15
®
Ignition, pilot valve, main valves, vent, and auxiliary relay outputs:
If using proof of closure switches for either fuel valve, ensure they are wired
to the relevant auxiliary inputs and the corresponding option parameter is set
accordingly (refer to option parameter 10.1 -10.9).
Fuses not exceeding 4A must protect all relay outputs. Using a fuse in the
unit supply of 4A or where the total current exceeds 4A, use a separate
fuse on each relay output to achieve this. (See cautionary note in Burner
select input).
These outputs must be connected using multi-strand single conductor PVC
insulated 16, 18, 20AWG, 600V 90°C (16/0.2mm) wire. Wiring must comply
with all applicable codes, ordinances and regulations and, where required, must comply to NEC
Class 1 (Line Voltage) wiring. In most cases, the outputs can be connected directly to the ignition
transformer, alarm device and valves without the use of external relays.
It is recommended that the ignition transformer should be mounted as far away from the con-
trol unit as possible.
Ensure all connections to the ignition transformer are as short as possible and where possible, do not
run adjacent to any other wiring and that the ignition transformer earth connection is made to the
panel earth and not the wiring base earth.
Alarm Relays:
Alarm relays are shown with NO power to Terminal PB5. When power
is applied to Terminal PB5, the alarm relays will change state. In the
event of a limit fault or forced alarm, alarm
relay 1 will go OFF, connecting alarm 1 COM (PC3) to alarm 1 N/C
(PC1). In the event of a safety shutdown, alarm relay 2 will go OFF,
connecting alarm 2 COM (PC6) to alarm 2 N/C (PC5).
These outputs must be connected using multi-strand single conductor
PVC insulated 16, 18, 20AWG, 600V 90°C (16/0.2mm) wire
Burner select (ON/OFF-LIMITS) input:
WARNING: Any external limit device must be connected into the burner select (ON/OFF-
LIMITS) line, unless connected into the auxiliary inputs and the correct function selected.
• If a limit device is utilized in the burner select (ON/OFF-LIMITS) line, it must be capable
of supplying the total current required by the main and pilot valves.
• Any limit device connected to this unit must be listed or component recognized by authorities
who have jurisdiction for the specific purpose for which they are used.
• Wiring must comply with all applicable codes, ordinances and regulations.
• Wiring, where required, must comply with NEC Class 1 (Line Voltage) wiring.
This input should be connected to the burner select
switch and/or external limit circuit using multi-strand
single conductor PVC insulated 16, 18, 20 AWG 600V,
90°C (16/0.2mm) wire. Wiring must comply with all
applicable codes, ordinances and regulations and where
required must comply to NEC Class 1 (Line Voltage)
wiring.
The device connected to this input must be capable of supplying the current required by the
main and pilot valves and fused up to a maximum of 6A. If a fuse greater than 4A is used, each
fuel valve output MUST be separately fused at 4A maximum, to protect the relay contacts
from ‘welding’.
IGNITION PB 6
GAS VALVE 1 PB 9
OIL VALVE PB 11
VENT VALVE PB 13
AUX RELAY PB 14
PILOT VALVE PB 8
GAS VALVE 2 PB 10
ALARM 1 N/O PC 1
ALARM 1 N/C PC 2
ALARM 1 COM PC 3
ALARM 2 N/O PC 4
ALARM 2 N/C PC 5
ALARM 2 COM PC 6
MAX 6A LIVE
BURNER
SELECT PB 7