is the setpoint maintained by
the control.
ACTUAL VALUE - The actual reading of the
temperature that was chosen as the control input.
ID - The number that has been assigned to this
particular unit on the
Communications Setup
screen.
RUN HOURS – The total number of hours that the Air
Handler has run since the unit was installed.
Screen Title
Analog
Readings
Time
Graphic
Simulation
Date
Process Room
Readings
Panel ID of the
unit being
displayed
Status Box
Unit
Run Time
Mode of
Operation
Setpoint
Value
Actual
Value
090-512 O (OCT 10)
Page 12
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
ALARM MESSAGE - Warnings and Shutdown
messages are displayed in the lower left corner of the
screen. This area will be blank if there are no current
Warnings or Shutdowns.
ANALOG READINGS BOX
-
The following analog input
readings are possible. They are shown if they were
enabled during setup:
Outside Air Temperature
Discharge Air Temperature
Outdoor Air Damper
USER DEFINED OPERATING STATUS
ACCESSING:
DESCRIPTION: The purpose of this screen is to allow the user to assign additional analog channels to be more readily
viewable. Since the main
Operating Status
(Home) screen is capable of only showing a limited number of pre-assigned
analog values, it may be desirable for the user to have a method of viewing additional information that they can select, on
a common screen. They may even select values that are already being displayed on the
Operating Status
screen, as well
as values that are not shown there.
This screen is provided to allow the user to view up to 20
different analog channels of their choosing.
As an example of how this screen works, assume that in
addition to the data that is shown on the
Operating Status
screen, the user would like to monitor the
Outside Air
Temperature, Room Air Humidity
and
Pre-coil Air
Temperature,
all on the same screen (this one). Notice that
Outside Air Temperature
and
Room Air Humidity
are already
shown on the
Operating Status
(Home) screen, but the
Pre-
coil Air Temperature
is shown on the
Operating Status 2
screen. In order to set this screen up to show these three
values, the user would highlight the Enable User Defined
Channel 1 (or whatever channel they wish to use), by
selecting it with the mouse. Once the box is highlighted, click
on it to cause the possible settings for the channel to appear.
Use the mouse to scroll through the list. When the selection
that you want to use has been highlighted, click on it to
select it. Once selected, a value will appear to the right of
the list, which corresponds to the analog value for that
channel.
The following selections may be shown on this screen:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Differential Pressure
Outside Air Damper
Coil Temperature 1- 4
Pre-Wheel Regen Air Temperature
Post-Wheel Regen Air Temperature
Wheel Differential Pressure Switch
Auxiliary Analog 1 - 20
None
Operating Values… User Defined
090-510 O (OCT 10)
Page 13
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
OPERATING VALUES – OPERATING STATUS 2
ACCESSING:
DESCRIPTION: The
Operating Status 2
screen shows additional unit information.
The
Operating Status 2
, displays additional information
that cannot be shown on the first
Operating Status
screen. Along the sides of the page are labels identifying
the various areas of the screen.
The following information is shown on this screen:
DATE - The actual date will be displayed in this box.
The date must first be set correctly on the
Configuration
screen. Once set, the date will be
automatically adjusted for at the end of each month,
much like the calendar feature of most modern
watches. The primary use of the date feature is to
provide a date stamp for Warnings and Shutdowns.
TIME - The actual time will be displayed in this box.
The time must first be set correctly on the
Configuration
screen. The time will also need to be
adjusted for those locations which observe Daylight
Savings Time. The primary use of the time feature is
to provide a time stamp for Warnings and Shutdowns.
SCREEN TITLE - This is the title for the screen that is
showing. Each screen will have a title. The
Quantum™ LX manuals will extensively refer to
screens by these names. When referred to in these
manuals, screen names will be shown in bold italic
print, such as
Operating Status
.
ID - The number that has been assigned to this
particular unit on the
Communications Setup
screen.
RUN HOURS – The total number of hours that the Air
Handler has run since the unit was installed.
WARNING/SHUTDOWN STATUS BOX - The
Warning/Shutdown Status is displayed below the
Mode of Operation
status box. This status box is blank
with no message if there are no warnings or
shutdowns present.
If a Warning or Shutdown occurs, a message will be
shown, identifying the type of warning or shutdown. The
definitions for the two types of messages are as follows:
WARNING - A specific warning message will be
shown when a warning is present. A warning is a
condition that requires operator acknowledgement
but allows the Unit to continue to run if it is already
running. A Warning message indicates that a
warning setpoint has been reached, or exceeded.
SHUTDOWN - This specific shutdown message will
be shown when a shutdown is present. A shutdown
is a condition that requires an operator to
acknowledge, and causes the Unit to shut down. A
Shutdown message indicates that a shutdown
setpoint has been reached, or exceeded.
To clear a Warning or Shutdown, the operator must
access the
Current Safeties
screen, and acknowledge
the Warnings/Shutdowns by pressing the [Clear
Safeties] button. If the conditions that originally
caused the Warning or Shutdown have not been
corrected, the Warning or Shutdown will continue to
re-occur until the problem has been identified and
corrected.
Operating Values… Operating Status 2
Temperature
Readings
Screen Title
Additional
Analog
Readings
I/O
Status Box
Time
Run Status Box
Run Time
Date
Setpoint
Value
Mode of
Operation
Panel ID
Actual
Value
Warning /
Shutdown
Status
090-512 O (OCT 10)
Page 14
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
I/O STATUS BOX
-
The present operating status of the
digital I/O is shown. One of the following messages is
displayed:
On – The channel is energized or turned on.
Off - The channel is de-energized or turned off.
The following inputs are shown in the first block (if they
were enabled during setup).
Supply Fan Motor
Supply Air Flow Switch
Exhaust Fan #1
Exhaust Fan #2
Unit High Pressure
Cooling Stage #1
Cooling Stage #2
Cooling Stage #3
Cooling Stage #4
Heating
Supply Burner
Supply Burner Status
Supply Flame Failure
Supply Burner Safeties
Smoke Detector
Remote Start/Stop
Remote Process/Cleanup
Remote Process 1/Process 2
090-510 O (OCT 10)
Page 15
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
OPERATING VALUES – DESICCANT WHEEL
ACCESSING:
DESCRIPTION: The
Desiccant Wheel
screen shows information relating to operation of the Desiccant Wheel.
This screen is for informational purposes only. There are
no setpoints or data to be modified from here, only
viewed.
The status of the following conditions can be viewed here:
Desiccant Wheel
Active
Status
Input
Time
Regen Fan Status
On
Off
Regen Burner
Status
Control Input
Burner Output
Command
Room Air Humidity
Command
Input
Setpoint
Pre-Wheel Regen Air Temperature
Command
Input
Setpoint
Post-Wheel Regen Air Temperature
Command
Input
Setpoint
Operating Values… Desiccant Wheel
090-512 O (OCT 10)
Page 16
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
SAFETIES -
Current Safeties
ACCESSING:
DESCRIPTION: The
Current Safeties
screen shows the Warnings and Shutdowns that have recently occurred (up to 50).
When a warning or shutdown is triggered, a blue descriptive message shows on this screen. The date and time of the
warning or shutdown occurrence is shown to the right of its description. The most recent message will appear on the top
line of the screen with the oldest appearing at the bottom. When a Warning or Shutdown is logged to this screen, it will
also be logged to the
Safety History
screen.
The following
Current Safeties
screen key is provided:
[Clear Safeties] - Selecting this key will clear all
warnings and/or shutdowns from this screen. This will
also place a date/time stamp for the corresponding
entry on the
Safety History
screen showing that the
particular Warning or Shutdown was cleared. Clearing
the entry on the
Current Safeties
screen, will not
clear it from the
Safety History
screen.
To resume normal operation it will be necessary to go
through the following steps:
1. Correct the condition(s) causing the warning.
2. Press the [ALARM SILENCE] key. (This action may
precede correcting the condition(s) causing the
warning). Or, go to step 3.
3. To clear or reset the
Warnings/Shutdowns
screen and turn off any warning annunciation
device, from the screen, press the [Clear
Safeties] key. This will also clear the WARNING
or
SHUTDOWN
message from the
Operating
Status
screen.
4. If the conditions causing the warning have not
been corrected or a new fault has occurred, a
new
WARNING
or
SHUTDOWN
message will
appear. The
Safety History
screen keeps a record
of the warnings and shutdowns. This information
will help troubleshoot persistent operational
problems.
Refer to the
Warnings/Shutdowns Message
section for a
list of all the possible conditions.
Safeties… Current
090-510 O (OCT 10)
Page 17
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
SAFETIES - Safety History
ACCESSING:
DESCRIPTION: The
Safety History
screen shows the warnings and shutdowns that have recently occurred (up to 50
maximum). When a warning or shutdown is triggered, a blue descriptive message shows on this screen. The date and
time of the warning or shutdown occurrence is shown to the right of its description, followed by the date and time that
the safety was cleared. The most recent message will appear on the top line of the screen with the oldest appearing at
the bottom.
It is possible to view the conditions that existed on the
Operating Status
screen at the exact moment that a
condition occurred.
Use the mouse to select (highlight) a
warning or shutdown and then click on it to view its
associated
Freeze
(
Operating Status
) screen.
Freeze Screen Description
This
Freeze
screen provides a snapshot of the values
that were current at the time of the latest shutdown.
The information on the
Freeze
screen can help the
user to identify the cause of a fault, which occurred
when no one was present. The
Freeze
screen freezes
the information of the
Operating Status
screen AT
THE MOMENT OF A AIR HANDLER WARNING OR
SHUTDOWN. The Freeze screen has the same
appearance and contains the same information as the
Operating Status
screen. (For a description of the
information presented by the
Freeze
screen, refer to
the
Operating Status
screen). The
Freeze
screen will
retain the information generated by a warning or
shutdown. The last fifty warnings/shutdowns
Freeze
screens are saved. This data is saved during a power
outage.
Safeties… History
090-512 O (OCT 10)
Page 18
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
SYSTEM STATUS - Trending -
Trending Setup
ACCESSING:
DESCRIPTION: This is the Trending Setup screen. Up to eight channels can be monitored in real time trending, and up to
eight channels monitored in history trending.
Real Time Trending - is a method by which the user can
set the Quantum™ LX to map real-time events to a
graphic chart format. Using this feature allows for a live
snap-shot of recent unit process characteristics, such as
temperature, pressure and humidity readings. The events
that occur will scroll across the screen from left to right,
at a speed that is determined by the recording interval.
Real Time trending information is also stored to a log file,
which provides a time/date stamp for each of the selected
channels, as well as the value of the reading for that
channel. This log file can be viewed on the
Real Time Data
Log
screen. Trending data is lost upon power cycle.
The following setpoints are provided:
Real Time Recording Interval – The time interval that
defines how often the real time trending data values
are updated. This value may be set for any time
duration between 1.0 second and 86,400.0 seconds
(24 hours).
History Trending - is a method by which the user can set
the Quantum™ LX to record historical events to a graphic
chart format. This feature is similar to Real Time trending,
except that the data points can be set separately, the rate
at which the graphic chart is updated can be set to a
different rate, and the data is not lost at power cycle.
Using this feature allows for the recording of recent event
characteristics, such as temperature, pressure and
humidity readings. The events that occur will scroll across
the screen, at a speed that is determined by the recording
interval.
History Recording Interval – The time interval that
defines how often the history trending data values are
updated. This value may be set for any time duration
between 1.0 minute and 60.0 minutes (1 hour).
To program this screen with the data you wish to trend,
highlight the Enable Real Time Trend Channel 1 (or
whatever channel you wish to use), by selecting it with
the mouse. Once the box has been selected, a drop down
menu will appear for that channel. On the right hand side
of the drop down box will be an arrow. Selecting the
arrow will to cause all the possible settings for the channel
to appear. Use the mouse to scroll through the list. When
the selection that you want to use appears, click on it to
select it. Once selected, the value for this channel will be
automatically trended and shown on the Real Time
Trending graph (or History Trending Graph), as well as on
the Real Time Trending Data Log (Or History Trending
Data Log).
The following screen command keys are provided:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1-20
None
When in Remote Mode (not at the panel), the following
key is provided:
System Status… Trending… Trending Setup
090-510 O (OCT 10)
Page 19
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
Download Data Trending Files – Clicking on this
button initiates a downloading of the Real Time and
History data files from the Quantum™ LX to the
remote computer (the computer that you are
monitoring from). These files can then be imported
into a database such as Excel™.
A window will appear on the computer screen,
showing two files:
Realtimexx.csv
Historyxx.csv
The xx in both of these files will be replaced with the
ID number of the Quantum™ LX. When the files
appear in the screen window, simply right click on
either file, and select from the menu “Save Target
As…”, and save the files to a convenient location. By
using Windows Internet Explorer™, you can then
double click on the file, and it will automatically open
the file in Microsoft Excel™. The data can then be
used in whatever way the user would like.
SYSTEM STATUS - Trending – Real Time Trending
ACCESSING:
DESCRIPTION: This is the
Real Time Trending
screen. This screen will display in a graphical chart format the data values as
selected on the Real Time Trending Setup screen. Each of the possible eight selectable channels will be shown at the
bottom of the screen, each in a different color. The color data values displayed in the chart correspond to the matching
color of the trending channels at the bottom of the screen. A total of 900 Realtime events can be trended. Realtime events
are lost upon each power cycle.
The following are the possible data channels that may be
shown here:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1-20
None
System Status… Trending… Real Time Trending
090-512 O (OCT 10)
Page 20
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL
OPERATION - SERVICE
SYSTEM STATUS - Trending – History Trending
ACCESSING:
DESCRIPTION: This is the
History Trending
screen. This screen will display in a graphical chart format the data values as
selected on the
History Trending Setup
screen. Each of the possible eight selectable channels will be shown at the
bottom of the screen, each in a different color. The color data values displayed in the chart correspond to the matching
color of the trending channels at the bottom of the screen.
History trending can save up to 2000 values for each
selected channel. History data is stored in Flash memory.
Flash memory is non-volatile and all information is
retained even if the power to the panel is lost. The
interval at which the data is saved can be adjusted.
The following are the possible data channels that may be
shown here:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1-20
None
System Status … Trending … History Trending
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76