SloanLED -SHL2-Linear-High-Bays-logo Installation guide

Type
Installation guide

This manual is also suitable for

PAGE 1 OF 5
Contractor Essentials
SHL2 Linear High Bays
Installation Guide for Contractor Essentials SHL2 Linear High Bays
WARNING
• Toreduceriskofdeath,personalinjuryorpropertydamagefromre,
electric shock, falling parts, cuts/abrasions, and other hazards, read all
warning and instructions with this product, and all product labels
Before installing, servicing, or performing routine maintenance
upon this equipment, follow these general precautions
Commercial installation, service and maintenance of luminaires
shouldbeperformedbyaqualiedlicensedelectrician
If you are unsure about installation or maintenance of luminaires,
consultaqualied,licensedelectrician,andcheckyourlocalelectricalcode
To prevent wiring damage or abrasion, do not expose wiring to edges
of sheet metal or other sharp objects
Do not make or alter open holes in an enclosure of wiring
or electrical components during installation
WARNING
• Turnoelectricalpoweratfuseorcircuitbreakerbox
before wiring luminaire to power supply
• Turnopowerbeforeperforminganymaintenance
Verify that supply voltage is correct by comparing it
with luminaire label information
All wiring connections should be capped with UL
approved wire connectors
WARNING
Avoid direct eye exposure to light source
while powered on
Account for small parts and dispose of packing
material as these may be hazardous to children
To avoid risk of burning, disconnect power and
allowxturetocoolbeforehandlingluminaire
Wire guards
Cable kit
Cable mount kit, 3-m:
SHL2-CMK3
Cable mount kit, 5-m:
SHL2-CMK5
Chain kit
(included)
Pendant hanger
Pendant mount kit:
SHL2-PMK
For 3/8"
(9.5 mm)
IPS
Surface mounting
Surface mount kit:
SHL2-SMK-12X23
PAGE 2 OF 5
Contractor Essentials
SHL2 Linear High Bays
Installation Guide for Contractor Essentials SHL2 Linear High Bays
Lenses and Wire Guards
4. Remove screws attaching lens end cover to
luminaire body, and remove lens end cover.
5. Slide lens into luminaire body. 6. Reattach lens end cover.
Installation
1. Install chain into provided wire hanger.
Secure other end of chain to structure using
hardware rated for load. Install wire hanger
into slots on top of LED luminaire end piece.
Ensure wire hangers are fully engaged into
slots on top channel.
2. Connect LED high bay wiring to incoming
power lines, with BLACK-TO-BLACK,
WHITE-TO-WHITE, and GREEN-TO-
GREEN. Use only UL listed wire.
NOTE: PURPLE and GRAY wires inside
driver compartment are 0-10 VDC (low
voltage) dimming wires. Connect to dimming
low voltage wiring only.
3. CleanallresidueandngerprintsfromLED
luminaire. Double check all hanging hardware
before moving on to next installation.
Wiring
Diagram WHITE (NEUTRAL)
BLACK (LINE)
GREEN (GROUND)
Dimming wire to
0 - 10 V control
120-277
V
LED Driver
INPUT
OUTPUT
To LEDs
RED (+)
BLUE (–)
GRAY (Dim-)
PURPLE (Dim+)
PAGE 3 OF 5
Contractor Essentials
SHL2 Linear High Bays
Installation Guide for Contractor Essentials SHL2 Linear High Bays
Programming Guide for MS1 Sensor
Sensor Notes
When heating, ventilating, or air conditioning (HVAC) units turn on, they create turbulence which may cause sensors to activate. Sensor and HVAC registers must be
separated by at least 6' (1.8 m). If sensor's location gives it a view of other rooms or hallways, lights will turn on when movement is detected in these adjacent areas.
Sensor detection zone may be restricted by masking a portion of lens, or moving sensor to eliminate detection through doorway.
Inside of luminaire
or electrical box
Wires
Lock nut
Lights will not turn ON. Circuit breaker or fuse is OFF: Turn breaker ON. Ensure light being controlled are in working order (i.e. working bulbs, ballasts, etc.).
Sensor is wired incorrectly or may be defective. Conrmsensorwiringisdonecorrectlyandinspectvisuallyforproblems.
Lens is dirty or obstructed: Inspect lens visually and clean if necessary or remove obstruction.
Lights will not turn OFF. Make sure no motion is occurring in coverage area until 15 second (factory set) time delay expires.
Sensor is wired incorrectly or may be defective:Conrmthatsensorwiringisdonecorrectlyandinspectvisuallyforproblems.
Sensor may be mounted too closely to an air conditioning or heating vent: Move sensor or close vent.
Line voltage has dropped: Perform necessary tests to ensure line voltage has not dropped beneath 100 V.
Lights turn OFF and ON
too quickly.
Sensor may be mounted too closely to an air conditioning or heating vent: Move sensor to another location or close vent.
Tine delay set improperly: Refer to Time Delay Adjustment section.
Sensor Adjustment & Programming
Time Delay Knob
Turn knob on left "TIME" counter-clockwise to
minimum setting (30 seconds) and clockwise to
maximum setting (30 minutes). Verify by turning light
on with push button.
Sensor Sensitivity Range Knob
Default position: 75% (position 3).
Adjustable: 50% (position 1) to 100% (position 5).
Sensitivity adjustment is in center, marked "SENSE".
TIME SENSE LIGHT
Sensor Sensitivity Range Knob (cont.)
Adjust sensitivity to avoid unwanted detection such
ashallwaytracoradjacentmovement.Turning
knob counter-clockwise will decrease sensitivity.
Turning knob clockwise will increase sensitivity.
Maximum sensitivity while turning clockwise will
increase it. Maximum sensitivity can be achieved by
turning fully clockwise on position 5.
PAGE 4 OF 5
Contractor Essentials
SHL2 Linear High Bays
Installation Guide for Contractor Essentials SHL2 Linear High Bays
Programming Guide for MS2 Sensor
Detection area: Detection area may be reduced
byselectingcombinationonDIPswitchestot
yourspecicapplication.
ON 1
ION 100%
II 50%
ON 234
ION ON ON 5 sec.
II ON ON 30 sec.
III ON ON 1 min.
IV ON 3 min.
VON ON 20 min.
VI ———30 min.
Hold time:Referstotimeperiodxtureremains
at 100% illumination after no motion is detected.
Standby period:Referstotimeperiodxtureremains
atlowlightlevelbeforecompletelyswitchingoinlong
absenceofmotion.Whensetto"+∞"mode,lowlightis
maintained until motion is detected.
ON 1 2 3
ION ON ON 0 sec.
II ON ON 1 min.
III ON ON 3 min.
IV ON 10 min.
VON ON 30 min.
VI ——— +∞
Daylight sensor:Sensorallowsxture
illuminationonlybelowadenedambient
brightness threshold. When set to "Disable"
mode,daylightsensorwillturnxtureonwhen
motion is detected regardless of ambient light
level. NOTE: Daylight sensor active only when
xtureiscompletelyturnedo.
ON 6789
ION ON ON ON
5 Lux
II ON ON ON
15 Lux
III ON ON ON
30 Lux
IV ON ON
50 Lux
VON ON ON
100 Lux
VI ON ON ON
150 Lux
VII ————
Disable
Standby dimming level: Preferred low light level
after hold time in long absence of motion.
ON 4 5
ION ON 10%
II ON 20%
III ON 30%
IV 50%
Specications
Operating voltage ................. 120-277 VAC, 50-60 Hz
Rated load.............................. 400 W @ 120 VAC, 800 W @ 220-277 VAC (inductive)
800 W @ 120 VAC, 1200 W @ 220-277 VAC (resistive)
Power consumption ............. < 1 W
HF system .............................. 5.8 GHz ± 75 MHz, ISM wave band
Transmitting power .............. <0.5 mW
Detection area .......................25% / 50% / 75% / 100%
Hold time ................................5 s / 30 s / 1 min. / 3 min. / 5 min. / 10 min. / 20 min. / 30 min.
Daylight sensor ..................... 5 Lux / 15 Lux / 30 Lux / 50 Lux / 100 Lux / 150 Lux / Disable
Standby period .....................0 s / 10 s / 1 min. / 3 min. / 5 min. / 10 min. / 30 min. / +∞
Standby DIM level ................. 10% / 20% / 30% / 50%
Mounting height....................19.7 - 49.2 ft (6 - 15 m)
Motion detection ................... 0.5 ~ 3 m/s
Detection angle .....................150° (wall installation), 360° (ceiling installation)
Operating temperature ........ -13° F to +131° F (-25° C to +55° C)
IP rating ..................................IP65
4.7"
(Ø 118.2 mm)
Ø 2.8"
(Ø 72 mm)
0.9"
(22.0 mm)
2.3"
(59.0 mm)
1.9"
(47.5 mm)
Antenna
module
Daylight sensor
Standby DIM level
Standby period
Hold time
Detection area
Daylight
sensor
DIP Switch Guide SensordatamaybesetforyourspecicapplicationbyselectingcombinationonDIPswitch.
PAGE 5 OF 5
Contractor Essentials
SHL2 Linear High Bays
Installation Guide for Contractor Essentials SHL2 Linear High Bays
SloanLED Headquarters
5725 Olivas Park Drive, Ventura, CA, USA
888.747.4LED (888.747.4533) • info@SloanLED.com
SloanLED.com
SloanLED Europe b.v.
Argonstraat 110, 2718 SN Zoetermeer, NL
+31 88 12 44 900 • Europe@SloanLED.com
P/N 402581 Rev C 2022-01-20
Customer service and technical support
Programming Guide for MS2 Sensor Remote Control
Remote Control Settings
Press"ON/OFF"button,switchesxture
from ON to OFF and sensor is disabled.
Press "Reset" or "Auto Mode" button to
quit mode.
ON/OFF
Press "RESET" button, all parameters are
same as DIP switch setting.
Reset
Press "AUTO MODE" button, sensor
begins working with same parameter
settingsaspreviousstatusbeforexture
was switched ON/OFF.
Auto
Mode
Press "DIM TEST" button to test dimming
function. Sensor will dim automatically and
return to normal mode.
DIM
Test
"TEST (2S)" button for factory testing purposes only.
Sensor will enter test mode,
Detection sensitivity: 100%
Hold time: 2 seconds
Standby dim level: 10%
Standby period: 0 seconds
Daylight sensor: Disable
Quit TEST mode by pressing any button.
Test
(2s)
QS 1
QS 2
QS 3
QS 4 NOTE: Detection area / Hold time /Standby period / Standby DIM level /
Daylight sensor may be adjusted by pressing corresponding button.
Remote will always use most recent setting.
Scene
options
Detection
area
Hold
time
Standby
period
Standby
DIM level
Daylight
sensor
QS 1 100% 30 s 1 min. 10% 5 Lux
QS 2 100% 1 min. 3 min. 10% 10 Lux
QS 3 100% 5 min. 10 min. 10% 30 Lux
QS 4 100% 10 min. 30 min. 10% Disable
As control angle of infrared Remote Control
isxed(15°),ifsensorsareinstalledtooclose
to each other, settings for both sensors will
becongured.Pleaserefertochartbelowfor
recommended distance between sensors.
Mounting height Distance between sensors
49.2 ft (15 m) m
39.4 ft (12 m) 1.3 ft (0.4 m)
30.0 ft (9 m) 1.3 ft (0.4 m)
20.0 ft (6 m) 2.0 ft (0.6 m)
10 ft (3 m) 2.6 ft (0.8 m)
Reset Mode
Auto
QS1QS2 QS3QS4
100%50%75%25%
5s 30s 1min 3min
30min20min10min
5min
10% 20%30% 50%
0s 10s 1min 3min
+
30min10min
5min
8
5Lux 15Lux30Lux 50Lux
100Lux 150Lux Disable
Quick Setting
Detection Area
Hold Time
Stand-by DIM Level
Stand-by Period
Daylight Sensor
ON/OFF T
DIM
est
T
(2s)
est
Motion Sensor Motion Sensor7.5° 7. 5 °
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5

SloanLED -SHL2-Linear-High-Bays-logo Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI