DANLERS GREUW PIR5E Installation guide

Type
Installation guide

This manual is also suitable for

Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected] Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue, or visit our website.
ThisproductconformstoBSEN60669-2-1.
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.6ampsovercurrent,1kVovervoltage.Pleaseensure
thatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
PIR Occupancy Switch Modules (5 metre)
GREUW PIR5E GREUW PIR5X
GREUW PIR5EP GREUW PIR5XP
DANLERS5metrePIRoccupancyswitchmodulestintoEurodata
platesandrequirea35mmdeepbackbox.Alternatively,theycanbe
mountedintoaluminaireviaamountingbezel.(GREUWBEZEL)
Theyincorporateapassiveinfra-redquadsensortodetectmovement
ofawarmbodywithintheirdetectionzoneandaphotocelltomonitor
theambientlightlevel.
On detecting movement, if the ambient light level is not above an
ambientthreshold,thePIRwillswitchtheloadon.
Theambientthresholdcanbesetbytheusertobetweenapproximately
100luxandinnitelux(photocellinactive)viatheLUXadjuster.This
luxrangeisobtainedintheHIGHLUXsetting,setviathesideadjuster,
whichcanbeslidwithasmallatbladescrewdriver.ALOWLUXrange
whichgoesdowntoapproximately15lux(maximumapprox800lux)
isalsoavailable.Seediagrams1and2.
Ifnomoremovementisdetectedwithinacertaintime,thenthePIR
willswitchofftheload.
ThetimecanbesetviatheTIMEadjusterto10seconds,20s,40s,
1minute 20s, 2m40s, 5m, 10m, 20m or 40minutes. See diagram 1.
Variantsaredenedbythelastcharactersofthepartnumber:
• EorX Exposedorhiddenadjusters,seediagram3.
• P PhotocelloverridesthePIRduringoccupancy,seebelow.
PVariant: If the ambientlightlevelgoesabovetheLUXthreshold,
andstaysthereforthesetTIME,thenthePhotocellwillswitchoffthe
loadregardlessofthePIRsensinganymovementduringtheTIME
period. This variant is designed for warehouse applications rather
thanofceapplications.
21/09/15 INS946GREUWPIR5
The TIME is set by lining up the adjuster with the appropriate dot,
clockwise:10s,20s,40s,1m20s,2m40s,5m,10m,20m,40minutes.
ItisbesttosetuptheLUXwhenthelocalambientlightlevelisclose
totheminimumdesiredworkinglightlevel(aluxmeterplacedonthe
workingsurfacemayhelp).WiththeLUXsetfullyclockwise,slowly
moveitanticlockwise(-to+).WhentheLEDchangesfromgreento
red,theLUXthresholdissettothepresentluxlevel.
ThissameLUXsettingpointcanbeusedforotherdeviceslocatedwhere
thecurrentlightinglevelisnotatthedesiredminimumworkinglevel.
LEDwillnotturngreenatstartofLUXsetup:
• TurnLUXfurtherclockwise,switchPIRtoLOWLUXsetting.
LEDwillnotturnredduringLUXsetup:
• EnsurePIRinHIGHLUXsetting,turnLUXfurtheranticlockwise.
Relayclicksoffbutloadstayson:
• SmalluorescentorLEDload,augmentwithCAPLOADacrossload
• Faultdevelopedduetoovervoltagespike
LEDashescontinually:
• Faultdeveloped,recyclesupply.
Variants
Setting up TIME and LUX
Fault nding
DANLERSPIRmodulescanswitchupto6amps(1500W)of:
• Fluorescentlamps;eitherhighfrequencyorswitchstart
• Incandescentormainshalogenlamps;integralsafetyfuserecommended.
• Electronicorwirewoundtransformers.
Theycanalsoswitchupto
• 2amps(500W)ofCompactuorescentorLEDlamps(typically50lamps)
• 1amp(250W)ofFans.
Toswitchlargerloadsordischargelampsacontactorshouldbeused.
1.Pleasereadthesenotescarefullybeforecommencingwork.
Incaseofdoubtpleaseconsultaqualiedelectrician.
Makesurethepowerisisolatedfromthecircuit.
2.PIRmodulesshouldbeinstalledtoachievecorrectcoverageofthe
workingarea,seediagram4.Withthegridmoduleupright(i.e.wall
mounted)thepatternisslightlywiderthanitistall.
3.The greatest energy savings will be made if the PIR modules
individuallycontrolasetof lamps.Theycanbe wired inparallel
but this should ideally be limited to three.
4. The PIR modules should be connected as:
L Live
N Neutral
SL SwitchedLineoutput
5.Typicalwiringdiagramsareshownindiagrams5&6.
6.Oncethewiringhasbeencompletedandveried,switchonthe
supply and test the operation.
WhenthePIRmoduleispoweredup,theLEDjustabovetheTIME
adjusterwillashvetimes-greenifitissettotheHIGHLUXrange
(factorydefault)orredifsettotheLOWLUXrange.Itwillthenswitch
ontheloadfor10seconds.Oncetheloadswitchesoff,thePIRmodule
is in operating mode.
Adjustment diagrams
Loading limits
Installation procedure
TIME
min max
LUX
max min
20s
40s
1m 20s 2m 40s 5m
10m
10s
20m
40m 100 lux
(LO: 15 lux)
1000
lux
Typical Settings
Detection diagrams
Typical wiring diagrams
L
load
A few PIR occupancy switch modules
wired in parallel
N
230 VAC
SL
L
load
Single PIR occupancy switch module
N
230 VAC
SL
*Optional
CAPLOAD
augmenting
load, see
fault finding
Optional
manual wall
switch for
overriding off
Start up mode
High/Low
Lux Adjustment
HIGH
LUX
LOW
LUX
Concealment lid
TO REMOVE:
Slide lid
approx. 2mm
away from
lens then lift off
TO REPLACE:
Align then
push straight
down
Up to 7m
Detection
zone
For optimum
coverage
recommended
mounting height
between 2.4
and 5m
Up to
5m
Perspective view
Plan view Side elevation
Up to 5m
Detection
Zone
50°
100°
Up to 5m
Detection
Zone
40°
80°
Ceiling mounted Wall mounted
1. 2. 3.
4.
5. 6.