PAGE 5 OF 5
Contractor Essentials™
SHL2 Linear High Bays
Installation Guide for Contractor Essentials™ SHL2 Linear High Bays
SloanLED Headquarters
5725 Olivas Park Drive, Ventura, CA, USA
888.747.4LED (888.747.4533) • info@SloanLED.com
SloanLED.com
SloanLED Europe b.v.
Argonstraat 110, 2718 SN Zoetermeer, NL
+31 88 12 44 900 • Europe@SloanLED.com
P/N 402581 Rev C 2022-01-20
Customer service and technical support
Programming Guide for MS2 Sensor Remote Control
Remote Control Settings
Press"ON/OFF"button,switchesxture
from ON to OFF and sensor is disabled.
Press "Reset" or "Auto Mode" button to
quit mode.
ON/OFF
Press "RESET" button, all parameters are
same as DIP switch setting.
Reset
Press "AUTO MODE" button, sensor
begins working with same parameter
settingsaspreviousstatusbeforexture
was switched ON/OFF.
Auto
Mode
Press "DIM TEST" button to test dimming
function. Sensor will dim automatically and
return to normal mode.
DIM
Test
"TEST (2S)" button for factory testing purposes only.
Sensor will enter test mode,
Detection sensitivity: 100%
Hold time: 2 seconds
Standby dim level: 10%
Standby period: 0 seconds
Daylight sensor: Disable
Quit TEST mode by pressing any button.
Test
(2s)
QS 1
QS 2
QS 3
QS 4 NOTE: Detection area / Hold time /Standby period / Standby DIM level /
Daylight sensor may be adjusted by pressing corresponding button.
Remote will always use most recent setting.
Scene
options
Detection
area
Hold
time
Standby
period
Standby
DIM level
Daylight
sensor
QS 1 100% 30 s 1 min. 10% 5 Lux
QS 2 100% 1 min. 3 min. 10% 10 Lux
QS 3 100% 5 min. 10 min. 10% 30 Lux
QS 4 100% 10 min. 30 min. 10% Disable
As control angle of infrared Remote Control
isxed(15°),ifsensorsareinstalledtooclose
to each other, settings for both sensors will
becongured.Pleaserefertochartbelowfor
recommended distance between sensors.
Mounting height Distance between sensors
49.2 ft (15 m) m
39.4 ft (12 m) 1.3 ft (0.4 m)
30.0 ft (9 m) 1.3 ft (0.4 m)
20.0 ft (6 m) 2.0 ft (0.6 m)
10 ft (3 m) 2.6 ft (0.8 m)
Reset Mode
Auto
QS1QS2 QS3QS4
100%50%75%25%
5s 30s 1min 3min
30min20min10min
5min
10% 20%30% 50%
0s 10s 1min 3min
+
30min10min
5min
8
5Lux 15Lux30Lux 50Lux
100Lux 150Lux Disable
Quick Setting
Detection Area
Hold Time
Stand-by DIM Level
Stand-by Period
Daylight Sensor
ON/OFF T
DIM
est
T
(2s)
est
Motion Sensor Motion Sensor7.5° 7. 5 °