Functional description - Sabroe Vibration Monitoring system
10/27 0013581 en 2021.03
Data monitoring and control
3.2 Controls
Example of screen #8, Compressor controls SVM01.
Fig. 4: Compressor settings screen
The compressor settings screen (Fig. 4) is used for setting of alarm and shutdown limits. The
three vertical columns showing sensors 1 and 2 alarms and settings are grouped identically with
the vibration data fields seen in the compressor monitoring screen (Fig. 2). Additionally, the col-
our marking relates to the settings for alarm factors and alarm delay settings.
The two upper data fields of ‘Alm’ and ‘SD’ (Fig. 4, (1)) are the final alarm settings in absolute val-
ue that will correspond to the monitoring value fields on the compressor monitoring screen.
The two middle data fields represent the ‘Alm and SD factor’ (2) that will be the multiply value
used to calculate the upper limits during the step 1 sweep session. The two lower data fields of
‘Alm and SD delay’ (3) are the timer setting in seconds to delay the alarm and shutdown action.
• Alarm will be shown in the alarm list and a digital output signal switched ON. Alarm status
has auto reset.
• Shutdown means compressor stop, where the normal ON digital output is switched OFF.
SD status has manual reset and must be acknowledged in the alarm screen and reset on
the red reset button on above screen (4).
Determination of alarm and shutdown limits can be made in one or two steps:
Step 1 is to perform an automatic setting sweep action in which the alarm and shutdown factors
are multiplied to the actual registered vibration value during a compressor running session,
changing the capacity slowly from minimum to maximum capacity. This should possibly be re-
peated to ensure representative initial state values. Step 2 is the possible overwrite of the limits
to operate with comparison values for easier overviews or to use experienced settings.
The left screen side (4) shows the ‘Auto alarm setting’. The upper timer field is the timer setting in
seconds (default 900 seconds) for the maximum sweep session duration time. The barograph
timer and the timer field above that are the actual timer counting of the sweep session. The baro-
graph will show counting from zero of activation and the above timer will do a countdown from
maximum timer setting.
The step 1 sweep session must be started on the green start button , by which the sweep ses-
sion will run either the maximum timer setting or may be stopped manually on the red stop button