Belden Hirschman RSPS20 User manual

Type
User manual

This manual is also suitable for

Installation RSPS20/25
Release
09
12/2019
Technical support
https://hirschmann-support.belden.com
User Manual
Installation
Industrial Ethernet Rail Switch Power Smart
RSPS20/25
2019-12-06
Installation RSPS20/25
Release
09
12/2019
The naming of copyrighted trademarks in this manual, even when not specially indicated, should
not be taken to mean that these names may be considered as free in the sense of the trademark
and tradename protection law and hence that they may be freely used by anyone.
© 2019 Hirschmann Automation and Control GmbH
Manuals and software are protected by copyright. All rights reserved. The copying, reproduction,
translation, conversion into any electronic medium or machine scannable form is not permitted,
either in whole or in part. An exception is the preparation of a backup copy of the software for
your own use.
The performance features described here are binding only if they have been expressly agreed
when the contract was made. This document was produced by Hirschmann Automation and
Control GmbH according to the best of the company's knowledge. Hirschmann reserves the right
to change the contents of this document without prior notice. Hirschmann can give no guarantee
in respect of the correctness or accuracy of the information in this document.
Hirschmann can accept no responsibility for damages, resulting from the use of the network
components or the associated operating software. In addition, we refer to the conditions of use
specified in the license contract.
You can get the latest version of this manual on the Internet at the Hirschmann product site
(www.hirschmann.com).
Hirschmann Automation and Control GmbH
Stuttgarter Str. 45-51
72654 Neckartenzlingen
Germany
Installation RSPS20/25
Release
09
12/2019
3
Contents
Safety instructions 5
About this manual 11
Key 12
1 Description 13
1.1 General description 13
1.2 Device name and product code 14
1.3 Device views 17
1.3.1 Front view 17
1.3.2 Rear view 19
1.4 Power supply 20
1.4.1 Supply voltage with the characteristic value M9 or K9 20
1.4.2 Supply voltage with the characteristic value CC 20
1.5 Ethernet ports 20
1.5.1 100/1000 Mbit/s twisted pair port (optional) 20
1.5.2 100 Mbit/s F/O port (optional) 21
1.6 Display elements 21
1.6.1 Device state 21
1.6.2 Port status 22
1.7 Management interfaces 23
1.7.1 V.24 interface (external management) 23
1.7.2 SD card interface 23
1.8 Signal contact 24
2 Installation 25
2.1 Checking the package contents 25
2.2 Installing the SD card (optional) 25
2.3 Installing and grounding the device 26
2.3.1 Installing the device onto the DIN rail 26
2.3.2 Grounding the device 27
2.4 Installing an SFP transceiver (optional) 28
2.5 Connecting the terminal blocks 28
4
Installation RSPS20/25
Release
09
12/2019
2.5.1 Supply voltage with the characteristic value M9 or K9 29
2.5.2 Supply voltage with the characteristic value CC 30
2.5.3 Signal contact 31
2.6 Operating the device 32
2.7 Connecting data cables 32
2.8 Filling out the inscription label 32
3 Making basic settings 33
4 Upgrading Software 34
5 Monitoring the ambient air temperature 35
6 Maintenance and service 36
7Disassembly 37
7.1 Removing the device 37
7.2 Removing an SFP transceiver (optional) 38
8 Technical data 39
8.1 General technical data 39
8.2 Dimension drawings 42
8.3 EMC and immunity 43
8.4 Network range 47
8.5 Power consumption/power output 48
8.6 Scope of delivery, order numbers and accessories 48
9 Underlying technical standards 50
A Further support 51
Installation RSPS20/25
Release
09
12/2019
5
Safety instructions
General safety instructions
You operate this device with electricity. Improper usage of the device
entails the risk of physical injury or significant property damage. The
proper and safe operation of this device depends on proper handling
during transportation, proper storage and installation, and careful
operation and maintenance procedures.
Before connecting any cable, read this document, and the safety
instructions and warnings.
Operate the device with undamaged components exclusively.
The device is free of any service components. In case of a damaged
or malfunctioning device, turn off the supply voltage and return the
device to Hirschmann for inspection.
Certified usage
Use the product only for the application cases described in the
Hirschmann product information, including this manual.
Operate the product only according to the technical specifications.
See “Technical data” on page 39.
Connect to the product only components suitable for the requirements
of the specific application case.
Installation site requirements
Install the device in a fire enclosure according to EN 60950-1.
Exclusively for device variants featuring supply voltage with
characteristic value K9 or M9:
See “Device name and product code” on page 14.
Install this device solely in a switch cabinet or in an operating site with
restricted access, to which maintenance staff have exclusive access.
Install the device at ambient temperatures > +113 °F (+45 °C) in
“restricted access locations” based on EN 60950-1 exclusively.
WARNING
UNCONTROLLED MACHINE ACTIONS
To avoid uncontrolled machine actions caused by data loss, configure all
the data transmission devices individually.
Before you start any machine which is controlled via data transmission, be
sure to complete the configuration of all data transmission devices.
Failure to follow these instructions can result in death, serious injury,
or equipment damage.
6
Installation RSPS20/25
Release
09
12/2019
Device casing
Only technicians authorized by the manufacturer are permitted to open
the casing.
Never insert pointed objects (narrow screwdrivers, wires, etc.) into the
device or into the connection terminals for electric conductors. Do not
touch the connection terminals.
Keep the ventilation slits free to ensure good air circulation.
Mount the device in the vertical position.
At ambient air temperatures > +140 °F (+60 °C):
The surfaces of the device housing may become hot. Avoid touching
the device while it is operating.
Qualification requirements for personnel
Only allow qualified personnel to work on the device.
Qualified personnel have the following characteristics:
Qualified personnel are properly trained. Training as well as practical
knowledge and experience make up their qualifications. This is the
prerequisite for grounding and labeling circuits, devices, and systems
in accordance with current standards in safety technology.
Qualified personnel are aware of the dangers that exist in their work.
Qualified personnel are familiar with appropriate measures against
these hazards in order to reduce the risk for themselves and others.
Qualified personnel receive training on a regular basis.
National and international safety regulations
Verify that the electrical installation meets local or nationally applicable
safety regulations.
Grounding the device
Grounding the device is by means of a separate ground connection on the
device.
Ground the device before connecting any other cables.
Disconnect the grounding only after disconnecting all other cables.
Shielding ground
The overall shield of a connected shielded twisted pair cable is connected
to the grounding connector on the front panel as a conductor.
Beware of possible short circuits when connecting a cable section with
conductive shielding braiding.
Requirements for connecting electrical wires
Before connecting the electrical wires, always verify that the
requirements listed are complied with.
Installation RSPS20/25
Release
09
12/2019
7
Requirements for connecting the signal contact
Requirements for connecting the supply voltage
All of the following requirements are complied with:
The electrical wires are voltage-free.
The cables used are permitted for the temperature range of the application case.
Table 1: Requirements for connecting electrical wires
All of the following requirements are complied with:
The voltage connected complies with the requirements for a safety extra-low voltage
(SELV) as per IEC/EN 60950-1.
The connected voltage is limited by a current limitation device or a fuse.
Observe the electrical threshold values for the signal contact.
See “General technical data” on page 39.
Table 2: Requirements for connecting the signal contact
Device variant Requirements
All variants All of the following requirements are complied with:
The supply voltage corresponds to the voltage specified on the type
plate of the device.
The power supply conforms to overvoltage category I or II.
The power supply has an easily accessible disconnecting device (for
example a switch or a plug). This disconnecting device is clearly
identified. So in the case of an emergency, it is clear which
disconnecting device belongs to which power supply cable.
The cross-section of the ground conductor is the same size as or
bigger than the cross-section of the power supply cables.
Relevant for North America:
The power supply cables are suitable for ambient air temperatures of
at least 167 °F (75 °C). The power supply cable wires are made of
copper.
Table 3: Requirements for connecting the supply voltage
8
Installation RSPS20/25
Release
09
12/2019
Supply voltage
The supply voltage is connected to the device casing through protective
elements exclusively.
For supply voltage connections with protective conductor connection:
First connect the protective conductor before connecting the wires for
the supply voltage.
Only for device
variants featuring
supply voltage with
the characteristic
value CC:
If you connect 2 independent power sources, verify that the minus
terminal is grounded. Failure to follow this instruction can result in
equipment damage.
The wire diameter of the power supply cable is at least 1 mm² (North
America: AWG16) on the supply voltage input.
The following requirements are alternatively complied with:
Alternative 1 The power supply complies with the requirements
for a limited power source (LPS) as per EN 60950-1.
Alternative 2 Relevant for North America:
The power supply complies with the requirements
according to NEC Class 2.
Alternative 3 All of the following requirements are complied with:
The power supply complies with the
requirements for a safety extra-low voltage
(SELV) as per IEC/EN 60950-1.
A fuse suitable for DC voltage is located in the
plus conductor of the power supply.
The minus conductor is on ground potential.
Otherwise, a fuse is also located in the minus
conductor.
Regarding the properties of this fuse:
See “General technical data” on page 39.
Exclusively for
device variants
featuring supply
voltage with
characteristic
value K9 or M9:
All of the following requirements are complied with:
Supply with DC voltage:
A fuse suitable for DC voltage is located in the plus conductor of the
power supply.
The minus conductor is on ground potential. Otherwise, a fuse is also
located in the minus conductor.
Regarding the properties of this fuse:
See “General technical data” on page 39.
The wire diameter of the power supply cable is at least 1 mm² (North
America: AWG16) on the supply voltage input.
Supply with AC voltage:
A fuse is located in the outer conductor of the power supply.
The neutral conductor is on ground potential at both voltage inputs.
Otherwise, a fuse is also located in the neutral conductor.
Regarding the properties of this fuse:
See “General technical data” on page 39.
The wire diameter of the power supply cable is at least 0.75 mm²
(North America: AWG18) on the supply voltage input.
Device variant Requirements
Table 3: Requirements for connecting the supply voltage
Installation RSPS20/25
Release
09
12/2019
9
CE marking
The labeled devices comply with the regulations contained in the following
European directive(s):
In accordance with the above-named EU directive(s), the EU conformity
declaration will be at the disposal of the relevant authorities at the
following address:
Hirschmann Automation and Control GmbH
Stuttgarter Str. 45-51
72654 Neckartenzlingen
Germany
www.hirschmann.com
The product can be used in the industrial sector.
Interference immunity: EN 61000-6-2
Emitted interference: EN 55032
Reliability: EN 60950-1
You find more information on technical standards here:
“Technical data” on page 39
Warning! This is a class A device. This device can cause interference in
living areas, and in this case the operator may be required to take
appropriate measures.
Note: The assembly guidelines provided in these instructions must be
strictly adhered to in order to observe the EMC threshold values.
LED or laser components
LED or LASER components according to IEC 60825-1 (2014):
CLASS 1 LASER PRODUCT
CLASS 1 LED PRODUCT
Device variant Directive
All variants 2014/30/EU (EMC)
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to
electromagnetic compatibility.
2011/65/EU and 2015/863/EU (RoHS)
Directive of the European Parliament and of the Council on the
restriction of the use of certain hazardous substances in
electrical and electronic equipment.
Exclusively for device variants
featuring supply voltage with
characteristic value K9 or M9:
2014/35/EU
Directive of the European Parliament and of the Council on the
harmonisation of the laws of the Member States relating to the
making available on the market of electrical equipment
designed for use within certain voltage limits.
10
Installation RSPS20/25
Release
09
12/2019
FCC note
Supplier's Declaration of Conformity
47 CFR § 2.1077 Compliance Information
RSPS20/25
U.S. Contact Information
Belden – St. Louis
1 N. Brentwood Blvd. 15th Floor
St. Louis, Missouri 63105, United States
Phone: 314.854.8000
This device complies with part 15 of the FCC rules. Operation is subject
to the following two conditions: (1) this device may not cause harmful
interference; (2) this device must accept any interference received,
including interference that may cause undesired operation.
Appropriate testing has established that this device fulfills the
requirements of a class A digital device in line with part 15 of the FCC
regulations.
These requirements are designed to provide sufficient protection against
interference when the device is being used in a business environment.
The device creates and uses high frequencies and can also radiate these
frequencies. If it is not installed and used in accordance with this
operating manual, it can cause radio transmission interference. The use
of this device in a residential area can also cause interference, and in this
case the user is obliged to cover the costs of removing the interference.
Recycling note
After usage, this device must be disposed of properly as electronic waste,
in accordance with the current disposal regulations of your county, state,
and country.
Installation RSPS20/25
Release
09
12/2019
11
About this manual
The “Installation” user manual contains a device description, safety
instructions, a description of the display, and the other information that you
need to install the device.
Documentation mentioned in the “User Manual Installation” that is not
supplied with your device as a printout can be found as PDF files for
downloading on the Internet at: https://www.doc.hirschmann.com
12
Installation RSPS20/25
Release
09
12/2019
Key
The symbols used in this manual have the following meanings:
Listing
Work step
Subheading
Installation RSPS20/25
Release
09
12/2019
13
1 Description
1.1 General description
The RSPS20/25 devices are designed for the special requirements of
industrial automation. They meet the relevant industry standards, provide
very high operational reliability, even under extreme conditions, and also
long-term reliability and flexibility.
You can choose from between a wide range of variants. You have the option
to set up your device individually based on different criteria:
Types of connectors
Temperature range
Supply voltage range
Certifications
Redundancy functions
You have the option of choosing various media to connect to the end devices
and other network components:
Multimode optical fiber
Singlemode optical fiber
Twisted pair cable
The device is mounted by latching in place on a DIN rail.
The devices work without a fan.
The redundancy concept allows the network to be reconfigured quickly.
There are convenient options for managing the device. Manage your devices
via:
Web browser
SSH
Telnet
V.24 interface (locally on the device)
Network management software (for example HiVision)
The Network Management Software Industrial HiVision provides you with
options for smooth configuration and monitoring. You find further
information on the Internet at the Hirschmann product pages:
http://www.hirschmann.com/en/QR/INET-Industrial-HiVision
The device provides you with a large range of functions, which the manuals
for the operating software inform you about. You find these manuals as PDF
files on the Internet at http://www.doc.hirschmann.com
14
Installation RSPS20/25
Release
09
12/2019
The Hirschmann network components help you ensure continuous
communication across all levels of the company.
1.2 Device name and product code
The device name corresponds to the product code. The product code is
made up of characteristics with defined positions. The characteristic values
stand for specific product properties.
You have numerous options of combining the device characteristics. You can
determine the possible combinations using the Configurator which is
available in the Belden Online Catalog https://catalog.belden.com on the web
page of the device.
Item Characteristic Character
istic value
Description
1 ... 4 Product RSPS Rail Switch Power Smart
5 ... 6 Data rate and
hardware type
20 Fast Ethernet switch
25 Fast Ethernet switch with extended redundancy
function
7 (hyphen)
8 ... 9 Number
Fast Ethernet ports
06 6 ×
10 ... 11 Number
Gigabit Ethernet ports
00 0 ×
12 ... 14 Configuration of the
uplink ports
2T1 2 × RJ45 socket for 10/100 Mbit/s Twisted pair
connections
2Z6 2 × SFP slot for 100 Mbit/s F/O connections
15 ... 16 Configuration of the
other ports
TT 4 × RJ45 socket for 10/100 Mbit/s Twisted pair
connections
YT 2 × SFP slot for 100 Mbit/s F/O connections
2 × RJ45 socket for 10/100 Mbit/s Twisted pair
connections
17 (hyphen)
18 Temperature range S Standard +32 °F ... +140 °F (0 °C ...
+60 °C)
T Extended 40 °F ... +158 °F (40 °C ...
+70 °C)
E Extended with
Conformal Coating
40 °F ... +158 °F (40 °C ...
+70 °C)
Table 4: Device name and product code
Installation RSPS20/25
Release
09
12/2019
15
19 ... 20 Supply voltage CC 2 voltage inputs for redundant power supply
Rated voltage range DC:
24 V DC ... 48 V DC
K9 1 voltage input
Rated voltage range AC:
110 V AC ... 230 V AC, 50 Hz ... 60 Hz
Rated voltage range DC:
60 V DC ... 250 V DC
M9 1 voltage input
Rated voltage range AC:
110 V AC ... 230 V AC, 50 Hz ... 60 Hz
Rated voltage range DC:
110 V DC ... 250 V DC
21 ... 22 Certificates and
declarations
You will find detailed information on the certificates and
declarations applying to your device in a separate overview.
See table 5 on page 16.
22 ... 23 Customer-specific
version
HS Hirschmann Standard
HM Hirschmann Fast MRP
HP Hirschmann PRP
HH Hirschmann HSR
Note: You can exchange software with each other on the following device variants:
HM
HP
HH
Item Characteristic Character
istic value
Description
Table 4: Device name and product code
16
Installation RSPS20/25
Release
09
12/2019
Application case Certificates and declarations Characteristic value
a
a. X = Certificate or declaration present
(X) = Certificate or declaration in preparation
(x) = Certificate or declaration available upon request
T9 TY U9 UT UX UY V9 VT VU VY X9 Y9 Z9
Standard applications CE X X XXXXXXXXXXX
FCC XXXXXXXXXXXXX
EN 60950-1 X X XXXXXXXXXXX
EN 61131-2 X X XXXXXXXXXXX
UL 508 X XXX XXXXX
UL 60950-1 (X) (X) (X) (X) (X) X (X) (X) (X)
Substation applications IEC61850-3 XXXX
IEEE 1613 XXXX
Oil and gas applications ISA-12.12.01 – Class I, Div. 2 X X
Railway applications (trackside) EN 50121-4 X X X X
Navy applications GL XXXX X
ABS (X) (X) (X) (X) (X)
BV (X) (X) (X) (X) (X)
DNV (X) (X) (X) (X) (X)
LR (X) (X) (X) (X) (X)
Table 5: Assignment: application cases, certificates and declarations, characteristic values
Installation RSPS20/25
Release
09
12/2019
17
1.3 Device views
1.3.1 Front view
Front view:
on the left: Device variants RSPS...........2Z6YT..CC....
on the right: Device variants RSPS...........2Z6TT..M9/K9....
1 LED display elements for device status
2 V.24 interface
3 Uplink ports
2 × SFP slot for 100 Mbit/s F/O connections
4 Other ports
alternatively,
depending on
device variant
Port configuration
characteristic value:
YT
2 × SFP slot for 100 Mbit/s F/O connections
2 × RJ45 socket for 10/100 Mbit/s Twisted pair
connections
Port configuration
characteristic value:
TT
4 × RJ45 socket for 10/100 Mbit/s Twisted pair
connections
5 Grounding screw
1
2
3
4
5
6
7
5
6
7
1
2
3
4
18
Installation RSPS20/25
Release
09
12/2019
6 Supply voltage connection
alternatively,
depending on
device variant
Supply voltage with
the characteristic
value:
CC
2 voltage inputs for redundant power supply
2-pin terminal block
Supply voltage with
the characteristic
value:
M9 or K9
1 voltage input
3-pin terminal block
7 Connection for the signal contact
Front view of device variants RSPS...........2T1TT........
1 LED display elements for device status
2 V.24 interface
3Uplink ports
2 × RJ45 socket for 10/100 Mbit/s Twisted pair connections
4 Other ports
4 × RJ45 socket for 10/100 Mbit/s Twisted pair connections
5 Grounding screw
1
2
3
4
5
6
7
Installation RSPS20/25
Release
09
12/2019
19
1.3.2 Rear view
6 Supply voltage connection
alternatively,
depending on
device variant
Supply voltage with
the characteristic
value:
CC
2 voltage inputs for redundant power supply
2-pin terminal block
Supply voltage with
the characteristic
value:
M9 or K9
1 voltage input
3-pin terminal block
7 Connection for the signal contact
1 Slot for the SD card
2 Thumb screw
1
2
20
Installation RSPS20/25
Release
09
12/2019
1.4 Power supply
You will find information on the characteristic values here:
“Device name and product code” on page 14
1.4.1 Supply voltage with the characteristic value M9 or K9
The following options for power supply are available:
1 × 3-pin terminal block
You will find information on connecting the supply voltage here:
See “Supply voltage with the characteristic value M9 or K9” on page 20.
1.4.2 Supply voltage with the characteristic value CC
The following options for redundant power supply are available:
2 × 2-pin terminal block
You will find information on connecting the supply voltage here:
See “Supply voltage with the characteristic value CC” on page 20.
1.5 Ethernet ports
You can connect end devices and other segments to the device ports using
twisted pair cables or optical fibers (F/O).
1.5.1 100/1000 Mbit/s twisted pair port (optional)
This port is an SFP slot.
The 100/1000 Mbit/s twisted pair port allows you to connect network
components according to the standard IEEE 802.3 100BASE-TX/
1000BASE-T.
This port supports:
Autonegotiation
Full duplex mode
Pin Function
1BI_DB+
2BI_DB
3BI_DA+
4 BI_DD+
5BI_DD
6BI_DA
7 BI_DC+
8BI_DC
Table 6: Pin assignment of the 10/100/1000 Mbit/s twisted pair port, RJ45 socket,
1000 Mbit/s mode, MDI-X mode
1
2
3
4
5
6
7
8
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Belden Hirschman RSPS20 User manual

Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI