2
ADJUSTMENT
The LMRH-102 is pre-set for operation as described in the Default Functionality section. Adjustment is
optional.
A “configuration” button inside the battery compartment allows the user easy access to the Wattstopper
patented Push n’ Learn™ technology to simply modify the operation of the DLM local network.
Step 1: Enter Push n’ Learn (PnL)
1. Locate the configuration button inside the LMRH-102 battery compartment.
2. Press and hold the configuration button for 3 seconds while pointing at a DLM IR device.
The Red LED on the ALL other communicating devices connected to the DLM local network start
to blink rapidly (2x/second).
3. Release the button when the LED turns on.
The LED continues to blink until you exit Push n’ Learn mode.
All loads on the DLM local network will turn off immediately after entering Push n’ Learn.
After 1 second, load 1 as assigned by the Plug n’ Go feature will turn on.
Step 2: Load Selection
A quick press on the “configuration” button steps through all the loads connected to the DLM local network.
When a load turns on, all switch buttons and sensors that are bound to the load will have their blue LED
solid on.
1. To bind the load to one of the buttons on the LMRH-102, press the desired button making sure that
the LED turns on brightly.
2. To unbind a load, press the button.
The LED will go dim to indicate the button on the handheld remote no longer controls this specific load.
3. A quick press on the configuration button will activate the next load.
4. Repeat the process until all the loads are assigned to the buttons you desire.
NOTE: More than one load can be assigned to a button, and a load can be assigned to multiple buttons.
RESET PROCESS
Load binding reset - To clear the unit so that it is not bound to any load:
1. Make sure the DLM local network is in Normal operating mode.
2. Press and hold the configuration button in the battery compartment until LMRH device red LEDs go solid ON (approximately 10 seconds).
Device reset - To get the unit back to its default Plug n’ Go state:
1. Make sure the system is in Normal operating mode.
2. Press and hold the configuration button in the battery compartment for 20 seconds.
System Reset - To return all devices on the DLM local network to PnG:
1. Put the DLM local network into PnL.
2. Press and hold the configuration button for 20 seconds, until DLM device red LEDs resume blinking rapidly (approximately 2x/second).
TROUBLESHOOTING
LEDs on the remote
don’t light.
Press a button. If the LED doesn’t light:
1. Check to see if the LED is actually lit, but very dim. This is normal.
2. Press the top of the button to fully turn ON the LED.
3. Check batteries. Replace if needed.
4. Remove the batteries for 5 minutes. After 5 minutes, reinstall the batteries and try again.
The wrong lights are
controlled.
Configure the buttons to control the desired lights using the Push n’ Learn adjustment procedure.
Remote LEDs turn ON
and OFF but lights
don’t change.
1. Make sure the DLM local network is not in PnL.
2. Be sure you’re pointing the remote at a DLM IR enabled device that is within range.
To test, see if you can put the network into PnL using the remote from your current position.
• If successful, exit PnL and go on to step 3.
• If not successful, move closer to the IR enabled local network device and more directly in front of it,
or try pointing toward a different IR-enabled device.
3. Make sure the buttons are bound to the loads you want to control.
4. Configure the buttons to control the desired loads using the Push n’ Learn adjustment procedure.
Button LED blinks;
lights don’t change.
The button is not bound to any load. Configure the buttons to control the desired loads using the
Push n’ Learn adjustment procedure.
3 AAA 1.5V batteries
Point at
Configuration
Button
800.879.8585 www.legrand.us/wattstopper