Altronix new Maximal3RH rack mount access power controller distributes and switches power to access control
systems and accessories. It converts a 115VAC 50/60Hz input into eight (8) independently controlled 12VDC
or 24VDC fuse protected outputs. Outputs are activated by an normally open (NO) or normally closed (NC)
dry trigger input from an Access Control System, Card Reader, Keypad,
Push Button, PIR, etc. This unit will route power to a variety of
access control hardware devices including: Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. Outputs will operate in
both Fail-Safe and/or Fail-Secure modes. The FACP Interface
enables Emergency Egress, Alarm Monitoring, or may be
used to trigger other auxiliary devices. The fire alarm disconnect
feature is individually selectable for any or all of the outputs.
Input:
• 115VAC60Hz.,1.9amp.
• Normallyclosed[NC]ornormallyopen[NO]
dry contact inputs (switch selectable).
Outputs:
• 12VDCor24VDC@6amptotaloutputcurrent.
• Eight(8)fuseprotectedoutputs.
• MaximumcurrentperACM8R-Moutputis2.5amp.
• IndividuallyselectableMagLock/Strike(Fail-Safe,
Fail-Secure) solid state fuse protected outputs.
• Thermalandshortcircuitprotectionwithautoreset.
Fire Alarm Interface:
• LatchingorNon-Latchingfirealarmresetswitch
individually selectable for each output.
• RemoteresetcapabilityforlatchingFireAlarm
Interface mode.
• FireAlarmdisconnectinputoptions:
a) Normallyopen[NO]ornormallyclosed[NC]
dry contact input.
b) Polarity reversal input from FACP signaling
circuit.
Visual Indicators:
• IndividualOutputStatusLEDslocatedonthe
front panel.
Battery Backup:
• Built-inchargerforsealedleadacidorgeltype
batteries (if batteries are required install
separate enclosure).
• Maximumchargecurrent0.7amp.
• Automaticswitchovertostand-bybattery
when AC fails.
• Zerovoltagedropwhenunitswitchesovertobattery
backup (AC failure condition).
Supervision:
• ACfailsupervision(form“C”contact).
• Lowbatteryandbatterypresencesupervision
(form“C”contact).
Additional Features:
• Removableterminalblockswithlockingscrewflange.
• 3-wirelinecord.
• Illuminatedmasterpowerdisconnectcircuitbreaker
with manual reset.
Rack Dimensions:
3.25”Hx19.125”Wx8.5”D
Shipping Weight (approximate):
- Maximal3RH: 12.6 lbs.
Maximal3RH
Rack Mount Access Power Controller
Rev.DSMaximal3RH-A19K
Overview
Specifications
3.125"
8.5"
.75"
19.125"
17.625"
- - - +
OUT1
- - - +
OUT2
- - - +
OUT3
- - - +
OUT4
- - - +
OUT5
- - - +
OUT6
- - - +
OUT7
- - - +
2 1
OUT8
IN1
IN2
IN3
IN5
IN6
IN7
IN8
IN4
GND
GND
GND
RESET
FACP
GND
GND
Altronix Corp. - 140 58th Street, Brooklyn, NY 11220 • 718-567-8181 • 888-258-7669 • altronix.com
TOP & BOTTOM
FRONT
REAR
Maximal3RH Rack Chassis Dimensions
3.25”Hx19.125”Wx8.5”D