Multiple Unit Piping and Flushing
Often projects require more than one heat pump. Where
possible, it makes sense for multiple units to share a common
ground loop. Common ground loops for multiple units bring
new challenges including the need to avoid backward ow
through inactive units, increased pumping requirements,
and more complex ushing needs. Three types of multiple
unit systems are described below along with guidelines for
installation of each type.
vFlow™ internal variable ow technology is a great assist
for systems with multiple units. vFlow™ is available in three
different congurations:
1. Internal variable-speed pump
2. I
nternal modulating valve for closed loops
3. Internal modulating valve for open loops
The internal modulating valve for open loops version should
never be used on closed loops.
The internal variable speed pump version of vFlow™includes
an internal Magna variable speed circulator controlled by
the DXM2 microprocessor, internal 3-way ushing valves,
an internal bladder type expansion tank, and front-mounted
pressure ports that allow access to the pressure drop across
the coaxial heat exchanger only. The Magna pump includes
an internal check valve. The pump curve for the Magna
circulator is shown in Figure 6. The internal expansion tank
will operate as a pressure battery for the geothermal system.
It will absorb uid from the loop when loop pressure rises
and inject uid into the loop when loop pressure falls. In this
way the expansion tank will help to maintain a more constant
loop pressure and avoid at loops due to seasonal pressure
changes in the loop.
When using the internal variable speed pump as the loop
pump in multiple unit installations it is important to ensure
that the variable speed pump can provide adequate ow
through the heat pump against the loop head when all units
are operating.
Units with UPM Geo pumps should not be combined with
units with Magna Geo pumps on the same loop. UPM Geo
units are best suited for small applications with a single
geothermal heat pump.
It may be possible to ush a multiple unit system through
the unit’s ushing valves. Flushing pressure drop of the
valve may be calculated to determine if it is acceptable.
Engineering data for the 3-way ushing valves can be found
in Table 3.
For example, if a system includes two 2-ton units and four ¾
loop circuits we can calculate the ushing pressure drop as
follows. From Table 2 we know that it will take 4 gpm to ush
each ¾” circuit. If there is no provision to isolate the circuits
for ushing, we will have to ush with a minimum of 4 circuits
x 4 gpm/circuit = 16 gpm total. A check of other piping sizes
used must be done to ensure that 16 gpm total ow will ush
all piping.
Pressure drop through the ushing valve can be calculated
using the following formula.
ΔP = (GPM/Cv)
2
where,
ΔP = pressure drop in psi through the valve while ushing
GPM = ushing ow in gallons per minute
Cv = valve Cv in ushing mode
We know from Table 3 that the Cv for the ushing valve in a
HZS/P024 is 10.3 in the ushing mode (90° ow). Therefore,
ΔP = (GPM/Cv)
2
= (16/10.3)
2
= 2.4 psi per valve (there are
two ushing valves). So long as the ushing pump is able to
provide 16 gpm at the ushing pressure drop of the loop plus
the 2.4 x 2 valves = 4.8 psi of the ushing valves, the internal
ushing valves may be used. If the ushing pump is not able
to overcome the pressure drop of the internal ushing valves,
then larger external ushing valves must be used.
Unit Conguration
Multiple vFlow™ units with internal variable-speed ow
controller and check valve, piped in parallel sharing a
common loop MUST be congured for ‘VS PUMP PARALLEL’
in Installer Settings Menu.
Installer Settings
System Cong Unit Cong
Loop Cong
Multiple Units with Internal Flow Controllers
The simplest multiple unit system is one with two (or more)
units utilizing internal Flow Controllers with no external
pumps or ushing valves. In this case the units are piped
in parallel and use the internal ushing valves to ush the
system. The variable speed pump includes an internal check
valve to prevent back (short circuiting) ow through the units.
In this case, ush the loop through the internal ushing
valves in the unit farthest from the loop rst. Once the loop is
ushed, then change the internal ushing valves to ush the
heat pump. Next, move the ushing cart to the next closest
unit to the loop.3
Table 3: Internal 3-Way Flushing Valve Data
Model
Flushing
Connection
Straight
Flow Cv
90°
Flow Cv
HZS/024 - 036 1" FPT 25 10.3
HZS/048 - 060 1" FPT 58 14.5