DANLERS CEDR 6PLR Installation guide

Type
Installation guide
Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: [email protected] Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIRoccupancyswitches•Daylightlinkeddimmers•Manualhighfrequencydimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers•Heating,ventilationandair-conditioningcontrols•Bespoke/O.E.M.products
Please call for more information or a free catalogue, or visit our website.
ThisproductconformstoBSEN60669-2-1andBSEN55015.
Pleaseensurethemostrecenteditionoftheappropriatelocalwiringregulationsareobserved
andsuitableprotectionisprovidede.g.a10ampcircuitbreakerandvoltagesurgeprotection.
Pleaseensurethatthisdeviceisdisconnectedfromthesupplyifaninsulationtestismade.
Thisproductiscoveredbyawarrantywhichextendsto5yearsfromthedateofmanufacture.
Precautions and Warranty
Ceiling directional PIR occupancy switch
CEDR6PLR
DANLERSceilingdirectionallongrangepassiveinfra-redoccupancy
switches(PIRSwitch)canbeceilingmountedintoaKlik-AXsocket.
ThesePIRswitchesincorporateapassiveinfra-redquadsensorto
detectmovementofawarmbodywithintheirdetectionzone(diagram
A)andaphotocelltomonitortheambientlightlevel.
Upondetectingmovement,iftheambientlight is dark enough, the
PIRswitchwillturntheloadon.Theambientthresholdcanbesetby
theusertobetweenapproximately30luxandinnitelux(photocell
inactive)viatheLUXadjuster(diagramC).
Ifnomoremovementisdetectedwithinapre-selectedtime,then
thePIRswitchwillturntheloadoff.Thistimelagcanbesetviathe
TIMEadjusterto10seconds,20s,40s,1minute15seconds,2m30s,
5m, 10m, 20m or 40 minutes (diagram C).
Bothadjustersarelocatedunderneaththeendoftheadjustablebarrel.
ThebarrelofthisPIRswitchcanberotatedthrough360degrees
andangledbetweenhorizontaland45degreesdown.Thelongest
detectionrangeisachievedwhenthebarrelishorizontal.
Loading
Theswitchshouldonlybeconnectedtoa230V50HzACsupply.
ThesePIRswitchescanswitchupto:
6amps(1500W)ofresistiveloads.
6amps(1500W)ofuorescentloads.
3amps(750W)ofelectronicandwirewoundtransformerloads.
2amps(500W)ofCFL,2Dlamps,LEDDriversandLEDlamps
andttings.
1amp(250W)offans
Minimumload2Wresistive,suitableformostenergysavinglamps,
LEDsandemergencyttings.
Largerloadscanbeswitchedviaacontactor.
27/07/15 INS941 CEDR6PLR
Variants
AsDANLERSdesignandmanufactureintheUK,variantscanbesupplied,
codedbythefollowingsufxesandappliedinthisorder:
• 12Vor24V  12Vor24V(acordc)operation
• VF VoltFreecontacts
• GorLG GoldorLogicGoldcontacts
• NC NormallyClosedcontacts
• SD BarrelxedintheStraightDownposition.
Variantdetailsarecoveredinanenclosedaddendumsheetifapplicable.
Troubleshooting
The load will not switch on:
• TheLUXadjusterissettoolowandisinhibitingtheswitch.
• ThemovingbodyisnotemittingmoreIRthanthebackground.
  (Personwearinginsulatingclothinginawarmenvironment)
• PersonistoofarfromthePIRswitch,seedetectiondiagram.
• Personismovingunusuallyslowly(perhapswhentesting).
The load switches on when nobody is present:
• PIRlocatedclosetoaheatsource,fanorindraughtow.
• Ceilingmovement,especiallyinmetalmezzaninewarehouses.
Installation procedure
1.Pleasereadthesenotescarefullybeforecommencingwork.
Incaseofdoubtpleaseconsultaqualiedelectrician.
2.ThePIRoccupancyswitch(PIR)shouldbeinstalledtoachievecorrect
coverageofthearea,seediagramA.
Ifthephotocelloverridefacility
isrequired,thePIRmustbelocatedinapositionwheredaylightcan
givegreaterilluminationthanthearticiallight.Avoidlocatingthis
productwhereitisexposedtodraughtyconditionsorneartoheat
sources.
3.ThegreatestenergysavingswillbeachievedifeachPIRcontrols
anindependentsetoflamps.Theycanbewiredinparallelbutthis
should ideally be limited to three (diagram F).
4.Makesurethepowerisisolatedfromthecircuit.
TheceilingdirectionalPIRsmountintoaKlik-AXsocket
DANLERSpartnumbers-circularCESO,squareCESOSQ.
Theseshouldbewiredasshown(diagramE):
L Livein
N Neutral in
A SwitchedLineout
Start-up mode
WhenthePIRispoweredup,itwillswitchontheloadfor1minute,
theloadwillthenswitchoffandthePIRwillenteritsOperatingMode.
If a manual override-off switch is positioned before the PIR in the
circuit(diagramsD&F,note1)itwilldothiseachtimethewallswitch
isswitchedon.Alternatively,ifthewallswitchisplacedafterthePIR
(diagramsD&F,note2)itwillnotenterthestart-upmodeeachtime.
Time and Lux set-up
Forconvenience,ensurethattheTIMEissettotheminimumwhen
settinguptheLUXlevel.AfterwardssettheTIMEtoavaluesuitable
fortheapplication,makingreferencetodiagramC.
TheLUXisbestsetupwhenthelocalambientlightisatapproximately
theminimumdesiredlightlevel.WiththeLUXsetfullyclockwisewait
forthePIRtoswitchoff.RotatetheLUXadjusterslowlyanticlockwise
(-to+),whilstwavingyourhandapproximately1minfrontofthePIR,
untiltheloadswitcheson.
L
load
Note 1: Optional
manual wall switch
for overriding off.
Note 2: Alternative
position for optional
wall switch
N
230 VAC
L
N
SL
load
Note 1: Optional manual wall switch
for overriding off
Note 2: Alternative
position for optional
wall switch.
L
N
230 VAC
L
N
SL
L
N
SL
L
N
SL
A: CEDR 6PLR Detection diagram
D: Wiring diagram, single PIR
F: Wiring diagram, multiple PIRs
C: Adjusting time and lux
B: Barrel positioning
10m 25m
Strong Detection Zone:
Walking along corridor. Secondary Detection Zone:
Walking across corridor.
Side elevation view
Ideal mounting height between 2.2 and 3m
15m
Plan view
Strong Detection Zone:
Walking along corridor. Secondary Detection Zone:
Walking across corridor.
10m 25m
15m
L N SL
CESO or
CESO SQ
L N
(A)
Back box or
BESA box
Lamp
load
PIR Switch
E: Wiring diagram, socket
TIME
minmax
LUX
maxmin
Typical settings
30 LUX
1000 LUX
PHOTOCELL
INACTIVE 40m
20m
10m
5m
2.5m
80s
10s
20s
40s
  • Page 1 1
  • Page 2 2

DANLERS CEDR 6PLR Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI