  • Hello! I've reviewed the Installation Instruction for the GREEN BROOK ELECTRICAL LED Emergency Exit Sign model RAZEMEXITSGNUP. This document outlines the installation process, as well as routine testing procedures to ensure proper operation. It specifies the use of a LiFePO4 battery, and provides details on the maintained and non-maintained emergency modes, testing schedule and other technical specifications. I am ready to assist with any questions you have about this device.
  • What is the emergency duration of the LED Emergency Exit Sign?
    What type of battery does the sign use?
    How often should a functional test be conducted?
    How often should a full duration test be conducted?
    What does it mean if the charge indicator is unlit?
320
Routine Testing
Testing Record
Testing should be carried out in accordance with the recommendations of BS5266 & EN50172.
1. Do not switch off unswitched mains supply after installation. If interruption is unavoidable, the batteries must be
disconnected or damage to the batteries may occur. Leave the luminaire on continuous charge for 24 hours.
2. A monthly functional test should be conducted manually.
3. Annually, a full three hour duration test should be conducted manually.
4. Batteries should be replaced when the luminaire no longer meets the 3 hours duration performance.
5. Testing is performed by interrupting the unswitched supply for the test duration manually.
During testing the luminaire should remain illuminated in emergency mode.
6. Ensure that the ‘charge indicator’ is ‘ON’ during ‘Charging Mode’.
If the charge indicator (LED) is unlit, this signifies a fault.
7. Replace faulty light source and batteries immediately.
To assist with this testing, a test record is included below.
To increase the chance of a fault being reported between monthly tests, it is desirable that staff are made aware
of the purpose of the indicator.
1
2
3
4
5
6
7
8
9
10
11
12
Functional/DurationMonth Year 1 Year 2 Year 3 Year 4 Year 5
Product: _______________ Location:_____________ Installation Date:____________
Charge Power:
Discharge Power:
Viewing Distance:
EM Duration:
Ambient Temp:
Emergency
Mode: Function:
Battery:
Guarantee:
3W(M) / 0.8W(NM)
0.7W
30M
3 hours
0-45°C
Maintained/Non-Maintained
Standard
LiFePO4 3.2V 1.1Ah
3 Years
Installation Instruction
Product Code: G
Product Description: LED Emergency Exit Sign
Specification
G ar 3
1 2
3
5 6
4
Dimension
Pictogram Replacement
313mm
42mm
212mm
161mm
Installation Instruction
GBE Mar 23
Ceiling Mounted
1 2
3 4
5 6 7
8 9 10
ALWAYS SWITCH OFF THE
MAINS SUPPLY BEFORE
INSTALLATION OR SERVICING
Ceiling N
L
Blue (N)
Brown (L)
Blue
Brown
Maintained
Non-Maintained
Connect battery
to converter
GBE Mar 23
ALWAYS SWITCH OFF THE
MAINS SUPPLY BEFORE
INSTALLATION OR SERVICING
Wall Mounted
1 2
3 4
5 6 7
8 9 10 11
Wall
N
L
Blue (N)
Brown (L)
Blue
Brown
Maintained
Non-Maintained
Connect battery
to converter
GBE Mar 23
/