Honeywell C7031G 2000 Series Electronic Temperature Sensors are designed to measure temperature accurately and reliably in various applications. These sensors are commonly used in HVAC systems, industrial processes, and scientific research. With their rugged construction and diverse mounting options, they can be deployed in demanding environments and challenging locations. The C7031G sensors have a wide temperature measurement range and provide a linear output signal, making them compatible with most control systems.

Honeywell C7031G 2000 Series Electronic Temperature Sensors are designed to measure temperature accurately and reliably in various applications. These sensors are commonly used in HVAC systems, industrial processes, and scientific research. With their rugged construction and diverse mounting options, they can be deployed in demanding environments and challenging locations. The C7031G sensors have a wide temperature measurement range and provide a linear output signal, making them compatible with most control systems.

INSTALLATION INSTRUCTIONS
62-0220-03
C7031G; C7041B,C,F,K; T775-SENS-OAT/STRAP
Series 2000 Electronic Temperature Sensors
C7031G, C7041F, T775-SENS-OAT OUTDOOR; STRAP-ON, C7041B,
C DUCT; C7031D, C7041D IMMERSION
SENSOR APPLICATIONS
Table 1. Electronic Sensor Application Guide
C7031D,
C7041D
C7031G, C7041F,
T775-SENS-OAT
C7041B,C
Strap-on
Model Application Output Element Insertion Length
C7031D Immersion 1097 ohms @ 77 F 5 in. (127 mm)
C7031G Outdoor 3484 ohms @ 77 F
C7041B Duct 20 K ohm NTC @ 77 F 6 in. (152) or 12 in. (305 mm)
C7041C Duct 20 K ohm NTC @ 77 F 18 in. (457 mm)
C7041D Immersion 20 K ohm NTC @ 77 F 5 in. (127 mm)
C7041F Outdoor 20 K ohm NTC @ 77 F
C7041K Strap-On 20 K ohm NTC @ 77 F
T775-SENS-OAT Outdoor 1097 ohms @ 77 F
T775-SENS-STRAP Strap-On 1097 ohms @ 77 F
C7041B,C
Duct
C7031D,
C7041D
Immersion
C7031G, C7041F,
T775-SENS-OAT
Outdoor
Be sure to take advantage of the entire line of quality Honeywell Sensors
C7041P
Button
Probe
Strap-on
C7041R
Duct
Rigid
Copper C7031J,
C7041J
Duct
Cable
Averaging
C7031G; C7041B,C,F,K; T775-SENS-OAT/STRAP SERIES 2000 ELECTRONIC TEMPERATURE SENSORS
62-0220—03 2
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to
follow them could damage the product or
cause a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
Mounting
The mounting method depends on the particular sensor
application. The following procedures include:
duct applications
outdoor applications
immersion well applications
strap-on applications
NOTE: Also refer to the instructions for the electronic
control.
Duct Mounting (C7041B,C)
IMPORTANT
Select a spot for the sensor that will exposed it to
average duct air temperature. Avoid locations
where stratification can cause sensing errors.
1. Cut a hole in the duct just large enough to accept
the sensing element.
2. Use the sensor’s case to mark locations of pilot
holes for the mounting screws.
3. Drill pilot holes and fasten the sensor to the duct.
Fig. 1. C7041B,C Dimensions in in. (mm).
Outdoor Mounting (C7031G, C7041F;
T775-SENS-OAT)
The outdoor air temperature sensors have a weather-
proof enclosure. Mount the sensor where it can sense
average outdoor air temperature. All mounting hardware
is provided with the sensor. Be sure to mount the sensor
out of direct sunlight with the sensor probe point down.
Normally, the north side of a building provides a suitable
location.
NOTE: C7031G, C7041F, and T775-SENS-OAT are
weatherproof for outdoor use. Knockouts allow
for
1/2 in. conduit connection.
1. Remove and set aside the wiring box cover.
2. Mount the sensor to standard 1/2 in. conduit.
NOTE: Mount sensor so that the element points
down.
3. Make wiring connections using two wire nuts.
4. Reattach the wiring box cover.
Fig. 2. C7031G, C7041F, T775-SENS-OAT
Dimensions in in. (mm).
2-5/16
(59)
15/16
(23)
1-11/16
(43)
4-3/16
(107)
3/4
(19)
4
(70)
1-11/16
(43)
C7031B: 5-11/16 (145)
C7041B: 11-5/8 (295)
C7041C: 17-5/8 (448)
M22131
1-13/16
(46)
7/16 (12)
1/8 NPSM (3)
3-7/8 (99)
2-1/4 (57)
3/4
(19)
1 (25)
5
(127)
7/8
(22)
8-5/16
(211)
M22132
3-5/8 (91)
C7031G; C7041B,C,F,K; T775-SENS-OAT/STRAP SERIES 2000 ELECTRONIC TEMPERATURE SENSORS
3 62-0220—03
Immersion Well Mounting (C7031D, C7041D)
NOTE: The C7041D uses the 50001774-001 Well
Assembly. See Fig. 5 for dimensions.
The C7031D Sensor includes an immersion well. The
C7041D Sensor does not include a well. For the C7041D,
order the well as an accessory (part no.: 50001774-001).
When used on a boiler, follow the manufacturer
instructions for location. If a tapped hole is not provided
for the immersion well, provide one as follows:
1. Drain boiler and drill a 23/32 in. (18 mm) hole at the
selected location.
2. Cut threads in the hole with a 1/2 in. (13 mm) by
14 NPT tap.
In other installations, mount the immersion well in an
elbow with a heel outlet as shown in Fig. 3.
1. Drain the system, if you have not already done it,
and open the tapped hole.
2. Put pipe joint compound on the threads of the
immersion well and screw it into the tapped hole or
elbow, tightening it securely.
3. Refill the system and check for leaks.
Mount the C7031D/C7041D into the well:
NOTE: Mounting using previously installed
Honeywell wells (part no.: 32005960-001)
requires an adapter
(part no.: 50001775-001).
1. When an adapter is required, first thread it into the
well no more than one or two turns.
2. Slide the sensor into the well.
3. Rotate the sensor to thread it tightly into the adapter
and the adapter tightly into the well.
Fig. 3. Method of Mounting C7031D/C7041D Sensor.
Fig. 4. C7031D, C7041D Dimensions in in. (mm).
Fig. 5. 50001774-001 Immersion Well Dimensions in in. (mm).
1/2 NPT (13)
M22135
SENSING ELEMENT
(SEALED IN STAINLESS STEEL
TUBE INSIDE OF INSERTION WELL)
2-5/16
(59)
1-11/16
(43)
4-3/16
(107)
1/4
(6)
4
(70)
1-11/16
(43)
6-11/16 (170)
M22596
5 (127)
1/2 NPSM (13)
3/4 (19)
3/8
(10)
1 (26) 4 (102)
FITS 1/2 NPT TAPPED HOLE
M22597
1/2 NPSM
INTERNALLY
THREADED
C7031G; C7041B,C,F,K; T775-SENS-OAT/STRAP SERIES 2000 ELECTRONIC TEMPERATURE SENSORS
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2008 Honeywell International Inc.
62-0220—03 J.I. Rev. 01-08
Strap-on Mounting (C7041K, T775-SENS-
STRAP)
The Sensor mounts on metal pipes from 1-5/8 inch to five
inches in diameter using the straps supplied. Clean the
pipe surface where the sensor makes contact before
mounting. If necessary, remove pipe insulation at the
installation point. Thermal compound is recommended.
Locate the sensor on the discharge pipe within 3 ft. (0.9
m) of the boiler. See Fig. 6.
NOTE: Insulation around the contact area increases
sensor accuracy.
Fig. 6. Strap-on Mounting of Sensor.
Fig. 7. Strap-on Dimensions in in. (mm).
M22136
SENSOR
PIPE
COPPER PLATE MUST
MAKE GOOD CONTACT
WITH METAL PIPE
WORM GEAR
2-5/16
(59)
4-3/16
(107)
4
(70)
1-11/16
(43)
7-1/8 (182)
9/16 (14)
1-1/2
(38)
1-1/2
(38)
2-5/16
(59)
M22134
1-1/4
(32)
5 (127)
MAXIMUM PIPE DIAMETER SHOWN.
MINIMUM PIPE DIAMETER: 1-5/8 (41)
1
1
4-3/16 (107)
COPPER PLATE
FOAM PAD
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Honeywell C7031G 2000 Series Electronic Temperature Sensors User manual

Type
User manual

Honeywell C7031G 2000 Series Electronic Temperature Sensors are designed to measure temperature accurately and reliably in various applications. These sensors are commonly used in HVAC systems, industrial processes, and scientific research. With their rugged construction and diverse mounting options, they can be deployed in demanding environments and challenging locations. The C7031G sensors have a wide temperature measurement range and provide a linear output signal, making them compatible with most control systems.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI