Hirschmann RSP 20/25/30/35 User manual

Type
User manual
Installation RSP20/25/30/35
Release
16
12/2019
Technical support
https://hirschmann-support.belden.com
User Manual
Installation
Industrial Ethernet Rail Switch Power
RSP20/25/30/35
03.12.2019
Installation RSP20/25/30/35
Release
16
12/2019
The naming of copyrighted trademarks in this manual, even when not specially indicated, should
not be taken to mean that these names may be considered as free in the sense of the trademark
and tradename protection law and hence that they may be freely used by anyone.
© 2019 Hirschmann Automation and Control GmbH
Manuals and software are protected by copyright. All rights reserved. The copying, reproduction,
translation, conversion into any electronic medium or machine scannable form is not permitted,
either in whole or in part. An exception is the preparation of a backup copy of the software for
your own use.
The performance features described here are binding only if they have been expressly agreed
when the contract was made. This document was produced by Hirschmann Automation and
Control GmbH according to the best of the company's knowledge. Hirschmann reserves the right
to change the contents of this document without prior notice. Hirschmann can give no guarantee
in respect of the correctness or accuracy of the information in this document.
Hirschmann can accept no responsibility for damages, resulting from the use of the network
components or the associated operating software. In addition, we refer to the conditions of use
specified in the license contract.
You can get the latest version of this manual on the Internet at the Hirschmann product site
(www.hirschmann.com).
Hirschmann Automation and Control GmbH
Stuttgarter Str. 45-51
72654 Neckartenzlingen
Germany
Installation RSP20/25/30/35
Release
16
12/2019
3
Contents
Safety instructions 5
About this manual 17
Key 18
1 Description 19
1.1 General description 19
1.2 Device name and product code 20
1.3 Device views 23
1.3.1 Front view 23
1.3.2 Rear view 24
1.4 Power supply 24
1.4.1 Supply voltage with the characteristic value K9 24
1.4.2 Supply voltage with the characteristic value KK 24
1.4.3 Supply voltage with the characteristic value TT 25
1.4.4 Supply voltage with the characteristic value CC 25
1.5 Ethernet ports 25
1.5.1 10/100 Mbit/s twisted pair port 25
1.5.2 100/1000 Mbit/s twisted pair port (optional) 26
1.5.3 100 Mbit/s F/O port 26
1.5.4 100/1000 Mbit/s F/O port (optional) 26
1.6 Display elements 27
1.6.1 Device state 27
1.6.2 Port status 28
1.7 Management interfaces 29
1.7.1 V.24 interface (external management) 29
1.7.2 SD card interface 29
1.8 Signal contact 30
2 Installation 31
2.1 Checking the package contents 31
2.2 Installing the SD card (optional) 31
2.3 Installing and grounding the device 32
4
Installation RSP20/25/30/35
Release
16
12/2019
2.3.1 Installing the device onto the DIN rail 32
2.3.2 Grounding the device 33
2.4 Installing an SFP transceiver (optional) 33
2.5 Connecting the terminal blocks 34
2.5.1 Supply voltage with the characteristic value K9 34
2.5.2 Supply voltage with the characteristic value KK 36
2.5.3 Supply voltage with the characteristic value TT 37
2.5.4 Supply voltage with the characteristic value CC 38
2.5.5 Signal contact 39
2.6 Operating the device 40
2.7 Connecting data cables 40
2.8 Filling out the inscription label 40
3 Making basic settings 41
4 Upgrading Software 42
5 Monitoring the ambient air temperature 43
6 Maintenance and service 44
7Disassembly 45
7.1 Removing the device 45
7.2 Removing an SFP transceiver (optional) 46
8 Technical data 47
8.1 General technical data 47
8.2 Dimension drawings 51
8.3 EMC and immunity 52
8.4 Network range 54
8.5 Power consumption/power output 58
8.6 Scope of delivery, order numbers and accessories 58
9 Underlying technical standards 61
A Further support 62
Installation RSP20/25/30/35
Release
16
12/2019
5
Safety instructions
General safety instructions
You operate this device with electricity. Improper usage of the device
entails the risk of physical injury or significant property damage. The
proper and safe operation of this device depends on proper handling
during transportation, proper storage and installation, and careful
operation and maintenance procedures.
Before connecting any cable, read this document, and the safety
instructions and warnings.
Operate the device with undamaged components exclusively.
The device is free of any service components. In case of a damaged
or malfunctioning device, turn off the supply voltage and return the
device to Hirschmann for inspection.
Certified usage
Use the product only for the application cases described in the
Hirschmann product information, including this manual.
Operate the product only according to the technical specifications.
See “Technical data” on page 47.
Connect to the product only components suitable for the requirements
of the specific application case.
Installation site requirements
Install the device in a fire enclosure according to EN 60950-1.
Only for device variants featuring supply voltage with characteristic
value K9 or KK:
Install this device solely in a switch cabinet or in an operating site with
restricted access, to which maintenance staff have exclusive access.
Install the device at ambient temperatures greater than +113 °F
(+45 °C) in “restricted access locations” based on EN 60950-1
exclusively.
WARNING
UNCONTROLLED MACHINE ACTIONS
To avoid uncontrolled machine actions caused by data loss, configure all
the data transmission devices individually.
Before you start any machine which is controlled via data transmission, be
sure to complete the configuration of all data transmission devices.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
6
Installation RSP20/25/30/35
Release
16
12/2019
Device casing
Only technicians authorized by the manufacturer are permitted to open
the casing.
Never insert pointed objects (narrow screwdrivers, wires, etc.) into the
device or into the connection terminals for electric conductors. Do not
touch the connection terminals.
Keep the ventilation slits free to ensure good air circulation.
Mount the device in the vertical position.
At ambient air temperatures > 140 °F (+60 °C):
The surfaces of the device housing may become hot. Avoid touching
the device while it is operating.
Qualification requirements for personnel
Only allow qualified personnel to work on the device.
Qualified personnel have the following characteristics:
Qualified personnel are properly trained. Training as well as practical
knowledge and experience make up their qualifications. This is the
prerequisite for grounding and labeling circuits, devices, and systems
in accordance with current standards in safety technology.
Qualified personnel are aware of the dangers that exist in their work.
Qualified personnel are familiar with appropriate measures against
these hazards in order to reduce the risk for themselves and others.
Qualified personnel receive training on a regular basis.
National and international safety regulations
Verify that the electrical installation meets local or nationally applicable
safety regulations.
Grounding the device
Grounding the device is by means of a separate ground connection on the
device.
Ground the device before connecting any other cables.
Disconnect the grounding only after disconnecting all other cables.
Ground the device via the ground screw.
Shielding ground
The overall shield of a connected shielded twisted pair cable is connected
to the grounding connector on the front panel as a conductor.
Beware of possible short circuits when connecting a cable section with
conductive shielding braiding.
Requirements for connecting electrical wires
Before connecting the electrical wires, always verify that the
requirements listed are complied with.
Installation RSP20/25/30/35
Release
16
12/2019
7
Requirements for connecting the signal contact
Requirements for connecting the supply voltage
All of the following requirements are complied with:
The electrical wires are voltage-free.
The cables used are permitted for the temperature range of the application case.
Table 1: Requirements for connecting electrical wires
All of the following requirements are complied with:
The voltage connected complies with the requirements for a safety extra-low voltage
(SELV) as per IEC/EN 60950-1.
The connected voltage is limited by a current limitation device or a fuse.
Observe the electrical threshold values for the signal contact.
See “General technical data” on page 47.
Table 2: Requirements for connecting the signal contact
Device variant Requirements
All variants All of the following requirements are complied with:
The supply voltage corresponds to the voltage specified on the type
plate of the device.
The power supply conforms to overvoltage category I or II.
The power supply has an easily accessible disconnecting device (for
example a switch or a plug). This disconnecting device is clearly
identified. So in the case of an emergency, it is clear which
disconnecting device belongs to which power supply cable.
The cross-section of the ground conductor is the same size as or
bigger than the cross-section of the power supply cables.
Relevant for North America:
The power supply cables are suitable for ambient air temperatures of
at least 167 °F (75 °C). The power supply cable wires are made of
copper.
Table 3: Requirements for connecting the supply voltage
8
Installation RSP20/25/30/35
Release
16
12/2019
Only for device
variants featuring
supply voltage with
the characteristic
value CC:
If you connect 2 independent power sources, verify that the minus
terminal is grounded. Failure to follow this instruction can result in
equipment damage.
The wire diameter of the power supply cable is at least 0.75 mm² (North
America: AWG18) on the supply voltage input.
The following requirements are alternatively complied with:
Alternative 1 The power supply complies with the requirements
for a limited power source (LPS) as per EN 60950-1.
Alternative 2 Relevant for North America:
The power supply complies with the requirements
according to NEC Class 2.
Alternative 3 All of the following requirements are complied with:
The power supply complies with the
requirements for a safety extra-low voltage
(SELV) as per IEC/EN 60950-1.
A fuse suitable for DC voltage is located in the
plus conductor of the power supply.
The minus conductor is on ground potential.
Otherwise, a fuse is also located in the minus
conductor.
Regarding the properties of this fuse:
See “General technical data” on page 47.
Device variant Requirements
Table 3: Requirements for connecting the supply voltage
Installation RSP20/25/30/35
Release
16
12/2019
9
Supply voltage
The supply voltage is connected to the device casing through protective
elements exclusively.
For supply voltage connections with protective conductor connection:
First connect the protective conductor before connecting the wires for
the supply voltage.
Only device variants
featuring supply
voltage with
characteristic value
TT:
If you connect 2 independent power sources, verify that the minus
terminal is grounded. Failure to follow this instruction can result in
equipment damage.
The wire diameter of the power supply cable is at least 0.75 mm² (North
America: AWG18) on the supply voltage input.
The following requirements are alternatively complied with:
Alternative 1 The power supply complies with the requirements
for a limited power source (LPS) as per EN 60950-1.
Alternative 2 All of the following requirements are complied with:
The power supply complies with the
requirements for a safety extra-low voltage
(SELV) as per IEC/EN 60950-1.
A fuse suitable for DC voltage is located in the
plus conductor of the power supply.
The minus conductor is on ground potential.
Otherwise, a fuse is also located in the minus
conductor.
Regarding the properties of this fuse:
See “General technical data” on page 47.
Alternative 3 Relevant for North America:
The power supply complies with the requirements
according to NEC Class 2.
Only for device
variants featuring
supply voltage with
characteristic
value K9 or KK:
All of the following requirements are complied with:
Supply with DC voltage:
A fuse suitable for DC voltage is located in the plus conductor of the
power supply.
The minus conductor is on ground potential. Otherwise, a fuse is also
located in the minus conductor.
Regarding the properties of this fuse:
See “General technical data” on page 47.
The wire diameter of the power supply cable is at least 1 mm² (North
America: AWG16) on the supply voltage input.
Supply with AC voltage:
A fuse is located in the outer conductor of the power supply.
The neutral conductor is on ground potential at both voltage inputs.
Otherwise, a fuse is also located in the neutral conductor.
Regarding the properties of this fuse:
See “General technical data” on page 47.
The wire diameter of the power supply cable is at least 0.75 mm²
(North America: AWG18) on the supply voltage input.
Device variant Requirements
Table 3: Requirements for connecting the supply voltage
10
Installation RSP20/25/30/35
Release
16
12/2019
ATEX directive 2014/34/EU – specific regulations for safe
operation
Relevant for RSP devices when operating in explosive gas atmospheres
according to ATEX directive 2014/34/EU, the following applies:
List of standards:
EN 60079-0:2012, A11:2013
EN 60079-15:2010
Certificate No.: DEKRA 15ATEX0017X
Use only device variants featuring supply voltage with characteristic
value CC.
Make sure that the device has the following label:
II 3G Ex nA IIC T4 Gc DEKRA 15ATEX0017X
Ambient rating and temperature code for RSP types:
T4: 0 °C Ta +60 °C for “S” types or
T4: 40 °C Ta +70 °C for “T” or “E” types
The modules shall be installed in a suitable enclosure in accordance
with IEC 60079-15 providing a degree of protection of at least IP54
according to IEC 60529, taking into account the environmental
conditions under which the equipment will be used.
When the temperature under rated conditions exceeds 158 °F (70 °C)
at the cable or conduit entry point, or 176 °F (80 °C) at the branching
point of the conductors, the temperature specification of the selected
cable and cable entries shall be in compliance with the actual
measured temperature values.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
The USB port shall remain disconnected.
Installation RSP20/25/30/35
Release
16
12/2019
11
Relevant for use in explosion hazard areas (Hazardous
Locations, Class I, Division 2):
The relay connections are to be installed and used within their Entity
Parameters as per Control Drawing 000189237DNR.
Avertissement - Risque d'explosion - Ne pas débrancher tant que le
circuit est sous tension à moins que l'emplacement soit connu pour ne
contenir aucune concentration de gaz inflammable.
Avertissement - Risque d'explosion - La substitution de tout composant
peut rendre ce matériel incompatible pour une utilisation en classe I,
division 2.
12
Installation RSP20/25/30/35
Release
16
12/2019
Control Drawing for RSP devices according to Class I Division 2 Hazardous Locations
Rev.: 0 Document No.: 000189237DNR Page 1/2
For Use in Hazardous Locations Class I Division 2 Groups A, B, C, D:
Only allowed for RSP 20/25/30/35 model No´s. which are individually labeled
“FOR USE IN HAZARDOUS LOCATIONS”.
Nonincendive fi eld wiring circuits must be wired in accordance with the National Electrical Code
(NEC), NFPA 70, article 501; CEC, Appendix J, Annex J18.
The earth conductor must be at least of the same wire size (mm² or AWG)
as the supply conductors.
WARNING – EXPLOSION HAZARD
Substitution of any components may impair suitability for hazardous locations or explosive
atmospheres.
WARNING – EXPLOSION HAZARD
Do not disconnect equipment unless power has been switched off or the area is known to be
known to be non-hazardous.
Installation RSP20/25/30/35
Release
16
12/2019
13
Control Drawing for RSP devices according to Class I Division 2 Hazardous Locations
Rev.: 0 Document No.: 000189237DNR Page 2/2
Ordinary Location,
Non-Hazardous Area,
Non-Explosive Atmosphere
Explosive Atmosphere
Class I Division 2
Groups A, B, C, D
Hazardous Location
RSP
Relay
Power Supply unit type CC: 24 VDC - 48 VDC
Power Supply unit type K9: 110 VAC - 230 VAC or
60 VDC - 250 VDC
Power Supply unit type KK: 2x 110 VAC - 230 VAC or
2x 60 VDC - 250 VDC
(Refer to the power supply code of the type designation on the device.)
Temperature Code: T4
Ambient Temperature rating:
Ta: 0 °C to +60 °C for “S” temperature types
Ta: í40 °C to +70 °C for “T” or “E” temperature types
(Refer to the temperature code of the type designation on the device.)
Relay contacts:
Equipment with nonincendive  eld wiring parameters.
Polarity is not relevant.
The relay terminals are dependent upon the following
Entity parameters:
U
i
I
i
C
i
L
i
30 V 90 mA 2 nF 1 H
14
Installation RSP20/25/30/35
Release
16
12/2019
IECEx – Certification Scheme for Explosive Atmospheres
For RSP devices labeled with an IECEx certificate number, the following
applies:
List of standards:
IEC 60079-0:2011+Cor.2012+Cor.2013
IEC 60079-15:2010
The equipment shall only be used in an area of not more than pollution
degree 2, as defined in IEC 60664-1.
Make sure that the device has the following label:
Ex nA IIC T4 Gc IECEx DEK 15.0014X
Environmental class and temperature code for RSP types:
T4: 0 °C Ta +60 °C for “S“ types or
T4: 40 °C Ta +70 °C for “T“ or “E“ types
The modules shall be installed in a suitable enclosure in accordance
with IEC 60079-15 providing a degree of protection of at least IP54
according to IEC 60529, taking into account the environmental
conditions under which the equipment will be used.
When the temperature under rated conditions exceeds 158 °F (70 °C)
at the cable or conduit entry point, or 176 °F (80 °C) at the branching
point of the conductors, the temperature specification of the selected
cable and cable entries shall be in compliance with the actual
measured temperature values.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
The USB port shall remain disconnected.
Installation RSP20/25/30/35
Release
16
12/2019
15
CE marking
The labeled devices comply with the regulations contained in the following
European directive(s):
In accordance with the above-named EU directive(s), the EU conformity
declaration will be at the disposal of the relevant authorities at the
following address:
Hirschmann Automation and Control GmbH
Stuttgarter Str. 45-51
72654 Neckartenzlingen
Germany
www.hirschmann.com
The product can be used in the industrial sector.
Interference immunity: EN 61000-6-2
Emitted interference: EN 55032
Reliability: EN 60950-1
You find more information on technical standards here:
“Technical data” on page 47
Warning! This is a class A device. This device can cause interference in
living areas, and in this case the operator may be required to take
appropriate measures.
Note: The assembly guidelines provided in these instructions must be
strictly adhered to in order to observe the EMC threshold values.
LED or laser components
LED or LASER components according to IEC 60825-1 (2014):
CLASS 1 LASER PRODUCT
CLASS 1 LED PRODUCT
Device variant Directive
All variants 2014/30/EU (EMC)
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to
electromagnetic compatibility.
2011/65/EU and 2015/863/EU (RoHS)
Directive of the European Parliament and of the Council on the
restriction of the use of certain hazardous substances in
electrical and electronic equipment.
Only for device variants
featuring supply voltage with
characteristic value K9 or KK:
2014/35/EU
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to the
making available on the market of electrical equipment
designed for use within certain voltage limits.
16
Installation RSP20/25/30/35
Release
16
12/2019
FCC note
Supplier's Declaration of Conformity
47 CFR § 2.1077 Compliance Information
RSP20/25/30/35
U.S. Contact Information
Belden – St. Louis
1 N. Brentwood Blvd. 15th Floor
St. Louis, Missouri 63105, United States
Phone: 314.854.8000
This device complies with part 15 of the FCC rules. Operation is subject
to the following two conditions: (1) this device may not cause harmful
interference; (2) this device must accept any interference received,
including interference that may cause undesired operation.
Appropriate testing has established that this device fulfills the
requirements of a class A digital device in line with part 15 of the FCC
regulations.
These requirements are designed to provide sufficient protection against
interference when the device is being used in a business environment.
The device creates and uses high frequencies and can also radiate these
frequencies. If it is not installed and used in accordance with this
operating manual, it can cause radio transmission interference. The use
of this device in a residential area can also cause interference, and in this
case the user is obliged to cover the costs of removing the interference.
Recycling note
After usage, this device must be disposed of properly as electronic waste,
in accordance with the current disposal regulations of your county, state,
and country.
Installation RSP20/25/30/35
Release
16
12/2019
17
About this manual
The “Installation” user manual contains a device description, safety
instructions, a description of the display, and the other information that you
need to install the device.
Documentation mentioned in the “User Manual Installation” that is not
supplied with your device as a printout can be found as PDF files for
downloading on the Internet at: https://www.doc.hirschmann.com
18
Installation RSP20/25/30/35
Release
16
12/2019
Key
The symbols used in this manual have the following meanings:
Listing
Work step
Subheading
Installation RSP20/25/30/35
Release
16
12/2019
19
1 Description
1.1 General description
The RSP20/25/30/35 devices are designed for the special requirements of
industrial automation. They meet the relevant industry standards, provide
very high operational reliability, even under extreme conditions, and also
long-term reliability and flexibility.
You can choose from between a wide range of variants. You have the option
to set up your device individually based on different criteria:
Number of ports
Transmission speed
Types of connectors
Temperature range
Supply voltage range
Certifications
Redundancy functions
You have the option of choosing various media to connect to the end devices
and other network components:
Multimode optical fiber
Singlemode optical fiber
Twisted pair cable
The device is mounted by latching in place on a DIN rail.
The devices work without a fan.
The redundancy concept allows the network to be reconfigured quickly.
There are convenient options for managing the device. Manage your devices
via:
Web browser
SSH
Telnet
V.24 interface (locally on the device)
Network management software (for example Industrial HiVision)
The Network Management Software Industrial HiVision provides you with
options for smooth configuration and monitoring. You find further
information on the Internet at the Hirschmann product pages:
http://www.hirschmann.com/en/QR/INET-Industrial-HiVision
20
Installation RSP20/25/30/35
Release
16
12/2019
The device provides you with a large range of functions, which the manuals
for the operating software inform you about. You find these manuals as PDF
files on the Internet at http://www.doc.hirschmann.com
The Hirschmann network components help you ensure continuous
communication across all levels of the company.
1.2 Device name and product code
The device name corresponds to the product code. The product code is
made up of characteristics with defined positions. The characteristic values
stand for specific product properties.
You have numerous options of combining the device characteristics. You can
determine the possible combinations using the Configurator which is
available in the Belden Online Catalog https://catalog.belden.com on the web
page of the device.
Item Characteristic Character
istic value
Description
1 ... 5 Product RSP20 Fast Ethernet switch
RSP25 Fast Ethernet switch with extended redundancy
function
RSP30 Gigabit Ethernet switch
RSP35 Gigabit Ethernet switch with extended
redundancy function
6 (hyphen)
7 ... 8 Number
Fast Ethernet ports
08 8 ×
11 11 ×
9 ... 10 Number
Gigabit Ethernet ports
00 0 ×
03 3 ×
11 ... 13 Configuration of the
uplink ports
3Z6 3 × Optional SFP slot for:
100 Mbit/s twisted pair connections
100 Mbit/s F/O connections
3O6 3 × Optional SFP slot for:
100 Mbit/s twisted pair connections
1000 Mbit/s twisted pair connections
100 Mbit/s F/O connections
1000 Mbit/s F/O connections
14 ... 15 Configuration of the
other ports
TT 8 × RJ45 socket for 10/100 Mbit/s Twisted pair
connections
ZT 4 × RJ45 socket for 10/100 Mbit/s Twisted pair
connections
4 × Optional SFP slot for:
100 Mbit/s twisted pair connections
100 Mbit/s F/O connections
16 (hyphen)
Table 4: Device name and product code
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Hirschmann RSP 20/25/30/35 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI