Hirschmann RSP 20/25/30/35 User manual

Type
User manual
Installation RSP20/25/30/35
Release
17
01/2021
Technical support
https://hirschmann-support.belden.com
User Manual
Installation
Industrial Ethernet Rail Switch Power
RSP20/25/30/35
21.01.2021
Installation RSP20/25/30/35
Release
17
01/2021
The naming of copyrighted trademarks in this manual, even when not specially indicated, should
not be taken to mean that these names may be considered as free in the sense of the trademark
and tradename protection law and hence that they may be freely used by anyone.
© 2021 Hirschmann Automation and Control GmbH
Manuals and software are protected by copyright. All rights reserved. The copying, reproduction,
translation, conversion into any electronic medium or machine scannable form is not permitted,
either in whole or in part. An exception is the preparation of a backup copy of the software for
your own use.
The performance features described here are binding only if they have been expressly agreed
when the contract was made. This document was produced by Hirschmann Automation and
Control GmbH according to the best of the company's knowledge. Hirschmann reserves the right
to change the contents of this document without prior notice. Hirschmann can give no guarantee
in respect of the correctness or accuracy of the information in this document.
Hirschmann can accept no responsibility for damages, resulting from the use of the network
components or the associated operating software. In addition, we refer to the conditions of use
specified in the license contract.
You can get the latest version of this manual on the Internet at the Hirschmann product site
(www.hirschmann.com).
Hirschmann Automation and Control GmbH
Stuttgarter Str. 45-51
72654 Neckartenzlingen
Germany
Installation RSP20/25/30/35
Release
17
01/2021
3
Contents
Important information 5
Safety instructions 7
About this manual 19
Key 20
1 Description 21
1.1 General description 21
1.2 Device name and product code 22
1.3 Device views 25
1.3.1 Front view 25
1.3.2 Rear view 26
1.4 Power supply 27
1.4.1 Supply voltage with the characteristic value K9 27
1.4.2 Supply voltage with the characteristic value KK 27
1.4.3 Supply voltage with the characteristic value TT 27
1.4.4 Supply voltage with the characteristic value CC 27
1.5 Ethernet ports 28
1.5.1 10/100 Mbit/s twisted pair port 28
1.5.2 100/1000 Mbit/s twisted pair port (optional) 28
1.5.3 100 Mbit/s F/O port 29
1.5.4 100/1000 Mbit/s F/O port (optional) 29
1.6 Display elements 30
1.6.1 Device state 30
1.6.2 Port status 31
1.7 Management interfaces 32
1.7.1 V.24 interface (external management) 32
1.7.2 SD card interface 32
1.8 Signal contact 33
2 Installation 34
2.1 Checking the package contents 34
2.2 Installing the SD card (optional) 34
4
Installation RSP20/25/30/35
Release
17
01/2021
2.3 Installing and grounding the device 35
2.3.1 Installing the device onto the DIN rail 35
2.3.2 Grounding the device 36
2.4 Installing an SFP transceiver (optional) 37
2.5 Connecting the terminal blocks 37
2.5.1 Supply voltage with the characteristic value K9 38
2.5.2 Supply voltage with the characteristic value KK 39
2.5.3 Supply voltage with the characteristic value CC 40
2.5.4 Supply voltage with the characteristic value TT 41
2.5.5 Signal contact 42
2.6 Operating the device 43
2.7 Connecting data cables 43
2.8 Filling out the inscription label 44
3 Making basic settings 45
4 Upgrading Software 47
5 Monitoring the ambient air temperature 48
6 Maintenance and service 49
7Disassembly 50
7.1 Removing the device 50
7.2 Removing an SFP transceiver (optional) 51
8 Technical data 52
8.1 General technical data 52
8.2 Dimension drawings 55
8.3 EMC and immunity 56
8.4 Network range 59
8.5 Power consumption/power output 63
8.6 Scope of delivery, order numbers and accessories 63
9 Underlying technical standards 66
A Further support 67
Installation RSP20/25/30/35
Release
17
01/2021
5
Important information
Note: Read these instructions carefully, and familiarize yourself with the
device before trying to install, operate, or maintain it. The following notes may
appear throughout this documentation or on the device. These notes warn of
potential hazards or call attention to information that clarifies or simplifies a
procedure.
Symbol explanation
This is a general warning symbol. This symbol alerts you to
potential personal injury hazards. Observe all safety notes that
follow this symbol to avoid possible injury or death.
If this symbol is displayed in addition to a safety instruction of the
type “Danger” or “Warning”, it means that there is a danger of
electric shock and failure to observe the instructions will
inevitably result in injury.
This symbol indicates the danger of hot surfaces on the device.
In connection with safety instructions, non-observance of the
instructions will inevitably result in injuries.
DANGER
DANGER draws attention to an immediately dangerous situation, which will
inevitably result in a serious or fatal accident if not observed.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION
CAUTION indicates a possible danger which, if not avoided, may result in
minor injuries.
6
Installation RSP20/25/30/35
Release
17
01/2021
NOTICE
NOTE provides information about procedures that do not involve the risk of
injury.
Installation RSP20/25/30/35
Release
17
01/2021
7
Safety instructions
General safety instructions
You operate this device with electricity. Improper usage of the device
entails the risk of physical injury or significant property damage. The
proper and safe operation of this device depends on proper handling
during transportation, proper storage and installation, and careful
operation and maintenance procedures.
Before connecting any cable, read this document, and the safety
instructions and warnings.
Operate the device with undamaged components exclusively.
The device is free of any service components. In case of a damaged
or malfunctioning device, turn off the supply voltage and return the
device to Hirschmann for inspection.
Certified usage
Use the product only for the application cases described in the
Hirschmann product information, including this manual.
Operate the product only according to the technical specifications.
See “Technical data” on page 52.
Connect to the product only components suitable for the requirements
of the specific application case.
WARNING
UNCONTROLLED MACHINE ACTIONS
To avoid uncontrolled machine actions caused by data loss, configure all
the data transmission devices individually.
Before you start any machine which is controlled via data transmission, be
sure to complete the configuration of all data transmission devices.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
8
Installation RSP20/25/30/35
Release
17
01/2021
Installation site requirements
If you connect the device to a power supply that does NOT meet the
requirements for Limited Power Source, NEC Class 2 or PS2
according to IEC/EN 62368-1 and is NOT limited to 100 W output
power, the device must be installed in either a switch cabinet or other
fire enclosure.
The fire enclosure can be made of metal or plastic with fire-protection
properties of at least V-1 according to IEC 60695-11-10. Bottom
openings of the fire enclosure must NOT exceed 2 mm in diameter.
Only for device variants featuring supply voltage with characteristic
value K9 or KK:
Install this device only in a switch cabinet or in an operating site with
restricted access, to which maintenance staff have exclusive access.
Strain relief
Note: If the strain relief is insufficient, there is a risk of torsion, contact
problems and creeping interruptions.
Relieve the connection points of cables and lines from mechanical
stress.
Design strain relieves in such a way that they prevent any mechanical
damage to cables, wires or conductors caused by external influences
or their own weight.
To prevent damage to device connections, connectors and cables,
follow the instructions for proper installation in accordance with DIN
VDE 0100-520:2013-06, sections 522.6, 522.7 and 522.13.
Device casing
Only technicians authorized by the manufacturer are permitted to open
the casing.
Never insert pointed objects (narrow screwdrivers, wires, etc.) into the
device or into the connection terminals for electric conductors. Do not
touch the connection terminals.
Keep the ventilation slits free to ensure good air circulation.
Mount the device in the vertical position.
At ambient air temperatures > +140 °F (+60 °C):
The surfaces of the device housing may become hot. Avoid touching
the device while it is operating.
Installation RSP20/25/30/35
Release
17
01/2021
9
Qualification requirements for personnel
Only allow qualified personnel to work on the device.
Qualified personnel have the following characteristics:
Qualified personnel are properly trained. Training as well as practical
knowledge and experience make up their qualifications. This is the
prerequisite for grounding and labeling circuits, devices, and systems
in accordance with current standards in safety technology.
Qualified personnel are aware of the dangers that exist in their work.
Qualified personnel are familiar with appropriate measures against
these hazards in order to reduce the risk for themselves and others.
Qualified personnel receive training on a regular basis.
National and international safety regulations
Verify that the electrical installation meets local or nationally applicable
safety regulations.
Grounding the device
Grounding the device is by means of a separate ground connection on the
device.
Ground the device before connecting any other cables.
Disconnect the grounding only after disconnecting all other cables.
Ground the device via the ground screw.
Shielding ground
The overall shield of a connected shielded twisted pair cable is connected
to the grounding connector on the front panel as a conductor.
Beware of possible short circuits when connecting a cable section with
conductive shielding braiding.
Requirements for connecting electrical wires
Before connecting the electrical wires, always verify that the
requirements listed are complied with.
Requirements for connecting the signal contact
All of the following requirements are complied with:
The electrical wires are voltage-free.
The cables used are permitted for the temperature range of the application case.
Table 1: Requirements for connecting electrical wires
All of the following requirements are complied with:
The voltage connected complies with the requirements for a safety extra-low voltage
(SELV) as per IEC 60950-1 or ES1 as per IEC/EN 62368-1.
The connected voltage is limited by a current limitation device or a fuse.
Observe the electrical threshold values for the signal contact.
See “General technical data” on page 52.
Table 2: Requirements for connecting the signal contact
10
Installation RSP20/25/30/35
Release
17
01/2021
Requirements for connecting the supply voltage
Device variant Requirements
All variants All of the following requirements are complied with:
The supply voltage corresponds to the voltage specified on the type
plate of the device.
The power supply conforms to overvoltage category I or II.
The power supply has an easily accessible disconnecting device (for
example a switch or a plug). This disconnecting device is clearly
identified. So in the case of an emergency, it is clear which
disconnecting device belongs to which power supply cable.
The cross-section of the ground conductor is the same size as or
bigger than the cross-section of the power supply cables.
Relevant for North America:
The power supply cables are suitable for ambient air temperatures of
at least +167 °F (+75 °C). The wires of the power supply cables are
made of copper.
Only for device
variants featuring
supply voltage with
the characteristic
value CC:
If you connect 2 independent power sources, verify that the minus
terminal is grounded. Failure to follow this instruction can result in
equipment damage.
The wire diameter of the power supply cable is at least 0.75 mm² (North
America: AWG18) on the supply voltage input.
The following requirements are alternatively complied with:
Alternative 1 The power supply complies with the requirements
for a limited power source (LPS) according to IEC/
EN 60950-1 or PS2 according to IEC/EN 62368-1.
Alternative 2 Relevant for North America:
The power supply complies with the requirements
according to NEC Class 2.
Alternative 3 All of the following requirements are complied with:
The power supply complies with the
requirements for a safety extra-low voltage
(SELV) according to IEC 60950-1 or ES1
according to IEC/EN 62368-1.
A back-up fuse suitable for DC voltage is
located in the plus conductor of the power
supply.
The minus conductor is on ground potential.
Otherwise, a back-up fuse is also located in the
minus conductor.
Regarding the properties of this back-up fuse:
See “General technical data” on page 52.
Table 3: Requirements for connecting the supply voltage
Installation RSP20/25/30/35
Release
17
01/2021
11
Only device variants
featuring supply
voltage with
characteristic value
TT:
If you connect 2 independent power sources, verify that the minus
terminal is grounded. Failure to follow this instruction can result in
equipment damage.
The wire diameter of the power supply cable is at least 0.75 mm² (North
America: AWG18) on the supply voltage input.
The following requirements are alternatively complied with:
Alternative 1 The power supply complies with the requirements
for a limited power source (LPS) according to IEC/
EN 60950-1 or PS2 according to IEC/EN 62368-1.
Alternative 2 All of the following requirements are complied with:
The power supply complies with the
requirements for a safety extra-low voltage
(SELV) according to IEC 60950-1 or ES1
according to IEC/EN 62368-1.
A back-up fuse suitable for DC voltage is
located in the plus conductor of the power
supply.
The minus conductor is on ground potential.
Otherwise, a back-up fuse is also located in the
minus conductor.
Regarding the properties of this back-up fuse:
See “General technical data” on page 52.
Alternative 3 Relevant for North America:
The power supply complies with the requirements
according to NEC Class 2.
Only for device
variants featuring
supply voltage with
characteristic
value K9 or KK:
All of the following requirements are complied with:
Supply with DC voltage:
A back-up fuse suitable for DC voltage is located in the plus conductor
of the power supply.
The minus conductor is on ground potential. Otherwise, a back-up
fuse is also located in the minus conductor.
Regarding the properties of this back-up fuse:
See “General technical data” on page 52.
The wire diameter of the power supply cable is at least 1 mm² (North
America: AWG16) on the supply voltage input.
Supply with AC voltage:
A fuse is located in the outer conductor of the power supply.
The neutral conductor is on ground potential at both voltage inputs.
Otherwise, a fuse is also located in the neutral conductor.
Regarding the properties of this fuse:
See “General technical data” on page 52.
The wire diameter of the power supply cable is at least 0.75 mm²
(North America: AWG18) on the supply voltage input.
Device variant Requirements
Table 3: Requirements for connecting the supply voltage
12
Installation RSP20/25/30/35
Release
17
01/2021
Supply voltage
The supply voltage is connected to the device casing through protective
elements exclusively.
For supply voltage connections with protective conductor connection:
First connect the protective conductor before connecting the wires for
the supply voltage.
ATEX directive 2014/34/EU – specific regulations for safe
operation
Relevant for RSP devices when operating in explosive gas atmospheres
according to ATEX directive 2014/34/EU, the following applies:
List of standards:
EN 60079-0:2012, A11:2013
EN 60079-15:2010
Certificate No.: DEKRA 15ATEX0017X
Use only device variants featuring supply voltage with characteristic
value CC.
Make sure that the device has the following label:
II 3G Ex nA IIC T4 Gc DEKRA 15ATEX0017X
Ambient rating and temperature code for RSP types:
T4: 0 °C Ta +60 °C for “S” types or
T4: 40 °C Ta +70 °C for “T” or “E” types
The modules shall be installed in a suitable enclosure in accordance
with IEC 60079-15 providing a degree of protection of at least IP54
according to IEC 60529, taking into account the environmental
conditions under which the equipment will be used.
When the temperature under rated conditions exceeds 158 °F (70 °C)
at the cable or conduit entry point, or 176 °F (80 °C) at the branching
point of the conductors, the temperature specification of the selected
cable and cable entries shall be in compliance with the actual
measured temperature values.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
The USB port shall remain disconnected.
Installation RSP20/25/30/35
Release
17
01/2021
13
Relevant for use in explosion hazard areas (Hazardous
Locations, Class I, Division 2):
The relay connections are to be installed and used within their Entity
Parameters as per Control Drawing 000189237DNR.
Avertissement - Risque d'explosion - Ne pas débrancher tant que le
circuit est sous tension à moins que l'emplacement soit connu pour ne
contenir aucune concentration de gaz inflammable.
Avertissement - Risque d'explosion - La substitution de tout composant
peut rendre ce matériel incompatible pour une utilisation en classe I,
division 2.
14
Installation RSP20/25/30/35
Release
17
01/2021
Control Drawing for RSP devices according to Class I Division 2 Hazardous Locations
Rev.: 0 Document No.: 000189237DNR Page 1/2
For Use in Hazardous Locations Class I Division 2 Groups A, B, C, D:
Only allowed for RSP 20/25/30/35 model No´s. which are individually labeled
“FOR USE IN HAZARDOUS LOCATIONS”.
Nonincendive fi eld wiring circuits must be wired in accordance with the National Electrical Code
(NEC), NFPA 70, article 501; CEC, Appendix J, Annex J18.
The earth conductor must be at least of the same wire size (mm² or AWG)
as the supply conductors.
WARNING – EXPLOSION HAZARD
Substitution of any components may impair suitability for hazardous locations or explosive
atmospheres.
WARNING – EXPLOSION HAZARD
Do not disconnect equipment unless power has been switched off or the area is known to be
known to be non-hazardous.
Installation RSP20/25/30/35
Release
17
01/2021
15
Control Drawing for RSP devices according to Class I Division 2 Hazardous Locations
Rev.: 0 Document No.: 000189237DNR Page 2/2
Ordinary Location,
Non-Hazardous Area,
Non-Explosive Atmosphere
Explosive Atmosphere
Class I Division 2
Groups A, B, C, D
Hazardous Location
RSP
Relay
Power Supply unit type CC: 24 VDC - 48 VDC
Power Supply unit type K9: 110 VAC - 230 VAC or
60 VDC - 250 VDC
Power Supply unit type KK: 2x 110 VAC - 230 VAC or
2x 60 VDC - 250 VDC
(Refer to the power supply code of the type designation on the device.)
Temperature Code: T4
Ambient Temperature rating:
Ta: 0 °C to +60 °C for “S” temperature types
Ta: í40 °C to +70 °C for “T” or “E” temperature types
(Refer to the temperature code of the type designation on the device.)
Relay contacts:
Equipment with nonincendive  eld wiring parameters.
Polarity is not relevant.
The relay terminals are dependent upon the following
Entity parameters:
U
i
I
i
C
i
L
i
30 V 90 mA 2 nF 1 H
16
Installation RSP20/25/30/35
Release
17
01/2021
IECEx – Certification Scheme for Explosive Atmospheres
For RSP devices labeled with an IECEx certificate number, the following
applies:
List of standards:
IEC 60079-0:2011+Cor.2012+Cor.2013
IEC 60079-15:2010
The equipment shall only be used in an area of not more than pollution
degree 2, as defined in IEC 60664-1.
Make sure that the device has the following label:
Ex nA IIC T4 Gc IECEx DEK 15.0014X
Environmental class and temperature code for RSP types:
T4: 0 °C Ta +60 °C for “S“ types or
T4: 40 °C Ta +70 °C for “T“ or “E“ types
The modules shall be installed in a suitable enclosure in accordance
with IEC 60079-15 providing a degree of protection of at least IP54
according to IEC 60529, taking into account the environmental
conditions under which the equipment will be used.
When the temperature under rated conditions exceeds 158 °F (70 °C)
at the cable or conduit entry point, or 176 °F (80 °C) at the branching
point of the conductors, the temperature specification of the selected
cable and cable entries shall be in compliance with the actual
measured temperature values.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 119 V.
Connectors shall be connected or disconnected exclusively in dead-
voltage state.
The USB port shall remain disconnected.
Installation RSP20/25/30/35
Release
17
01/2021
17
CE marking
The labeled devices comply with the regulations contained in the following
European directive(s):
In accordance with the above-named EU directive(s), the EU conformity
declaration will be at the disposal of the relevant authorities at the
following address:
Hirschmann Automation and Control GmbH
Stuttgarter Str. 45-51
72654 Neckartenzlingen
Germany
www.hirschmann.com
The product can be used in the industrial sector.
Interference immunity: EN 61000-6-2
Emitted interference: EN 55032
Reliability: EN 62368-1
You find more information on technical standards here:
“Technical data” on page 52
Warning! This is a class A device. This device can cause interference in
living areas, and in this case the operator may be required to take
appropriate measures.
Note: The assembly guidelines provided in these instructions must be
strictly adhered to in order to observe the EMC threshold values.
LED or laser components
LED or LASER components according to IEC 60825-1 (2014):
CLASS 1 LASER PRODUCT
CLASS 1 LED PRODUCT
Device variant Directive
All variants 2014/30/EU (EMC)
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to
electromagnetic compatibility.
2011/65/EU and 2015/863/EU (RoHS)
Directive of the European Parliament and of the Council on the
restriction of the use of certain hazardous substances in
electrical and electronic equipment.
Only for device variants
featuring supply voltage with
characteristic value K9 or KK:
2014/35/EU
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to the
making available on the market of electrical equipment
designed for use within certain voltage limits.
18
Installation RSP20/25/30/35
Release
17
01/2021
FCC note
Supplier's Declaration of Conformity
47 CFR § 2.1077 Compliance Information
RSP20/25/30/35
U.S. Contact Information
Belden – St. Louis
1 N. Brentwood Blvd. 15th Floor
St. Louis, Missouri 63105, United States
Phone: 314.854.8000
This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
Recycling note
After usage, this device must be disposed of properly as electronic waste,
in accordance with the current disposal regulations of your county, state,
and country.
Installation RSP20/25/30/35
Release
17
01/2021
19
About this manual
The “Installation” user manual contains a device description, safety
instructions, a description of the display, and the other information that you
need to install the device.
Documentation mentioned in the “User Manual Installation” that is not
supplied with your device as a printout can be found as PDF files for
downloading on the Internet at: https://www.doc.hirschmann.com
20
Installation RSP20/25/30/35
Release
17
01/2021
Key
The symbols used in this manual have the following meanings:
Listing
Work step
Subheading
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68

Hirschmann RSP 20/25/30/35 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI