Aqua Free FLUSH 2.0 Operating instructions

Type
Operating instructions
Contents Page
1 Safety information 2
2 Instructionsforttingandinitialoperation 2
3 Generalinstructions 2
4 Productdescription 3
5 Technicaldata 4
6 Itemssupplied 4
7 Handling 4
8 Programmingtheushingsystem 8
9 Correctingmalfunctions 11
10 Manufacturer 12
FLUSH 2.0
Operating and
installation instructions
32
1 Safety instructions
2 Instructionsforttingandinitialoperation
Onlysuitablyqualiedtechniciansusingappropriatetools
shouldinstallandset-uptheFLUSH2.0ushingsystem.
3 Generalinstructions
3.1 Backowprotection
3.2 Storage
Dryalloftheindividualcomponentsbeforestorageand
disconnectthebattery.Storethecomponentsoftheushing
systeminthecaseprovided.
3.3 Disposal
Pleasedisposeofthepackagingforthisproductinan
environmentallyfriendlyway.Donotdisposeofbatteries
withdomesticrefuse.Takethemtospecialbatterycollection
points.
4 Productdescription
Aqua freehasdevelopedtheFLUSH2.0ushingsystem
toautomaticallyandindividuallyushwateroutletsthatare
rarelyusedorleftunusedforperiodsoftime.Itprevents
waterstagnationandthethreatofmicrobialcontaminationin
thepipes.
FLUSH2.0canbeeasilyinstalledonanytaps,showers
orotherwateroutletsinprivatehomes,publicbuildingsor
commercialestablishments.
Recommendations for ushing cycles and ushing
duration:
If drinking water pipes are ushed daily Aquafree recom-
mends a ushing duration of 5 minutes.
Howevertheprecisedurationdependsonthecrosssection
andlengthofthepipeandthewaterpressurealthough
referenceshouldalwaysbemadetonationalguidelinesfor
ushing.
IMPORTANT! Beforetheushingsystemisusedwitha
mixertaporsimilaritisimportanttomakesurenon-return
valvesaretted.
NOTE
IMPORTANT!Pleasereadtheseinstructionscarefully.
Themanufactureracceptsnoliabilityforanydamagethat
occursbecausetheseinstructionsarenotfollowed.
Forfuturereferencekeeptheseinstructionsinthecase
withtheushingsystem.
CAUTION
Iftheushingsystemisconnectedtoalow-pressure
systemsuchasaboilerthereisariskofpressurebuild
up,causingleakage.
Beforeinstallingtheushingsystemcheckthewater
outletandassociatedpipework.Ifgasketsorjoints
aredamagedorunsecure,theadditionalweightofthe
ushingsystemcancauseleakage.
Thebatteryoftheushingsystemlastsforoneyear.
Thedateofthenextbatterychangecanberecorded
onthedeviceitselfusingthestickerssupplied.
Intheeventofbatteryfailurethevalvefailsafeposition
isCLOSEDandthe“DELAY”,“FREQUENCY”and
“RUNTIME”LEDsonthedisplaywillashrepeatedly.
Whenthebatteryischangedtheushingprogramwill
returntoitsdefaultsettings.Therequiredprogramme
shouldbere-enteredandthenre-activatedbypressing
theSETkeyforatleastveseconds.
WARNING
Iftheushingsystemisusedwithoutnon-returnvalves
beingttedorworking,anybackpressurefromthe
hotwatersupplyriskscontaminatingthewholeofthe
drinkingwatersupplysystem.
Non-returnvalvesshouldbettedonboththehotwater
andcoldwatersupplypipestothetap.
Theushingsystemshouldnotbeusedwithout
functioningnon-returnvalvesinplace.
54
5 Technicaldata
Couplingoptionsprovided M24×1; M22×1; G½"
Operatingvoltage: 9VoltDC
Operatingpressure: 0.2-10bar
Watertemperature:
5°-60°C
(withoutlimitation)
60°-90°C(lifetimereduced
by40%)
Flowrate: 20l/min
IPrating: IP68
Batteriesused: 1×9voltPP3(alkaline)
Flushingdurations:
30 sec; 1 min; 2 min; 3 min;
4 min; 5 min; 10 min
Flushingintervals:
every1h;2h;4h;8h;12h;
24 h; 48 h; 72 h
Medium: drinkingwater
6 Itemssupplied
1×FLUSH2.0ushing
system
2×9-voltPP3battery
1×M24adapter
(includingsealinggasket
andU-clamp)
1×spanner
(22mmund24mm)
1×M22adapter
(includingsealinggasket
and.U-clamp)
2×hygienicow
straightener
1×G½"-adapter
(includingsealinggasket
andU-clamp)
1×replacementsealing
gasket
5×replacementO-rings
(forattachmentpiece)
1×operatinginstructions
1x short instructions 5xbatterychangesticker
7 Handling
Installation:
Checkwhethernon-returnvalvesarettedinthepipes
supplyingthetap.
Removetheaerator(fromtaps)orunscrewtheshower
hose(fromshowers)
Toinsertthebattery,rstunscrewthetransparentcover
oftheushingsystemandremovetheblackbattery
coverbelowtheoperatingpanel.
Thenttheappropriatequick-tadapterwithsealing
gasket(thesetincludesthreedifferentadapters).
CAUTION
CAUTION
Ensurethattheadapteristtedtoaxedwateroutletsuch
asawall-mountedshowerorfree-standingtap.
Fittingattheendofaexibleshowerhoseisnotpermitted
becauseoftheuncontrolledoutowofushingwaterand
possibleresultantwaterdamage.
Whenthetransparentcoverisremovedtheunit
electronicscanbedamagedbywateringress.
Forthisreasonalwaysdetachtheushingsystem
beforeprogrammingitorchangingthebattery.
Ensurethatyoualwaysprogrammetheushing
systemandchangethebatteryinadryenvironment.
WARNING
Iftheushingsystemisusedwithoutnon-returnvalves
beingttedorworking,anybackpressurefromthe
hotwatersupplyriskscontaminatingthewholeofthe
drinkingwatersupplysystem.
Non-returnvalvesshouldbettedonboththehotwater
andcoldwatersupplypipestothetap.
Theushingsystemshouldnotbeusedwithout
functioningnon-returnvalvesinplace.
76
Connectthesnapcontactoftheushingsystemto
thebattery.Removetheprotectivelmfromthebatteryif
necessary.Oncethebatteryisinstalledthesystemperforms
asystemcheckinwhicheachoftheLEDsashesoncein
turn.
Programtheushingdevice,ifnecessaryrefertosection
8.3.
Replacetheblackcoveronthebatterycompartmentand
screwthetransparentcoverbackintoplace.
Emptythewashbasinandcheckthatthewatercanow
awayfreely.Fixthewaterlevelswitchtotheinneredge
ofthewashbasinwiththeoatpointingverticallydown-
wards.
Wetthesuctioncupwithwatersothatitholdsrmlyto
thesideofthebasin.Ensurethatthecableisnothan-
gingdownandpullingonthesuctioncup.
MoistentheO-ringoftheFLUSHcouplingwithwater(for
easierandsaferinstallation);thenpushthecouplinginto
theadaptorwithaslightturningmovementandlockthe
FLUSH2.0inplacewiththeU-clamp.Checkthatthe
ushingsystemisseatedsecurely.
Turnonthetapandnowatershouldow.
Carryoutatestush(seesection8.3)
Regularchecks:
Every4weeks:
• Checkforpotentialblockingofthewashbasin.
• Checkthatthewatercanowawayfreely.
• Checkthatthelevelswitchiscorrectlypositioned,
securelyxedandtheoatabletomovefreely.
• Ifnecessarypositionthelevelswitchandsuctioncup
correctly.Replacedamagedsuctioncupifrequired.
Every6months:
• Checkthefunctionoftheushingsystem:testthema-
nualmodeofdrawingwaterandcarryoutatestush,
seesection8.3.
Yearly:
• Replacethebattery,renewthebatterychangesticker
NOTE
CAUTION
Theushingprogramcannotbeactivatedifthebattery
voltageistoolow.Inthiscasethe“DELAY”,
“FREQUENCY”and“RUNTIME”LEDsashandthe
batterymustbereplaced.
Ifthedrainisblockedorthelevelswitchwronglytted,
watercannotrunawaycreatingariskofoverow.
Makesurethatnoobjectscanobstructtheowofwater
andthatthewatercandrainawayfreely.
Ensurethatthesuctioncupiscorrectlyttedandsecurely
xed.
Checkthatthelevelswitchiscorrectlyoriented;theoatmustbeableto
movefreelyandmustpointdownwards.
988
Afteruse:
Turnoffthetap,removetheU-clampanddisconnectthe
FLUSHunit.
Todeactivatetheushingelectronicsunscrewthe
transparentcoverandremovetheblackbatterycover.
ThendisconnectthebatteryfromtheFLUSHunit.
Releasethelevelswitch.
Drytheushingsystemandstorethecomponentsinthe
caseprovided.
Replacethetapaeratororshowerhoseasappropriate.
8 Programmingtheushingsystem
8.1 Operatingprinciple
DELAY:Preselectionofstartingtime/delaybeforethe
rstush
Example:DELAY=2h
Therstushbeginsin2hours.
FREQUENCY:Pausebetweenushes
Example:FREQUENCY=24h
Flushesarerepeatedevery24hours.
Theushingsystemiscontrolledwiththethreekeyslabelled
“SET”,“+”and“-“atthebottomoftheoperatingpanel.
8.2 Defaultsettings
Thedefaultsettingsoftheushingsystemareasfollows:
DELAY: 0minutes
FREQUENCY: 24hours
RUNTIME: 5minutes
Toactivatetheushingsystempressthe“SET”key
andholditdownforatleastveseconds.Successful
programmingisindicatedbytheashingofoneLED
fromtheleft-handrow.
TheLEDsareturnedoffafteroneminuteofinactivity.Ifone
ofthethreekeysispressedforthreesecondsthedisplayis
turnedonagain.
8.3 Examples
Thefunctiontobechangedcanbeselectedbypressingthe
“SET”keyrepeatedly.Therequiredtimescanthenbeset
withthe“+”and“-“keys.
Thefollowingillustratedexamplesprovideexplanationofthe
differentfunctionsavailable:
NOTE
NOTE
9
Afterthebatteryhasbeenconnectedtheushing
programdoesnotstartuntilyouholdthe“SET”key
downforatleast5seconds!
Afterthe“+”and“-“keyshavebeenreleasedthe
mostrecentvaluesarestored.Thesenewtimeswill
beusedforthenextushingcycle.
1110
RUNTIME:Durationofushing
Thevalveisopenedbypressingthe“+”key.
Thevalveisclosedbypressingthe“-“key.
9 TroubleShooting
Thefollowingtableprovidestypicalerrormodesansesolu-
tionfortheFLUSH2.0unit.Ifyourerrorisnotlistedplease
contactyourlocalAquafreerepresentative.
Error Cause Procedure
Flushing
programme
doesnotrun
Watersupply
faulty
Checkthatthetap
andanyisolation
valvesareopen
Theushing
programhasnot
beensaved
PressSETkeyfor
5seconds
Thebatteryisat
(the“DELAY”,
“FREQUENCY”
and“RUNTIME”
LEDsare
ashing)
Changethebattery
Levelswitch
incorrectlytted
Checkthatthe
levelswitchcan
movefreelyand
theoatispointing
downwards
Levelswitch
comesaway
fromsideof
washbasin
Washbasinisnot
clean
Checkthatthe
surface of the
washbasinis
clean,dryandfree
ofgrease
Suctioncupisnot
clean
Checkthatthe
surface of the
suctioncupis
clean,dryandfree
ofgrease
Leakage
betweenwater
outletand
FLUSHunit
Faultysealing
gasket
Checkthesealing
gasketsand
replaceanythat
aredamaged
MANUAL:Modefordrawingwatermanuallyand
checkingthefunctioningoftheushingsystem
(testush)
Example:RUNTIME=5‘:Flushingcontinuesfor5minutes.
Timescanbeincreasedwiththe“+”key.
Timescanbereducedwiththe“-“key.
GEBR-ANWFLUSH-GB-03/2018-V002
10 Manufacturer
Aqua freeSolutionsLtd.
TheMediaCentre,7NorthumberlandStreet
Hudderseld,HD11RL
Great Britain
E-Mail: [email protected]
Phone: +44(0)1484483045
Headquarters:
Aqua freeGmbH
Winsbergring31
22525Hamburg
Germany
Phone: +49(0)40468999702
Fax: +49(0)4046899999
www.aqua-free.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7

Aqua Free FLUSH 2.0 Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI