Eaton PXM4K Series Quick start guide

Type
Quick start guide

Eaton PXM4K Series is a powerful and versatile meter that provides accurate and reliable measurements of electrical parameters. With its advanced features and user-friendly interface, the PXM4K Series is an ideal choice for a wide range of applications, including energy monitoring, power quality analysis, and load management.

some of the key capabilities of the Eaton PXM4K Series include:

  • High accuracy: The PXM4K Series meters meet or exceed ANSI C12.20 Class 0.5 accuracy standards, ensuring precise and reliable measurements.

  • Wide measurement range: The PXM4K Series meters can measure a wide range of electrical parameters, including voltage, current, power, energy, power factor, and harmonics.

Eaton PXM4K Series is a powerful and versatile meter that provides accurate and reliable measurements of electrical parameters. With its advanced features and user-friendly interface, the PXM4K Series is an ideal choice for a wide range of applications, including energy monitoring, power quality analysis, and load management.

some of the key capabilities of the Eaton PXM4K Series include:

  • High accuracy: The PXM4K Series meters meet or exceed ANSI C12.20 Class 0.5 accuracy standards, ensuring precise and reliable measurements.

  • Wide measurement range: The PXM4K Series meters can measure a wide range of electrical parameters, including voltage, current, power, energy, power factor, and harmonics.

For detailed information concerning the operation and features
available in the PXM4/6/8K Meter Display - 6” Color Touchscreen
(PXM468K-DISP-6), please refer to PXM4/6/8K Meter Color
Touchscreen Display Features (IB150004EN) available on the Eaton
website (www.eaton.com/meters).
Figure 1. Dimensions of the PXM4/6/8K Meter Display - 6” Color
Touchscreen (PXM468K-DISP-6).
Installation
1. Disconnect and lockout all power to the enclosure.
2. Inspect the enclosure door to determine the best mounting loca-
tion for the PXM4/6/8K Meter Color Touchscreen Display.
ote:N A minimum clearance of 2.4 in. (61.0 mm) must be maintained
between the ventilation holes in the back of the display and any other
component within the enclosure.
3. Use the mounting template to mark the cutout area on the enclo-
sure door. Cut out the marked area.
7.24
(183.9)
0.063~0.240
(1.6~6.1)
5.67
(144.0)
Effective January 2015
Technical Data TD150015EN
PXM4/6/8K Meter Color Touchscreen
Display Quick Start Guide
Figure 2. Cut Out Dimensions.
4. Insure proper gasket placement on the PXM4/6/8K Meter Color
Touchscreen Display.
5. Insert the PXM4/6/8K Meter Color Touchscreen Display through
the cutout. Secure by finger tightening the supplied fasteners.
Figure 3. Mounting the PXM4/6/8K Meter Display.
6. Check for proper alignment of the PXM4/6/8K Meter Color
Touchscreen Display then torque fasteners to 6 lb-in. (0.7 N·m).
Connections
To use the PXM4/6/8K Meter Color Touchscreen Display, provide 24
Vdc and connect the power cable between the Color Touchscreen
Display and the PXM4/6/8K Meter.
The display’s plug-in terminals provide connections for +24 V,
Common (0), and GND.
6.79
(172.5)
0.12 (3.1) R
Typ.
5.2
(132.1)
Cut Out Dimensions
Technical Data TD150015EN
Effective January 2015
PXM4/6/8K Meter Color Touchscreen
Display Quick Start Guide
Eaton
Electrical Sector
1000 Eaton Boulevard
Cleveland, OH 44122
United States
877-ETN-CARE (877-386-2273)
Eaton.com
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD150015EN / TBG001189
January 2015
Eaton is a registered trademark.
All other trademarks are property of their
respective owners.
Figure 4. Power and COM Port Connections for the PXM4/6/8K Meter Display Touch Screen Display.
PXM Display Power Cable
PXMCM-1
COM 1 RS485
Display Connection
PXM Display Data Cable
PXM Display Power Cable
PXM468K-DISP-6
SHIELD WIRE TERMINATED TO DB9 SHELL
1.5
(38.1)
72.0
(1828.8)
72.0
(1828.8)
1.5
(38.1)
1.5
(38.1)
COM 0 only for PXD-MMG Display
PXMCM-1
COM 1 RS485
Display Connection
Included with the PXM4/6/8K Meter Color Touchscreen Display is a
data cable to connect DB9 COM 2 of the Color Touchscreen Display
to 3-terminal COM 1 (RS485) of the PXM4/6/8K Meter.
The supplied cables are designed to connect the meter to the
PXM4/6/8K Meter Color Touchscreen Display as follows:
Data cable: CM3
Power cable: CM4
Figure 5. Meter Web Server Configuration Screen Com 1 & 2
Setup.
In order to communicate with the display, the meter must be config-
ured as “Slave (RTU).This can be set using the meters web server
configuration page for Com 1 & 2.
For best results, use the default communication settings for the
PXM4/6/8K Meter and PXM4/6/8K Meter Color Touchscreen Display
(115.2 kbps, 1 start bit, 1 stop bit, no parity).
ote:N By default, the PXM4/6/8K Meter Color Touchscreen Display is preset
for a PXM4/6/8K Meter slave address of “01”. To accommodate a differ-
ent slave address, the User MUST Change the PXM4/6/8K Meter Color
Touchscreen Display’s “PLC DEFAULT STATION”.
Figure 6. Changing the PLC Default Station.
  • Page 1 1
  • Page 2 2

Eaton PXM4K Series Quick start guide

Type
Quick start guide

Eaton PXM4K Series is a powerful and versatile meter that provides accurate and reliable measurements of electrical parameters. With its advanced features and user-friendly interface, the PXM4K Series is an ideal choice for a wide range of applications, including energy monitoring, power quality analysis, and load management.

some of the key capabilities of the Eaton PXM4K Series include:

  • High accuracy: The PXM4K Series meters meet or exceed ANSI C12.20 Class 0.5 accuracy standards, ensuring precise and reliable measurements.

  • Wide measurement range: The PXM4K Series meters can measure a wide range of electrical parameters, including voltage, current, power, energy, power factor, and harmonics.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI