WAGO 16-Channel Digital Inpu/Output User manual

Type
User manual
Product manual | Version 1.1.0
WAGO I/O System Field
16-Channel Digital Input/Output; IO-Link Class A Hub; 24 V DC; 2.0 A; 8
× M12 Connection
765-1703/0200-0000
765-1703/0200-0000Legal Information
© 2020 WAGO Kontakttechnik GmbH & Co. KG
All rights reserved.
WAGO Kontakttechnik GmbH & Co. KG
Hansastraße 27
D - 32423 Minden
Phone: +49 571/887 – 0
Fax: +49 571/887 – 844169
Internet: ü www.wago.com
Technical Support
Phone: +49 571/887 – 44555
Fax: +49 571/887 – 844555
Every conceivable measure has been taken to ensure the accuracy and completeness of
this documentation. However, as errors can never be fully excluded, we always appreci-
ate any information or suggestions for improving the documentation.
We wish to point out that the software and hardware terms as well as the trademarks of
companies used and/or mentioned in the present manual are generally protected by
trademark or patent.
WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH.
Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
765-1703/0200-0000 Table of Contents
Product manual | Version: 1.1.0 iii
16DIO FLD IOL-A HUB DC 24V 2.0A
Table of Contents
1 Provisions.........................................................................................................................6
1.1 Document Portfolio.................................................................................................. 6
1.2 Intended Use........................................................................................................... 6
1.3 Technical Condition of Specified Devices ............................................................... 7
1.4 Typographical Conventions..................................................................................... 7
1.5 Legal Information .................................................................................................... 9
2 Safety ..............................................................................................................................11
2.1 General Safety Rules ............................................................................................ 11
2.2 Electrical Safety..................................................................................................... 11
2.3 Mechanical Safety................................................................................................. 12
2.4 Thermal Safety...................................................................................................... 12
2.5 Indirect Safety ....................................................................................................... 12
3 Overview .........................................................................................................................13
4 Properties .......................................................................................................................14
4.1 View....................................................................................................................... 14
4.2 Connections .......................................................................................................... 15
4.2.1 Supply Voltage and IO-Link..........................................................................15
4.2.2 Digital Inputs/Outputs ...................................................................................15
4.3 Circuit Diagram...................................................................................................... 16
4.4 Technical data....................................................................................................... 16
4.4.1 Product .........................................................................................................16
4.4.2 Mechanical data ........................................................................................... 16
4.4.3 Connection Technology................................................................................16
4.4.4 Power Supply ............................................................................................... 17
4.4.5 Electrical Safety............................................................................................17
4.4.6 Environmental Conditions ............................................................................18
4.4.7 Communication ............................................................................................18
4.5 Derating................................................................................................................. 18
4.6 Regulations and Standards................................................................................... 19
4.7 Approvals .............................................................................................................. 19
5 Functions........................................................................................................................20
5.1 Process Image ...................................................................................................... 20
5.2 Monitoring Functions............................................................................................. 20
5.3 Overload Protection............................................................................................... 20
5.4 Parameterization Tools ......................................................................................... 20
5.4.1 WAGO I/O Field app ....................................................................................21
6 Planning..........................................................................................................................23
765-1703/0200-0000Table of Contents
iv Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
6.1 Structure Guidelines.............................................................................................. 23
6.1.1 Installation Site and Touch-Proof Protection ................................................23
6.2 Power Supply Concept.......................................................................................... 23
6.2.1 Design Power Supply ...................................................................................23
6.3 Connection Example ............................................................................................. 25
6.4 Settings Options.................................................................................................... 25
6.4.1 Device Description Files (IODD) ..................................................................26
6.4.2 Port Configuration ........................................................................................26
6.4.3 Input Configuration .......................................................................................26
6.4.4 Configuration of the Substitute Value Behavior for the Digital Outputs........26
6.5 Switch ON and OFF Behavior............................................................................... 27
6.6 Retentive Data....................................................................................................... 27
6.7 Behavior in the Event of a Communication Interruption........................................ 27
6.8 Behavior in the Event of a Brief Power Supply Interruption .................................. 28
6.9 Behavior if Configuration Data is Lost or Invalid ................................................... 28
7 Transport and Storage...................................................................................................29
8 Installation and Removal...............................................................................................30
8.1 Installation ............................................................................................................. 30
8.1.1 Tools Required for Installation......................................................................30
8.1.2 Before Installation.........................................................................................30
8.1.3 Installation Instructions.................................................................................30
8.1.4 Note on Protecting against Heat Generation by the Product .......................31
8.1.5 Installation Distances ...................................................................................31
8.1.6 Installation ....................................................................................................31
8.2 Removal ................................................................................................................ 31
8.2.1 Tools Required for Removal.........................................................................31
8.2.2 Before Removal............................................................................................31
8.2.3 Removal of 0765-xxxx..................................................................................32
8.2.4 After Removal...............................................................................................32
9 Connection .....................................................................................................................33
9.1 General Information on Installation ....................................................................... 33
9.2 Connect Cables..................................................................................................... 33
9.3 Connect Power Supply.......................................................................................... 33
9.4 Connecting Fieldbus ............................................................................................. 34
9.5 Connect Sensors/Actuators .................................................................................. 34
10 Commissioning ..............................................................................................................37
10.1 Parameterization ................................................................................................... 37
10.1.1 WAGO IO-Link Configurator.........................................................................37
10.1.1.1 System Requirements .........................................................................37
10.1.1.2 Launching WAGO IO-Link Configurator ..............................................37
10.1.1.2.1 Operation as a Standalone Program ......................................... 37
10.1.1.2.2 Activation and Licensing ............................................................ 38
10.1.1.2.3 Install ......................................................................................... 39
765-1703/0200-0000 Table of Contents
Product manual | Version: 1.1.0 v
16DIO FLD IOL-A HUB DC 24V 2.0A
10.1.1.3 WAGO IO-Link Configurator User Interface ........................................39
10.1.1.3.1 Start Screen and Login Dialog................................................... 39
10.1.1.3.2 Workbench................................................................................. 40
10.1.1.3.3 Device Catalog .......................................................................... 40
10.1.1.3.4 Topology .................................................................................... 41
10.1.1.3.5 Device Controls Window............................................................ 42
10.1.1.3.6 Menu Bar and Toolbar ............................................................... 42
10.1.1.3.7 IO-Link Master Control............................................................... 47
10.1.1.3.8 IO-Link Master Control 2............................................................ 51
10.1.1.3.9 IO-Link Device Control............................................................... 55
10.1.1.4 Parameterizing the Product with WAGO IO-Link Configurator............62
10.1.1.4.1 Operate via TCI (Tool Calling Interface) .................................... 62
10.1.1.4.2 Performing an IO-Link Device Firmware Update ....................... 63
10.1.1.4.3 Quick Start Guide: Using an ETHERNET IO-Link Master ......... 63
10.1.1.4.4 Quick Start Guide: Using TCI, e.g., in STEP 7 or the TIA Portal
................................................................................................... 63
10.1.1.4.5 IO-Link Implementation.............................................................. 64
10.1.2 WAGO I/O Field app ....................................................................................65
10.1.2.1 Parameterizing the Product with the WAGO I/O Field App .................65
10.1.3 IO-Link Object Directories ............................................................................ 65
10.1.3.1 Index 0 (0x0) - "Direct Parameter Page 1" Object...............................68
10.1.3.2 Index 1 (0x01) - "Direct Parameter Page 2" Object.............................68
10.1.3.3 Index 2 (0x02) - "System Command" Object.......................................68
10.1.3.4 Index 3 (0x03) - "Data Storage Index" Object .....................................69
10.1.3.5 Index 12 (0x0C) - "Device Access Locks" Object................................71
10.1.3.6 Index 13 (0x0D) - "Profile Characteristics" Object...............................71
10.1.3.7 Index 32 (0x20) - "Error Count since Last Start" Object ......................71
10.1.3.8 Index 36 (0x24) - "Device Status" Object ............................................72
10.1.3.9 Index 37 (0x25) - "Detailed Service Status" Object .............................72
10.1.3.10 Index 64 (0x40) - "Port Configuration" Object .....................................72
10.1.3.11 Index 65 (0x41) - "DI Filter Configuration" Object................................73
10.1.3.12 Index 66 (0x42) - “Test Input/Output” (Test IO) Object........................74
10.1.3.13 Index 67 (0x43) - "Test Event" Object .................................................76
10.1.3.14 Index 68 (0x44) - “Port Temperature” Object ......................................77
10.1.3.15 Index 69 (0x45) - "Supply Voltage (Pin 1)” Object...............................77
10.1.3.16 Index 70 (0x46) - "DIO Voltage" Object...............................................77
10.1.3.17 Index 71 (0x47) - "Supply Current" Object...........................................78
10.1.3.18 Index 72 (0x48) - "DIO Current" Object ...............................................78
10.1.3.19 Index 73 (0x49) - “Configuration of the Substitute Value Behavior for
the Digital Outputs” Object ..................................................................79
10.1.3.20 Index 75 (0x4B) - "DI Inversion Configuration" Object ........................80
10.1.3.21 Index 76 (0x4C) - "Debug Information" Object ....................................81
11 Diagnostics.....................................................................................................................83
11.1 Diagnostics via Indicators...................................................................................... 83
11.2 Diagnostics via IO-Link.......................................................................................... 84
12 Service ............................................................................................................................88
12.1 Update Firmware................................................................................................... 88
13 Decommissioning ..........................................................................................................90
13.1 Disposal and Recycling......................................................................................... 90
14 Appendix.........................................................................................................................91
14.1 Protected Rights.................................................................................................... 91
765-1703/0200-0000Provisions
6 Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
1Provisions
This documentation applies to the following product:
0765-1703/0100-0000.
1.1 Document Portfolio
Note
Observe the applicable documentation!
This product must only be installed and operated according to the instructions of the com-
plete Instructions for use. Knowledge of the complete Instructions for use is required for
proper use.
1. Carefully read the Product Manual.
2. Before commissioning, follow the instructions in section 8Safety [}11].
Table 1: Complete instructions for use
Document Type Contents
& Product Manual Contains all the product-specific information for a product.
& Data Sheet Contains the technical data for a product.
& Instruction leaflet Is included with each product. Contains initial information on safe handling of
the product.
All documentation is available at: üwww.wago.com /<item number>.
1.2 Intended Use
The product is used to capture and control digital field signals (e.g., from sensors and ac-
tuators) that are sent to a higher-level IO-Link master or received by a higher-level IO-
Link master.
This product is intended for installation in automation technology systems.
This product meets the requirements of protection type IP67 and is designed for use in
dry indoor spaces.
This product is intended for use in indoor industrial areas without weather exposure (no
direct sunlight; no salt water or salt spray).
Operation of the products in Industrial area is permitted.
Operation of the product in other application areas is only permitted when correspond-
ing approvals and labeling are present.
Improper Use
Improper use of the product is not permitted. Improper use occurs especially in the follow-
ing cases:
Non-observance of the intended use.
Use without additional protective measures in environments within which dust, corro-
sive fumes, gases or ionized radiation can occur.
765-1703/0200-0000 Provisions
Product manual | Version: 1.1.0 7
16DIO FLD IOL-A HUB DC 24V 2.0A
Use of the product in areas with special risk that require continuous fault-free operation
and in which failure of or operation of the product can result in an imminent risk to life,
limb or health or cause serious damage to property or the environment (such as the
operation of nuclear power plants, weapons systems, aircraft and motor vehicles).
Warranty and Liability
The terms set forth in the General Business & Contract Conditions for Delivery and Ser-
vice of WAGO Kontakttechnik GmbH & Co. KG and the terms for software products and
products with integrated software stated in the WAGO Software License Contract – both
available at üwww.wago.com – shall apply. In particular, the warranty is void if:
The product is improperly used.
The deficiency (hardware and software configurations) is due to special instructions.
The hardware or software has been modified by the user or a third party.
Individual agreements always have priority.
Obligations of Installers/Operators
The installers and operators bear responsibility for the safety of an installation or a sys-
tem assembled with the products. The installer/operator is responsible for proper installa-
tion and safety of the system. All laws, standards, guidelines, local regulations and ac-
cepted technology standards and practices applicable at the time of installation, and the
instructions in the the products’ Instructions for Use, must be complied with. In addition,
the Installation regulations specified by Approvals must be observed. In the event of non-
compliance, the products may not be operated within the scope of the approval.
1.3 Technical Condition of Specified Devices
The product is delivered from the factory for the intended use with a defined hardware
and software configuration. These modules contain no parts that can be serviced or re-
paired by the user. The following actions will result in the exclusion of liability on the part
of WAGO Kontakttechnik GmbH & Co. KG:
Repairs
Changes to the hardware or software that are not described in the operating instruc-
tions
Improper use of the product
Further details are provided in the contractual agreements. Please send your requests for
modified or new hardware or software configurations directly to WAGO Kontakttechnik
GmbH & Co. KG.
1.4 Typographical Conventions
Number Notation
100 Decimals: Normal notation
0x64 Hexadecimals: C-notation
‘100’
‘0110.0100’
Binary: In single quotation marks
Nibbles separated by a period
765-1703/0200-0000Provisions
8 Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
Text Formatting
italic Names of paths or files
bold Menu items, entry or selection fields, emphasis
Code Sections of program code
> Selection of a menu point from a menu
“Value” Value entries
[F5] Identification of buttons or keys
Cross References / Links
Cross reference / link to a section in a document
Cross reference / link to a separate document
ü
Cross reference / link to a website
Cross reference / link to an email address
Action Instructions
ü This symbol identifies a precondition.
1. Action step
2. Action step
ð This symbol identifies an intermediate result.
ð This symbol identifies the result of an action.
Lists
Lists, first level
Lists, second level
Notes
DANGER
Type and source of hazard
Possible consequences of hazard that also include death or irreversible injury
Action step to reduce risk
WARNING
Type and source of hazard
Possible consequences of hazard that also include severe injury
Action step to reduce risk
765-1703/0200-0000 Provisions
Product manual | Version: 1.1.0 9
16DIO FLD IOL-A HUB DC 24V 2.0A
CAUTION
Type and source of hazard
Possible consequences of hazard that include at least slight injury
Action step to reduce risk
!
NOTICE
Type and source of malfunction (property damage only)
Possible malfunctions that may restrict the product’s scope of functions or ergonomics,
but do not lead to foreseeable risks to persons
Action step to reduce risk
Note
Notes and information
Indicates information, clarifications, recommendations, referrals, etc.
Figures
Figures in this documentation are for better understanding and may differ from the actual
product design.
1.5 Legal Information
Intellectual Property
Unless barred by applicable legal provisions, unauthorized copying and distribution of this
document, as well as the use and communication of its content are strictly prohibited un-
less expressly authorized by prior agreement. Third-party products are always mentioned
without any reference to patent rights. WAGO Kontakttechnik GmbH & Co. KG, or for
third-party products, their manufacturer, retain all rights regarding patent, utility model or
design registration.
Third-party trademarks are referred to in the product documentation. The “
®
” and “
TM
symbols are omitted hereinafter. The trademarks are listed in the Appendix (8Protected
Rights [}91]).
Subject to Change
The instructions, guidelines, standards, etc., in this manual correspond to state of the art
at the time the documentation was created and are not subject to updating service. The
installer and operator bear sole responsibility to ensure they are complied with in their
currently applicable form. WAGO Kontakttechnik GmbH & Co. KG retains the right to
carry out technical changes and improvements of the products and the data, specifica-
tions and illustrations of this manual. All claims for change or improvement of products
that have already been delivered – excepting change or improvement performed under
guarantee agreement – are excluded.
765-1703/0200-0000Provisions
10 Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
Licenses
The products may contain open-source software. The requisite license information is
saved in the products. This information is also available under üwww.wago.com.
765-1703/0200-0000 Safety
Product manual | Version: 1.1.0 11
16DIO FLD IOL-A HUB DC 24V 2.0A
2Safety
This section contains safety rules that must be followed for hazard-free use of the prod-
uct.
This section is aimed at the following target groups:
Planners and installers
Operators
Qualified assembly personnel
Qualified installation personnel (electrical installation, technician network installation
etc.)
Qualified operating personnel
Qualified service and maintenance personnel
Obey the following safety rules:
2.1 General Safety Rules
This documentation is part of the product. Therefore, retain the documentation during
the entire service life of the product. Pass on the documentation to any subsequent
user of the product. In addition, ensure that any supplement to this documentation is
included, if necessary.
The product must only be installed and put into operation by qualified electrical special-
ists per EN 50110‑1/-2 and IEC 60364.
Comply with the laws, standards, guidelines, local regulations and accepted technol-
ogy standards and practices applicable at the time of installation.
2.2 Electrical Safety
Power Supply
Only operate the product with PELV or SELV power sources.
Connecting impermissible current or frequency values may destroy the product.
Cables
Maintain spacing between control, signal and data lines and the power supply lines.
Make sure the pin assignment is correct.
Only use conductor cross-sections sufficient for the current load.
Protection
When working on the system (e.g., during maintenance), protect the Facility part con-
cerned from accidental or unauthorized restart.
Shielding/Network
Observe the applicable standards for EMC-compatible installations.
765-1703/0200-0000Safety
12 Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
2.3 Mechanical Safety
Cooling of the product must not be impaired. Ensure air can flow freely and that the
minimum clearances from adjacent products/areas are maintained.
Do not install the product on or in the vicinity of easily flammable materials.
Before startup, please check the product for any damage that may have occurred dur-
ing shipping. Do not put the product into operation in the event of mechanical damage.
2.4 Thermal Safety
The surface of the housing heats up during operation. Under special conditions (e.g., in
the event of a fault or increased surrounding air temperature), touching the product
may cause burns. Allow the product to cool down before touching it.
If the surface temperature of the product can exceed 55°C, wear protective gloves and
attach protective covers and/or touch-proof protection.
2.5 Indirect Safety
Only use a dry or cloth or a clothed dampened with water to clean the product. Do not
use cleaning agents, e.g., abrasive cleaners, alcohols or acetone.
Do not allow the product to come into contact with ketones (e.g., acetone) or chlori-
nated hydrocarbons (e.g., dichloromethane) under any circumstances.
Do not use hard objects that could cause scratches for cleaning.
Clean tools and materials are imperative for handling the product.
If automation solutions are implemented that can cause personal injury or major prop-
erty damage in the event of failure, you must take appropriate measures to ensure that
the system remains in a safe operating state even in the event of failure.
Before installation and operation, please read the product documentation thoroughly
and carefully. In addition, note the information on the product housing and further infor-
mation, e.g. at üwww.wago.com/<item number>.
Only permit skilled personnel approved by WAGO to perform repair work.
Network analysis tools (e.g., “Wireshark”) may only be used by trained specialists.
765-1703/0200-0000 Overview
Product manual | Version: 1.1.0 13
16DIO FLD IOL-A HUB DC 24V 2.0A
3Overview
The IO-Link Hub is part of the WAGO I/O System Field 765. The IO-Link Hub has a plas-
tic housing that is suitable for screw mounting on a carrier. The product is designed for in-
dustrial use with protection class IP67 or higher.
The IO-Link Hub is intended for use in conjunction with an IO-Link Master (direct 1:1 con-
nection). The IO-Link product interface for connecting the master complies with IO-Link
specification 1.1. It provides digital inputs and outputs as well as the power supply for
connecting sensors or actuators to the IO-Link Master.
The IO-Link Hub can be used to connect up to 16 digital inputs or outputs to a port of the
IO-Link Master and connect to a higher-level network.
The IO-Link Master is used to parameterize the product. Settings can be parameterized
based on the port:
Custom configuration for using each port as a digital input for connecting sensors or
digital outputs for connecting actuators to the IO-Link network
Configuration of the input filters
Configuration of the input signal inversion
Configuration of the substitute value strategy for outputs
The connected IO-Link Master module controls the IO-Link Hub, couples it to the higher-
level network (e.g., real-time ETHERNET) and supplies it with the required operating volt-
age (+24 VDC).
The IO-Link device interface of the IO-Link Hub is designed according to IO-Link Class A.
A 5-pin M12 connector with A coding is used on the IO-Link device interface.
The digital inputs correspond to IEC 61131-2, Type 3. They are p-switching.
The inputs have input filters with a configurable time threshold. The time threshold is con-
figured via the IO-Link Master.
In addition to the adjustable current limitation, the digital outputs have a hardware-sup-
ported device for overcurrent and short circuit protection. The current is measured at
each output, monitored for short circuit, overload and wire break and automatically limited
if the maximum permissible value is exceeded.
The behavior of the digital outputs in case of faults (e.g., loss of communication with the
IO-Link Master) can be configured. This is achieved by defining a substitute value strat-
egy.
5-pin M12 sockets with A coding are used to connect the digital inputs and outputs.
The product has various diagnostic options:
Visual diagnostics via LEDs
Diagnostic codes that are forwarded to the IO-Link Master to be evaluated
765-1703/0200-0000Properties
14 Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
4Properties
4.1 View
Figure1: View
Table 2: Legend for “View” Figure
Function Position Custom Name Description
IO-Link Class A 2 X21 IO-Link device and supply
connection
1 IOL (X21) IO-Link LED for connec-
tion X21
3 2L (X21) 2L supply voltage LED
(24VDC)
765-1703/0200-0000 Properties
Product manual | Version: 1.1.0 15
16DIO FLD IOL-A HUB DC 24V 2.0A
Table 2: Legend for “View” Figure
Function Position Custom Name Description
Identification 4 - Data Matrix Code (DM
Code)
Contains the serial number
of the module (UII)
Digital inputs/outputs (1L
powered)
8 X01....X08 Digital inputs/outputs,
ports X01 to X08, 2-chan-
nel, M12, A-coded
7 1, 3, 5, 7, 9, 11, 13, 15 Port LEDs for connections
X01 to X08, channel B (pin
2)
9 0, 2, 4, 6, 8, 10, 12, 14 Port LEDs for connections
X01 to X08, channel A (pin
4)
Marking 6 - Port marking
10 - Module marking
Assembly 5 - Mounting hole for front or
side mounting
11 - Mounting hole for front or
side mounting
4.2 Connections
4.2.1 Supply Voltage and IO-Link
Table 3: Supply Voltage and IO-Link
Supply Voltage and IO-
Link Communication
Pin Signal Description
M12, A-coded, plug, 5-pin
1 1L+ 24VDC supply voltage U
1L
2 2L+ 24VDC auxiliary/control
voltage U
2L
3 1L− Reference potential for 1L
+
4 C/Q IO-Link device (data)
5 2L− Reference potential for 2L
+
4.2.2 Digital Inputs/Outputs
Table 4: Digital input/output (2-channel, 1L powered)
Digital Input/Output X01
- X04
Pin Signal Description
M12, A-coded, socket, 5-
pin
1 1L+ Supply voltage, 1L pow-
ered
2 DIO B (DI B/DQ B) Digital input/output chan-
nel B
3 1L– Reference potential for 1L
+
4 DIO A (DI A/DQ A) Digital input/output chan-
nel A
5 - Not connected
765-1703/0200-0000Properties
16 Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
4.3 Circuit Diagram
The following figure shows the schematic circuit diagram of the product.
Figure2: Circuit Diagram for Each Port
4.4 Technical data
4.4.1 Product
Item Number 0765-1703/0100-0000
Product function 16-channel digital input/output
Product name (short) 16DIO FLD IOL-A HUB 24VDC 2.0A
Product name (long) 16-channel digital input/output; IO-Link Class A Hub;
24V DC; 2.0A; 8× M12 connector
4.4.2 Mechanical data
Width 60mm
Height 30mm
Length 158.5mm
Weight 170g
Housing Plastic
Mounting type Screw mount, 2× M4
Tightening torque 1.2Nm
Side mounting: 0.8 Nm
4.4.3 Connection Technology
IO-Link communication and supply connection M12, A-coded, plug, 5-pin
Digital Inputs/Outputs 8× M12, A-coded, socket, 5-pin
Tightening torque M12: 1.0Nm
765-1703/0200-0000 Properties
Product manual | Version: 1.1.0 17
16DIO FLD IOL-A HUB DC 24V 2.0A
Digital input/output (1L powered)
Digital Input
Characteristic Type 3 (IEC61131-2)
Indicators On/off status LED
Digital Output
Output voltage 24VDC, 2L powered
Current Nominal: 2.0 A per channel
Maximum: 2.4 A per channel acc. IEC 61131-2
Residual current Less than 1mA
Circuit High-side driver; no reverse current protection from the
digital output
Voltage drop through high-side path Less than 250mV
Self-protection Overcurrent, overload and overtemperature
Maximum capacitive load 100µF parallel to 12Ohm; 10Hz
Maximum inductive load 1.15H / 2A; 0.2Hz; DC13
Indicators On/off status LED
Events: overcurrent, overload and overtemperature
Actuator/Sensor Supply
Output Voltage 24VDC, 1L powered
Current Maximum 2.0A per channel
Circuit High-side driver; no reverse current protection of the
1L+ output
Self-protection Overcurrent, overload and overtemperature
Voltage drop through high-side path Less than 200mV
Maximum capacitive load 250µF parallel to 12Ohm; 0.1Hz
Maximum inductive load 1.15H / 2A; 0.2Hz; DC13
Diagnostics (1L+) Events: overcurrent, overload and overtemperature
4.4.4 Power Supply
Supply voltage Powered via 1L
24VDC (17.5VDC...32.0VDC)
Voltages above 34V can permanently damage the
product.
Voltages below approx. 9.5 V lead to the port being
switched off and can cause the product to malfunction.
Undervoltage warning 17.5V message ON
17.7V message OFF
Overvoltage warning 32.0V message ON
31.8V message OFF
Power consumption hub 100 mA (at 24 VDC)
Power consumption of the supply connection 1L: Max. 1.0A
2L: Max. 4.0A
Maximum current: Observe derating depending on the
temperature.
Reverse voltage protection Yes
4.4.5 Electrical Safety
Insulation resistance 60VDC
Test voltage 550VAC RMS
765-1703/0200-0000Properties
18 Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
Min. creepage distance 0.7mm
Requirements
Use of PELV/SELV power supplies with fault voltage limited to 60VDC.
When SELV power supplies are used: SELV power supplies with supply via the same
network phase
If PELV (Protective Extra Low Voltage) power supplies are used: PELV (Protective Ex-
tra Low Voltage) power supplies with a secondary power supply connection to the
common reference point
4.4.6 Environmental Conditions
Surrounding air temperature (operation) –25°C...+70°C
Surrounding air temperature (storage) –40°C...+80°C
Maximum temperature change 3K/min
Relative humidity (operation) 5%...95%
Pollution degree 3 (EN60664-1)
Altitude 0...2000m
Overvoltage category II (EN60664-1)
Protection type IP67 (EN60529)
Protection class III (EN61140)
4.4.7 Communication
IO-Link Device
IO-Link device type IO-Link Device
Specification IO-Link V1.1.2
4.5 Derating
Please note the derating for use of the IO-Link hub. The surrounding air temperature and
current affect the module's heat generation.
The derating curve was created with the conditions of use “without air circulation” and
“mounting on poor heat conductor (wood).”
The following figure shows the maximum permissible current that can flow into the IO-
Link hub depending on the surrounding air temperature.
1
2
3
4
20
T
[°C]
25 30 35 40 45 50 55 60 65 70
I
[A]
0,5 m/s
0 m/s
Figure3: Derating, 765-1703/0200-0000
765-1703/0200-0000 Properties
Product manual | Version: 1.1.0 19
16DIO FLD IOL-A HUB DC 24V 2.0A
4.6 Regulations and Standards
Table 13: Standards and Regulations
Standard Title
EN 61000-6-2 Electromagnetic compatibility (EMC) – Immunity for industrial en-
vironments
EN 61000-6-4 Electromagnetic compatibility (EMC) – Emission standard for in-
dustrial environments
EN 61131-2 Programmable logic controllers
IEC 61131-9 IO-Link
4.7 Approvals
The following approvals have been granted for the product:
Conformity marking
UL UL 61010-1 and UL
61010-2-201, “Ordinary
Location”
In progress
Note
More information on approvals
You can find detailed information on the approvals online at: üwww.wago.com/<item
number>
765-1703/0200-0000Functions
20 Product manual | Version: 1.1.0
16DIO FLD IOL-A HUB DC 24V 2.0A
5Functions
5.1 Process Image
Table 14: IO Link hub process data allocation
Bit 7 6 5 4 3 2 1 0
Port/Pin Port X04
Pin 2
Port X04
Pin 4
Port X03
Pin 2
Port X03
Pin 4
Port X02
Pin 2
Port X02
Pin 4
Port X01
Pin 2
Port X01
Pin 4
Port/Pin Port X08
Pin 2
Port X08
Pin 4
Port X07
Pin 2
Port X07
Pin 4
Port X06
Pin 2
Port X06
Pin 4
Port X05
Pin 2
Port X05
Pin 4
5.2 Monitoring Functions
The IO-Link hub has extensive internal sensors for measurement of:
Temperatures
Currents
Voltages
The measurements are performed for the device and for pin1, pin2 and pin4 of each
port.
In the IO-Link hub, the measured values are compared to limiting values, and an alarm is
triggered if an event falls above or below a limiting value (e.g., a temperature limit). The
IO-Link hub sends the event to the IO-Link master. Section 8Diagnostics via IO-Link
[}84] lists the events.
5.3 Overload Protection
The product has internal overload protection for the output current. The output currently is
constantly measured and monitored for values exceeding the maximum.
If the measured output current exceeds the maximum value, the product reduces the cur-
rent or switches the corresponding loads off.
The temperature is measured in the IO-Link hub. If the temperature exceeds 105°C, the
hub switches off the affected ports.
5.4 Parameterization Tools
The parameters of the IO-Link hub are set via the connected IO-Link master. When using
IO-Link masters from the WAGO 765 Series, there are several ways to set the parame-
ters. The following table provides an overview of the tools that are available for these
modules.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

WAGO 16-Channel Digital Inpu/Output User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI