Dometic Basic Chiller Control Operating instructions

Category
Thermostats
Type
Operating instructions
BasicChillerControl
OperationsManual
DometicGroupMarineDivision
Rev.20180709
L3527English
P/N338238
COPYRIGHT©20112018Dom et icGroupMarineDivision.AllRightsRes erved.
Nopartofthispublicationmaybere produced,t ranslated,storedinaretrievalsystem,ortransmittedinanyformorbyanymeanselectronic,
mechanical,phot ocopying,recordingorotherwisewithoutpriorwrittenconsentbyDometicMarine.Everyprecautionhasbeentakeninthe
preparationofthismanualtoinsureitsaccuracy.
However,DometicMarineassumesnoresponsibilityforerrorsandomission.Neitherisany
liabilit yassumedfordamagesresultingfromtheuseofthisproductandinf ormationcontainedherein.
Tableof
Con
t
en
t
s
INTRODUCTION............................... 3
PGD1NAVIGATION ............................ 3
TOUCHSCREENNAVIGATION................... 2
M
AIN PAGE................................. 2
C
HILLER ENABLE ......................... 2
CHILLER SUMMARY .......... ....... ....... 2
C
HILLER STAGE .......................... 2
T
RENDS ................................ 2
A
LARMS ................................ 2
R
EMOTE SUPPORT........................ 3
LOGO ........ .......................... 3
OFFI
CON .............................. 3
COOL ICON .............................. 3
H
EAT ICON ............ .................. 3
E
LECTRIC HEAT ICON:ONLY IF OPTION
IS
INSTALLED
.............................. 3
S
ETPOINT THERMOMETERS .................. 3
GENERALINFORMATION...................... 4
DIGITALINPUTS............................. 4
S
AFETY INPUTS .................. ............ 4
FSC
HILL WATER FLOW SWITCH ................ 4
R
EFRIGERANT HIHIGH SIDE PRESSURE LIMIT ...... 4
R
EFRIGERANT LOWLOW SIDE PRESSURE LIMIT .... 5
ANALOGINPUTS.............................. 5
H
IGH LIMIT TEMPERATURE .................. .... 5
F
REEZE TEMPERATURE .. ...................... 5
PRESSURETRANSDUCERS .................... 5
S
UCTION……………………………………......... 5
D
ISCHARGE ……………………….……………....... 5
RELAYOUTPUTS............................ 6
COMPC
OMPRESSOR..... ............... ... 6
CWPC
HILL WATER PUMP ............. ...... 6
SWPS
EA WATER PUMP ............. ........ 6
RVR
EVERSING VALVE.... .................. 6
EHE
LECTRIC HEAT .......... .............. 6
F
AULT ................. ......... .......... 6
SYSTEMOVERVIEW............
...............6
S
YSTEM POWERUP.. ........................6
SOFTWARE REVISION......................6
S
TARTUP........... .......................6
O
PERATIONAL CHECKS........................6
S
ETPOINTS................. ......... .......6
C
OOLING ...............................6
H
EATING ...............................7
COMPRESSORSTAGINGTIME..............7
RUN MODE COOLING...................... ..7
R
UN MODE REVERSE CYCLE HEATING........... 7
R
UN MODE ELECTRIC HEATING................7
OPERATIONALMODES ........................7
P
UMP OPERATION...........................7
C
HILLED WATER PUMP............... .....7
SEA WATER PUMP ................. ......7
C
OOLING MODE .......................... ...8
H
EATING MODE .............................8
STATUSSCREENNAVIGATION.................. 8
APPENDIXI:NAVIGATIONTREE..................14
APPENDIXII:INSTALLATION&SETUP
PROCEDURES...................
..............24
InitialWiring
............................. ..24
BasicWiringDiagram.............. ..
........25
FirmwareCompatibility.......................26
Networking................................27
SettingTimeandDate............. ..........30
ElectricHeat...
............ ......... .......31
SelectTemperatureType..................
...32
APPENDIXIII:ALARMTABLE....................33
APPENDIXIV:DEFAULTPARAMETERS............34
3
INTRODUC
T
I
ON
TheDometicPLCcontrolsisamicrocontrollerbasedunitdesignedtocontrolmultiplechillers.Thisdesignallowstheuserflexibility
intheapplicationandimprovedcontrolsandprotection.ThePLCChillerus estemperaturedifferentialandhysteresistomanage
thecapacityofthechillerinsingleormultis tage application.
Thisapplicationsupportsthefollowing:
o Selectionandsequencingofuptosixchillers
o Selectionandsequencingofonechillwaterpumpandoneseawaterpump
o Selectionandsequencingofupto6EHheaters
o Sequencingofde vicesforruntimeequalization
o Alarmsandinterlocks
o Troubleshootinghelp
Themaininterfacesupported
willbetheLCDdisplay,referredtoasthePGD1display.
Figure
1:
PGD1Button
De
sc
r
i
ptio
n
PGD1
NA
V
IGA
T
I
ON
EnterButton
ThePGD1controllerscreenwillautomaticallybootuptotheMainscreen.Thisscreenallowsyoutoenableordisablethechillerby
pressingtheEnterbutton.PressingtheEnterbuttonwilltakeyoutotheareaofscreenyouwishtomodify.Pressentermultipletimesif
requiredto scroll
downtotheareayouwishtoselect.
ScrollUp/DownButtons
Thisbuttonwillbeusedtomodifythevaluesuchastemperaturesetpointorprobeadjustmentvalues.TheScrollUporScrollDown
buttonwillalsonavigateyoufrompagetopageofthecontroller.Theflashingcursormustbeintheupperlefthandcorn erforthepage
navigation.Pressing
enterrepeatedlywillmoveittothatlocation.
EscButton
TheEscbuttonisusedtoexityourpresentscreenandtakeyoubackonescreen.Pressingitmultipletimeswilltakeyoubacktothe
Mainscreen.
PrgButton
Thisbuttontakesyoutothesystemmenus.Onceatthemenus,usethescrollbuttonstoscrollthroughthevariousoption s.Pressing
enterwillselectthatmenuitem.
ScrollDown
ScrollUp
Enter
AlarmIndicator
ProgramMode
EscapetoExit
4
AlarmButton
Thisbuttonwillflashredifthereisanactivealarm.Pressingthisbuttonwilltakeyoutotheactivealarmscreentodisplaythealarm.
Onceinthealarmscreen,usetheup/downbuttonstoscrollthroughalarms.TheAlarmscreencapturesasnapshotofthesystem
parametersatthe
timeofthefault.PressandholdtheAlarmbuttonfor3secondstocleartheactivealarmifthefaulthasbeen
corrected.
GE
NE
RALINFORMATION
TheDometicPLCcontrolsisamicrocontrollerbasedunitdesignedtocontrolmultiplechillers.Thisdesignallowstheuserflexibility
intheapplicationandimprovedcontrolsandprotection.ThePLCChillerusestemperaturedifferentialandhysteresistomanage
thecapacityofthechillerinsingleormultistageapplication.
Thechillersystemwillcomeprogrammedfromthefactorywiththeoptionsenabledforthatsystem.Althoughthesystemoffers
flexibility,theseoptionscanonlybeenabledbyafactoryrepresen tative.
TheuserwillbeabletoselectbetweenCool,HeatorElectricHeatmodeoperationinsinglestageconfigurationorIna
multistage
configuration.
ThePLCcontrollerisinte rnallygroundedwithisolationbetweeninputsandoutputs.Additionally,theoutputrelaysofferdouble
isolationsothatdifferentvoltagescanbeusedforgroupsofrelays.
Thesystemwillutilizevarioussensortypesformeasuringanalogtemperaturesandpressures.Fortemperaturemeasurements,the
systemwilluseNTCtype10K@77°thermistors.Pressuretransducersareratiometric0650PSI(45bar)rangeforbothsuctionand
dischargemonitoring.
AvailableOptions:
1. CompressorCurrentMonitoring
2. PumpCurrentMonitoring(SWandCW)
3. CondenserFreezeProtection
4. ElectricHeat
5. EEVControl
6. PressureTransducers
7. LoadSheddingInputSignal
8. LowCurrentAlarmtoindicateifsystemisnotactuallyrunningwhenenabled.(PumpsandCompressor)
9. Return
orSupplyWaterControl
DIGITAL
IN
PUTS
Digitalinputsareusedtomonitorthestatusoftheprotectioncircuitsforthesystem.
SAFETY I
NP
U
T
S
Alldiscreteinputswillbecheckedbeforethesystemwillbeenabled.Anyfaultsdetectedonstartupmustbeverifiedandcleared
viathePLCbeforesystemwillstartnormaloperation.
FS
CHILLED WATER FLOW
SWIT
C
H
WiththesystemineitherheatingorcoolingmodetheFlowswitchmustbeclosedpriortosystemstartingorastagebeingenabled.
InoperationifFlowislostformorethan10consecutiveseconds,thecompressororheatrelaywillbedisabled.Aflowswitchfault
willbe
recordedanddisplayed.
ACWFlowfaultwillberecordedandsystemwillbeinlockoutandamanualrestartwillberequired.ThePLCwillnotallowthecompressor
orelectricheatrelaytobeenergizedforthestagethathaslostfloworthewholesystemifacommonflowswitchisbeingused.
FaultmustbemanuallyacknowledgedviathePLCandclearedpriortoreenablingthesystemorstage.
REFRIGERANT
HI
HIGH SIDE PRESSURE
L
IM
I
T
ThePLCwillimmediatelyacknowledgeanopencircuitiftheHIpressureswitchistrippedanddeenergizethecompressor.Itwillrecord
anddisplayhighpressurefaultonthealarmscreen.IfthePLCdetectsahighpressurefaultduringoperation,aHPfaultwi llbedisplayed
andrecorded.
ThePLCwillnotallowthecompressorrelaytobereenergized,un tilswitchisintheclosedposition.
ThefaultmustbemanuallyacknowledgedviathePLCandclearedpriortore enablingthesystemorstage.
5
REFRIGERANT LOW
LOW SIDE PRESSURE
L
IM
I
T(Optional)
ThePLCwillimmediatelyacknowledgeanopencircuitifthelowpressureswitchistrippedanddeenergizethecompressor.Itwill
recordanddisplaylowpressurefaultonthealarmscreen.IfthePLC detectsalowpressurefaultduringoperation,aLPfaultwillbe
displayedandrecorded.
ThePLCwillnotallo wthecompressorrelaytobereenergized,untilswitchisintheclosedposition.
ThefaultmustbemanuallyacknowledgedviathePLCandclearedpriortoreenabling thesystemorstage.
ANALOGINPUTS
HIGH LIMIT
T
E
M
P
ERA
TU
RESETPOINT
ThehighlimittemperaturesensoriscontinuouslymonitoredwhetherinCooling,ReverseCycleorElectricHeatmode.
Thissensorisusedtodetectahightemperatureconditioninthesupplywaterfromthechiller.Ifthech illedwatertemperatureissensed
tobegreaterorequalto125°F(51.7°C),allenabledcompressorrelayswillbedeenergized,turningoffthecompressor(s)ifoperating
inreversecyclemode.If
electricheatisbeingused,allenabledheaterrelayswillbedeenergized,turningofftheheatingelement(s).
Asthetemperaturefalls,thecompressororelectricheatrelaywillreenergizewhenthetemperaturereaches110°F(43.3°C).
Ahightemperaturefaultwillberecordedanddisplayedifthesystemexceeds
thealarmsetpoint.Inahightemperaturesituation,PLC
willnotallowthecompressororelectricheatrelaytobeenergized.Thefaultmustbemanuallyacknowledgedontheactivealarm
screenandclea redpriortoreenablingthesystemorstage.
Ifatemperaturesensorisbadornotconnected,thePLCwilldisplayanalarmforthatsensor.
FREEZE
T
EM
P
E
R
A
T
U
RESETPOINT
ThelowlimittemperaturesensoriscontinuouslymonitoredwhetherinCooling,ReverseCycleorElectricHeatmode.
Thissensorisusedtodetectafreezeconditioninthesu pplywaterofthechiller.Ifthechilledwatertemperatureissensedtobeequalto
or less than38°F(3.3°C),thenthe compressor relaywill be deenergized,shuttingoff thecompressor. As the temperature rises, the
compressorrelaywillreenergizewhenthetemperaturereaches42°F(5.6°C).
Alowtemperaturefaultwillberecordedanddisplayedifthesystemfallsbelowthealarmsetpoint.Inalowtemperaturesituation,
PLCwillnotallowthecompressororelectricheatrelaytobeenergized.Thefaultmustbemanually
acknowledgedontheactivealarm
screenandcleare dpriortoreenablingthesystemorstage.
Ifatemperaturesensorisbadornotconnected,thePLCwilldisplayanalarmforthatsensor.
CondenserFreezeProtection(Optional)
Thesystemisequippedwithatemperaturesensormountedtothecondensercoil.Thissensoristheretosensethecoiltemperature.In
heatmodeifthecoiltemperaturedropsbelow40°F,thePLCcontrolswillautomaticallylowerthespeedofthecompressortohalfthe
speedthatitwas
currentlyrunning.Thedisplaywillindicate“FreezeDefrost”whileperformingthisoperation.
PRESSURE
TR
AN
SD
UCERS
SUCTION Pressure
ThesuctionpressureiscontinuouslymonitoredbythePLC.Ifthesuctionpressureisbelowthealarmsetpointforlongerthanthe
programmedtimedelay,afaultwilloccur .Thislowsuctionfaultwillberecordedanddisplayedonthealarmscreen.
ThefaultmustbemanuallyacknowledgedviathePLCandclearedpriortoreenablingthesystemorstage.
DISCHARGE Pressure
ThedischargepressureiscontinuouslymonitoredbythePLC.Ifthedischargepressureisabovethealarmsetpointforlongerthanthe
programmedtime,afaultwilloccur.Thishighpressurefaultwillberecordedanddisplayedonthealarmscreen.
ThefaultmustbemanuallyacknowledgedviathePLCandclearedpriortoreenablingthesystemorstage.

6
RELAYOUTPUTS
COMP
C
OMPR
E
SSOR
PLCCOMPoutputwillprovideswitchedpowertothecontactorcoiltoenablethecompressornormaloperation.
CWP
CHILL WATER
P
UM
P
PLCCWPoutputwillprovideswitchedpowertothecontactorcoilsforthechilledwaterpump.
SWP
SEA WATER
P
UM
P
PLCSWPoutputwillprovideswitchedpowertothecontactorcoilsfortheseawaterpump.
RV
REVERSING
VAL
VE
PLCRVoutputwillprovideswitchedpowertothecoilsforthereversingvalve.
EH
ELECTRIC
H
EA
T
PLCEHoutputwillprovideswitchedpowertothecontactorcoilsfortheelectricheat.
F
AULT
Provid esaNormallyOpen(NO)contactpoint.AnyfaultconditionwillclosetheNOcontact.Thisoutputcanbeusedtopoweralight,
relay,orinterfacetoaship’smonitoringsystem.Theoutputonthisterminalwillbe230VAC.
SYSTEM
OVERVIE
W
SYSTEM
P
OWER
UP
SOFTWARE REVI
S
I
O
N
Uponapplyingpowertothesystem,thedisplaywillindicatethesoftwarerevisionnumberordisplayitonthemainstatus
screen.
PLCisenabledandwaitingforuserselection.
MODBUS
ThePLCcomeswitha3wireModbusconnectionaspartoftheelectricalbox.Thisconnectionisusedformultistageconfigurationand
networkingtoaboatmanagementsystem.
S
TA
RT
UP
ThePLCChillercontrollercanbeoperatedasasingleoramultistagechillerplant.Duringinitialsetup,thesystemwillbeconfiguredfor
thenumberofstagesandtheavailableoptions.SelectbetweenReturnwaterorSupplywatercontrol.Theuserhastheoptiontoselect
betweenmetricvalues
beingdisplayedorImperialvaluesbeingdisplayedduringoperationofthesystem.
ChilledwatersetpointwillbeenteredforCoolandHeatmode.
Onceenabled,CWandSWpumpswillbeturnedonforoperation.
OPERATIONAL
CHECK
S
OncethePLCisenabledthesystemwillconductprestartupchecks.ThePLCprogramwillcheckallCWflowswitchesforfaults.ThePLC
willalsocheckHPandLPswitchesforfaults.
Individualstagefaultswillonlydisablethatstage.
S
ET
POI
N
T
S
C
OO
LI
N
G
CoolingsetpointisanadjustableparameterforReturncontrol(default)from48°F(8°C)to58°F(14°C)inonedegreeincrementsandfor
Supplycontrolfrom42°F(5°C)to58°F(14°C).Toadjustthecoolingsetpoint,simplytouchthe PLCscreenandchangetodesirednewset
point.Incooling
modeyouwillnotbeabletoenteranumberoutsideofthisrange.
7
H
EATING
Heatingsetpointisanadjustableparameterfrom95°F(35°C)to120°F(49°C)inonedegreeincrements,forbothReturn&Supply
control.Toadjusttheheatingsetpoint,simplytouchthePLCscreenandchangetodesirednewsetpoint.Inheatingmodeyouwillnot
beabletoenteranumberoutsideofthisrange.
C
OMPRESSOR
S
TAGING
T
IM
E
CompressorstagingtimeisaPLCadjustableparameterfrom10secondsto110secondsin10secondincrements.Toadjustthestaging
time,simplytouchthePLCscreenandchangetodesirednewsetpoint.Userwillnotbeabletoentera numberoutsideofthisrange.
OncethePLCinitiatesacoolingcycle,thestagingtimeisthetimeitwilltake(inseconds)forthenextcompressorrelaytoclose.
RUN MODE
C
OOL
ING
Compressorrotationisactiveduringrunmode.Thecompressorwiththelowestrunninghourswillbeenabledfirstandcompressorwith
thehighestrunninghourswillbedisabledfirst.
Firststag ewillbeenabledandthecompressorwillstartafterCWandSWflowsarestablefor10seconds(default).
Firststagewillcontinuetorunfor1minutebeforeenablingthenextstage.Ifthelooprequiresdemand,thenthenextstagewillbe
enabled.
R
UN
M
ODE
R
EVERSE
C
YCLE
H
EA
TI
NG
Compressorrotationisactiveduringrunmode.Thecompressorwiththelowestrunninghourswillbeenabledfirstandcompressorwith
thehighestrunninghourswillbedisabledfirst.
EnableReverseCycleHeatonlyforthesystem.
Firststag eheatingwillbeenabledandthecompressorwillstartafterCWandSWflowsarestablefor10seconds.
Firststagewillcontinuetorunfor5minutesbeforeenablingthenextheaterstage.Ifthelooprequiresdemand,thenthenextstagewill
beenabled.
R
UN
M
ODE
E
LECTRIC
H
EAT
I
N
G(optionalheaterbarrel)
Heaterrotationisactiveduringrunmode.Theheaterwiththelowestrunninghourswillbeenabledfirstandtheheaterwiththehighest
runninghourswillbedisabledfirst.
EnableElectricHeatonlyforthesystem.
Firststag ewillbeenabledandtheelectricheaterwillstartafterCWflow
isstablefor10seconds.
Firststag ewillcontinuetorunfor5minutesbeforeenablingthenextheaterst age.IfthePIDlooprequiresdemandthenthenex t
stagewillbeenabled.
OPERATIONAL
M
ODES
PUMP
O
PE
RA
TI
O
N
CHILLED WATER
P
UM
P
Thechilledwaterpumprelayshallcloseifthesystemisinheatmodeorcoolmode.Thepumpwillbeenabled5secondpriortothe
firststagebeingenabled.Pumpwillbeonforcontinuousoperationwhensystemisenabled
SEA WATER
P
UM
P
Theseawaterpumpwillhaveaselectableoperatingmodebetweencontinuousoperationorcyclewithcompressoroperation.
Thedefaultconfigurationistocyclewiththedemand.
Theseawaterpumprelayshallclose5secondsbeforethecompressorstartsinheatingorcoolingmodesandwillopen5seconds
afterthelas tcompressorcycleiscompleted.Ifimmersionheatingisavailableandused,theseawaterpumpwillbedisabled.
Inamultistage configurationthepumpoutputs
canbedaisychainedatthebackoftheunittosupplypowertothepumps.
Thiswillallowanystagetosu pplypowertothepumpswhenbein gstagedonandoffandasaredundantcontrolforthepumps.

8
COOLING
M
ODE
CoolingmodeisenteredwhenCoolisselectedonthetouchscreenorwiththedisplaybuttons.Thesystemwillautomatical lystartcooling
dependingontemperaturesetpoint.Thepumpswilloperateasdescribedinthepumpoperationsection.
Theboardwillenergizethecompressorrelayifreturnwater/supplywatertemperatureis
abovethecoolingsetpointandthestaging
delayhaselapsed.
Thecompressorwillcontinuetorununtilthecoolingsetpointhasbeenreachedoranalarmconditionexists.Astagewillhavea
minimumruntimeof100secondsbef oreitcanbeturnedoffandaminimumofftimeof
120secondsbeforeitcanbereenabled.This
minimumontimeisrequiredtoensurethatthesystemisnotcyclingonandoff andnotallowingthecompressortoproperlywarmup.
Thisensuresproperoillubricationofthesystem.Ifthesystemcallsforastagetobetoggledon/off,thenextavailablestagewillbeused
thatmeetsthestagingcriteria.Loadsheddingwilloccurinmultistageoperationwhenapproachingchilledwatersetpoint.Thereversing
valveistoggledtorelieveheadpressureattheendofacompressorruncycle.
HEATIN G
M
OD
E
ReverseCycleHeatingmodeisenteredwhenHeatisselectedonthetouchscreenorwiththedisplaybuttons.Thesystemwill
automaticallystartheatingdependingonthetemperaturesetpoint.Thepumpswilloperateasdescribedinthepumpoperationsection.
Thereversingvalverelaywillbeenergizedtochangethe
unittooperateinReverseCycleHeatingmode.
ThePLCwillenergizethecompressorrelayifreturn/supplywatertemperaturebelowtheprogrammedheatingsetpointandthestaging
delayhaselapsed.Thecompressorwillcontinuetorunandthereversingvalvewillremainenergizeduntiltheheatingsetpointhas
beenreachedoranalarmconditionexists.
ElectricHeatingmodeisenteredwhenElectricHeatisselectedonthetouchscreenorwiththedisplaybuttons.Thesystemwill
automaticallystartheatingdependingonthetemperaturesetpoint.
ThePLCwillenergizetheheaterrelayifreturn/supplywatertemperatureisbelowtheprogrammedsetpointandthestagingdelay
haselapsed
inamultistageconfigura t ion.
StatusScreenNavigation
Themainhomescreenisthestatusscreenwherethesinglestageoperationcanbereviewedorinamultistageconfigurationtheusercan
scrollandseethevaluesofthechilledwaterandotherparametersoftheadditionalstages.Theuserwillsimplyusethedownarrowkey
toscrollthroughthevariousparametersbeingdisplayedontheLCDscreen.TheLCDscreenwillalsoindicateonthemainscreenthe
modeofoperationwhetheritisCool,HeatorEHmode.Themainscreenwillalsoindicateifthereisanalarmpresentonthesystemby
flashingthewordalarminthelowerrighthandcornerorLoadsheddingifithasbeenactivated.
Figure2

9
Thefollowingscreenwillindicatethechilledwaterreturntemperaturethe chilledwatersupplytemperatureaswellasthecontrolsensor
temperaturewhichisthevaluebasedonthetypeofcontrolchosen.Returnwaterorsupplywatercontrolandthiswillbetheaveraged
valueofthenumberofstagesenabled.
Figure3
Thesecondscreenfollowingthemainscreenwillcontaininformationonthepumpstatus.
Figure4
Thethirdscreenwillcontainthechiller1informationorthewatertemperatures,thestatusofthesafetiesandcompressor. Thefollowing
screenswillcontaininformationfortheadditional
stagesenabledupto6stages.
Figure5
Thefinalscreenwillcontaintheimageoftherefrigerantcircuitandcontainthevalvepositioninformation.
Note:Screenordersmaydifferdependingonwhatfeaturesareenabled.

10
MainMenuItems:ScreenNavigationTree
Pressentertoselectitemstoviewandup/downarrowstoscrollthroughscreens.PressEsctoexitMenubeingviewedand
toreturntoMainStatusscreen.After3minutesofscreeninactivitythescreenwillautomaticallyreturntothemainstatus
screen.
MenuA:On/OffUnit
o UnitAddress: 1(Default)
o Mode Cool,Heat,EH,OFF
o Status: Displayed
MenuB:Setpoints:
CoolCntrl SP:45F
o StageUp StageDown
o SP+1F >>‐0F
o SP+3F >>‐2F
HeatCntrl SP:110F
o StageUp StageDown
o SP‐1F >> +0F
o SP‐3F >> +2F
SeawaterPumpControl:ByDemand(Default)orByUnitOn(ContinuousOperation)
Configuration:
o TemperatureUnits:F(Default)OrC
o PressureUnits: PSI(Default)orBar
MenuC:
Clock/Scheduler
o Date: Changedatehere.
o Hour: Changetimehere.
o Day: Displayed
NextScreen:
o DST: Enabled(Default)
o DescriptionFollows:
MenuD:Input/Output Viewvaluesorstatusofanalogsensors,digitalinputsorrelayoutputs.
o A:AnalogInputs:
o CWReturn
o InputB001: ActualValue
o ScrollforadditionalsensorvalueswithdownarrowbuttonthenESCtoexit.
o B:DigitalInputs:
o FlowSwitch
o DI3Status: ActualState(OpenorClosed)
o ScrollDownforadditionalactivedigitalinputs.Thiswillchangedependingonwhatisenabledinthesystem
configuration.
o C:RelayOutputs:
o SWPump
11
o Relay1Status: ActualState(ONorOFF)
o ScrollDownforadditionalactiverelayoutputs.Thiswillchangedependingonwhatisenabledinthesystem
configuration.
o D:AnalogOutputs:
o NOTUSED
MenuE:AlarmHistory
Willcapturethestatusofthefollowingparametersatthe
timeofthealarm.Themostrecentalarmwillbeshown.Useuparrowtoto
viewpreviousalarms.
o Alarmwillbedisplayedfollowedby:
o CWReturn: Actualvalue
o CWSupply: Actualvalue
o SeaWater: Actualvalue
o ControlValue: Actualvalue
MenuF:BoardSwitch
Thismenuallowsyoutochangetoviewadditionalboardsandmakechangestothatparticularboard.Thisonlyappliestoamultistage
configurationwhenunitsarenetworkedtogether.
o UnitAddress: 1(Default)
o Switchtounit: Desiredboardaddress
MenuG:Service
Somesubscreenswillrequirea
password.PleasecontactDometicforservicepassword.
Submenus:
SubMenuA:Information
o Theservicecontactinformationisavailableonthisscreen.
o Scrolltoviewadditionalfirmwareinformation.
o ThenextscreenwillcontaintheflashRAMinformation.
o Thenextscreenwillcontainthepowercyclestatuswhich
indicateshowmanydaystheunithasbeenrunninginthelast
timeitwasturnedofforon.
o ThenextscreenwillcontaintheEvofirmwareinformation.
SubMenuB:Commission
o Onthisscreenthetechnicianwillbeabletoenterthedealercontactinformation.Thedefault
contactinformationisthe
Dometiccontactinformation.Thentheuserwillselecttoupdatetheinformationbyselectingyesattheprompt.
o Thenscrolltothenextscreen.Onthescreentheuserwillbeaskedtocommissionthesystemandmustselectbetween
yesornothenpress
enter.Thiswillsavetheinformationandoncecommissionthatthestatecannotbechanged.
SubMenuC:WorkingHours
o Compressor
o Runhours: Actual
o NumStarts: Actual
12
Scrolltonextscreenstoviewpumpandelectricheathours(optionalifinstalled).
SubMenuD:BMSConfig
UsedonlyforconfigurationsystemtoworkwithSTIICnetwork.
o BMSPort1
o Protocol:Carel
o Adddress 1(Default)
o BaudRate 19200(Default)
SubMenuE:TestMode
o TestMode: Disabled(Default)
o Timeout: Disabled(Default)
SubMenuF:ServiceSettings
SubSubMenuA:WorkingHourSet
o Compressor
o ServiceSetPoint: 0000h(Default) Canbeusedtosetaserviceintervalforsystem.Willdisplay
messageonscreen.
o ResettoZero? NO(Default).
Usedtoresettherunhours
o Runhours: ActualValue. Usedtosettherunhoursifcompressororboardhasbeen
replaced.
Scrolltoviewadditionalitemssuchasthepumpsandelectricheatifinstalled.
SubSubMenuB:ProbeAdjustment
TempSensorCurve:Canselecta
differentsensorforretrofitsthathavethe30ksensor.
o CWReturn: 10k(Default)or30k
o CWSupply: 10k(Default)or30k
o SWInlet: 10k(Default)or30k
Tobeusedforcalibratingtheinstalledtemperaturesensorsorpressuretransducers.
o CWReturn
o InputB001
o Offsett
 0.0(Default)
o Value ActualValue
Scrolltoviewadditionalanalogsensorsforcalibration.
SubSubMenuC:Thermoregulation
Thismenuallowsyoutosetthesuperheatsetpoint.
o Superheat
o CoolSetpoint: 10F(Default)
o HeatSetpoint: 10F(Default)
Nextscreen
o SetpointSH: 10F(Default)
o
LowSHthresh: 2.0F(Default)
o LOPthresh: 30.0F(Default)
13
o MOPthresh: 82.4F(Default)
SubSubMenuD:UserSave
Thisisusedtosaveanyuserspecificsettings.
o Save? No(Default)Yes
o Restore? No(Default)Yes
o EnableAutoSave: Yes(Default)No
SubSubMenuE:StageAddress
Thismenuistobeusedinamultistage
configurationtochangetheadditionalunitaddresses.Thisistobedoneso
thattherearenoaddressconflictswhendaisychainingtheadditionalunitmodbusconnections.Thismustbedone
priortoconnectingalltheunitstogether.
o pLANBoardAddressing
o CurrentAddress: 1(Default)
o ChangeAddress
to:1(Default)
NextScreen
SystemSetup
o NumofStages 1(Default)Max6
SubSubMenu:FStageDisable
Thismenuistobeusedwheninamultistageconfiguration.Thisallowsatechniciantotakeastageofflinesothat
repairscanbemadeandtherest
ofthesystembeoperationalinautomode.Thesystemmustbeinanoffstateto
enablestagecontrol.
o Maintenance
o StageControl: No(Default)Yes.
IfEnabled,
o Stage1: Enabled(Default)Disabled
o Stage2: Enabled(Default)Disabled
o Stage3: Enabled(Default)Disabled
o Stage4:
 Enabled(Default)Disabled
SubMenuG:ManualManagement
Thismenuallowsthetechniciantomanuallyoperatetherelayoutputsaswellasenableordisableanalogsensors.
o SubSubMenuA:AnalogInput
o CWReturn
o ManualControlB001: Off(Default)On
o ManualPosition: ValueDesired
o
Value: ActualValue
Scrolltoadjustadditionalsensors
o SubSubMenuB:DigitalInput
o FlowSwitch
o ManualDI3: Off(Default)ON
o ManualPosition: Actual(EnterDesiredPosition)
o DIInputStatus: ActualValue
14
Scrolltoadjustadditionalinputs
o SubSubMenuC:RelayOutput
o SWPump
o ManualRelay1: OFF(Default)No
o ManualPosition: OFF(EnterDesired)
o RelayStatus: ActualPosition
ScrolltoadjustadditionalOutputs
o SubSubMenuD:AnalogOutputs
o NOTUSED
15
AppendixINavigationTree
MainStatusScreen
MainStatusScreen
CWSupplyTemp #.#°F
Mode Off/Cool/Heat/ElHt*
CWReturntemp #.#°F
CWSupplytemp #.#°F
ControlSensor #.#°F
Mode Off/Cool/Heat/ElHt*
PumpRelayOutputs
SWPump On/Off
CWPump On/Off
Chiller#1
CWreturntemp #.#°F
CWsupplytemp #.#°F
Flowstatus Ok/Alm/Off
Highpressurestatus Ok/Alm/Off
ElectricHeat*
Ok/Alm/Off
EHFL* Ok/Alm/Off
Compressor Ok/Alm/Off
SupplyTemp
Chiller1 #°F
FlowDiagram
SuperHeat #°F
Compressor #°F
TXVOpen #%
Steps #stp
SuctionPressure #psi
SuctionTemperature #°F
Legend
*Asteriskindicatesthisitemisonlyviewablewhen
activatedinthefactorysettings.
Asolidboxmeansthatitisasubmenuofthe
menuandneedstobeaccessedbypressingenter.
Adottedboxisabreakoutoftheadditional
informationthatiscontainedbelow
thatmenucategory.
16
Program
Program
Setpoints
Clock
Input/Output
AlarmHistory
BoardSwitch
Technician
Manufacturer
AnalogOutput
Valvestatus Stdby
Valveopening #.#%
Valveposition #stp
Coolcapacity #%
Superheat #.#°F
S1probe
Evap.Press #.# psig
Evap.Temp #.#°F
S2probe
SuctionTemp #.#°F
S1probe #.#psig
S2probe #.#°F
S3probe #.#psig
S4
p
robe #.#°F
Setpoints
Coolcontrol
Setpoint #°F
1StageUp #°F
1StageDown #°F
Heatcontrol
Setpoint #°F
1StageUp #°F
1StageDown #°F
SWPumpControl ByDemand/ByUnitOn
TemperatureUnits °F/°C
PressureUnits
p
si
/
bar
Clock/Scheduler
Date ##/##/##
Hour ##:##
Day #
DST Enable/Disable
Trans.Time #
Start #
End #
Input/Output
AnalogInput
DigitalInput
RelayOutput
AnalogOutputs
AnalogInput
CWReturnInputB001 ###
CWSupplyInputB002 ###
DigitalInput
HighpressureDI1 Open/Close
LowpressureDI2 Open/Close
WaterFlowDI3 Open/Close
ElHeatFlowDI5 Open/Close
HandCoolDI6 Open/Close
HandHeatDI7 Open/Close
RelayOutput
SWPumpRelay1 On/Off
CWPumpRelay2 On/Off
FaultRelay3 On/Off
CompressorRelay7 On/Off
ReversingValveRelay4 On/Off
BoardSwitch
Unitaddress: ##
Switchtounit: ##
Technician
Seepage#
Manufacturer
See
p
a
g
e#
AlarmHistory
Alarm# AlarmMessage
CWReturn #
CWSupply #
Controlvalve #
17
Program/Technician
BMSConfiguration
BMSPortNo. #
Protocol ######(scrolltoselect)
Address #
BaudRate #####
Technician
Information
Commission
WorkingHours
BMSConfiguration
Testmode
PumpControl
ServiceSettings
ManualManagement
Information
ServiceContactPhone ##########
Code: LEModule
Version &Date #.## ##/##/##
BIOS&Date #.## ##/##/##
Boot&Date #.## ##/##/##
FlashRam #Kb
Tmemory #
##Cycle/s #ms
PowerCycleStatus
LastOffTime ##/##/####:##:##
LastOnTime ##/##/####:##:##
LengthTime
off Days:# Hrs:## Min:##
EVOno.
FWVersion #.#
ServiceVersion #.#
Commission
Entercontactinfo
Name ####
TelephoneNo. ##########
Updateinfo? Yes/No
Commissiondate ##:## ##/##/##
Commissionsystem? Yes/No
WorkingHours
RunHours NumberStarts
Compressor #h #
ReversingValve #h #
ChilledWaterPump #h #
SeawaterPump #h #
ElectricHeat #h  #
ServiceSettings
Seepage#
ManualManagement
See
p
a
g
e#
TestMode
Testmode Enabled/Disabled
Timeout Enabled/Disabled
Parameters*
Testmodetimers
Testmodetime ##s
Seawaterpump #m
Chillwaterpump #m
Stage1Comp #s
Stage2Comp #s
Testmodesettings*
Seawaterpump Yes/No
Chilledwaterpump Yes/No
Compressor
Stage1 Yes/No
CWPumpControl
ManualControl Relay2On/Off
ManualPos. On/Off
StatusValue On/Of
f
18
Program/Technician/ManualManagement

ManualManagement
AnalogInput
DigitalInput
RelayOutput
Analo
g
Out
p
ut
AnalogInput
ManualControl ManualPos. StatusValue
CWReturn B001On/Off #.# #.#
CWSupply B002On/Of
f
#.# #.#
DigitalInput
ManualControl ManualPos. StatusValue
HighPressure DI1On/Off Open/Close Open/Close
Lowpressure DI2On/Off Open/Close Open/Close
WaterFlow DI3On/Off Open/Close Open/Close
Loadshedding DI5On/Off Open/Close Open/Close
ElectHtFlow* DI4On/Off Open/Close Open/Close
HandCool DI6On/Off Open/Close Open/Close
HandHeat
DI7On/Of
f
Open/Close Open/Close
RelayOutput
ManualControl ManualPos. StatusValue
SWPump Relay1On/Off On/Off On/Off
CWPump Relay2On/Off On/Off On/Off
Fault Relay3On/Off On/Off On/Off
Compressor Relay7On/Off On/Off On/Off
Revvalve Relay4On/Off On/Off On/Off
ElectricHeat* Relay5On/Off On/Off On/Off
AnalogOutput
Enablemanualvalveposition* Yes/No
ManualValveposition* #stp
19
Program/Technician/ServiceSettings

StageAddress
pLANBoardAddressing
CurrentAddress #
ChangeAddressto #
No.ofStages #
ServiceSettings
WorkingHourSet
ProbeAdjustments
Thermoregulation
UserSave
StageAddress
StageDisable
S
y
stemSetu
p
ProbeAdjustments
TempSensorCurve
CWReturn # k
CWSupply #k
Input Offset Value
CWReturn B001 #.# #.#
CWsupply B002 #.# #.#
Probeadjust
S1offset #.#psig
S1probe #.#psig
S2offset #.#°F
S2probe #.#°F
S3offset #.#psig
S3probe #.#
psig
S4offset #.#°F
S4
p
robe #.#°F
WorkingHourSet
SetPoint ResettoZero? RunHours
Compressor #h Yes/No #h
ChilledWaterPump #h Yes/No #h
SeawaterPump #h Yes/No #h
ElectricHeat* #h Yes/No #h
Thermoregulation
SuperheatSetpoint
CoolSetpoint #.#°F
HeatSetpoint #.#°F
SetpointSH #.#°F
LowSHthresh #.#°F
LOPthresh #.#°F
MOPthresh #.#°F
StageDisable
StageControl Yes/No
SystemSetup
WaterLoopControl Supply/Return
HeatSupTemp Yes/No
ElectricHeat Yes/No
EHFlowSwitch* Yes/No
UserSave
Save? Yes/No
Restore? Yes/No
Enableautosave Yes/No
20
Program/Manufacturer

Initialization
Thiswillclearthealarmhistorycontinue? Yes/No
InsertNewPasswords
User####
Technician(PW1) ####
Factory(PW2)####
FactorySave
Save?Yes/No
Restore?Yes/No
AutoRestore?Yes/No
UserSave
Save?Yes/No
Restore?Yes/No
AutoRestore?Yes/No
Defaultinstallation
Eraseusersettingandinstall
globaldefaultvalue? Yes/No
I/OConfiguration
Seepage#
Manufacturer
Configuration
I/OConfiguration
FactorySettings
Initialization
FactorySettings
Seepage#
Configuration
TemperatureUnits °F/°C
PressureUnits psi/bar
Forceclockenable Yes/No
Clockmode 24h/12h
DisableBuzzer Yes/No
Startupdelay #s
EnableUnitby
DigitalInput On/Off
Supervisor On/Off
pLANnetwork On/Off
Schedule On/Off
ManualControlReset
Enable Yes/No
Time #m
PW/ReturnDelay #s
Scheduler
No.ofSchedules #
OptimizedStart Yes/No
Set1Adjust Yes/No
Set2Adjust Yes/No
HolidaysNo. #
EVOConfigurator
EVOConfiguration
Seepage#
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Dometic Basic Chiller Control Operating instructions

Category
Thermostats
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI