NM500A

IFM NM500A Operating instructions

  • Hello! I've reviewed the operating instructions for ifm's Inductive NAMUR sensors, including models NF500A, NF501A, NG500A, NG501A, NI500A, NI501A, NM500A and NM501A. This document provides essential safety and installation information for use in hazardous areas. I am ready to answer your questions about these sensors, their specifications, and usage.
  • Can the device be installed by anyone?
    What are the maximum values for intrinsically safe circuits?
    Can the device be modified or repaired?
Operating instructions
(Ex protection related part)
Inductive NAMUR sensor
NF / NG /
NI / NM
11455628 / 0008 / 2022
GB
NF / NG / NI / NM Inductive NAMUR sensor
2
1 Safety instructions
Remarks for safe use in hazardous areas.
The device must only be installed, connected and set up by qualified staff. The qualified staff must
have knowledge of types of protection, regulations and provisions for apparatus in hazardous
areas.
The classification and marking of the device must be suitable for the application.
Adhere to the respective national regulations and provisions as well as the relevant installation
regulations.
Observe applicable documents.
2 Intended use
Use in hazardous areas according to the classification:
NF / NG:
ATEX classification Identification Permissible ambient temperature
II 1G Ex ia IIB T6 Ga Ta -20...70°C
II 1D Ex ia IIIC T₂₀₀ 90°C Da Ta -20...70°C
NI:
ATEX classification Identification Permissible ambient temperature
II 1G Ex ia IIB T6 Ga Ta -20...70°C
II 2G Ex ia IIC T6 Gb Ta -20...70°C
II 1D Ex ia IIIC T₂₀₀ 90°C Da Ta -20...70°C
NM:
ATEX classification Identification Permissible ambient temperature
II 2G Ex ia IIB T6 Gb Ta -20...70°C
II 1D Ex ia IIIB T₂₀₀ 90°C Da Ta -20...70°C
Type examination certificate:
IEC: IECEx BVS 06.0003X
EU: BVS 04 ATEX E091 X
The requirements of the following standards are met:
EN IEC 60079-0:2018, EN 60079-11:2012
IEC 60079-0:2017, IEC 60079-11:2011
Connection only to intrinsically safe circuits which are approved with the type examination certificate
and do not exceed the following maximum values:
Ui = 15 V, Ii = 50 mA, Pi = 120 mW
Maximum effective internal inductance (Li) and capacitance (Ci):
Article number Internal inductance (Li) in µH Internal capacitance (Ci) in nF
NF500A 145 210
Inductive NAMUR sensor NF / NG / NI / NM
3
NF501A 115 210
NG500A 85 200
NG501A 190 200
NI500A 120 250
NI501A 210 230
NM500A 450 250
NM501A 710 220
3 Installation
uProtect device and cable against destruction.
uAvoid electrostatic charging on plastic housings and cables.
uTo avoid electrostatic charging, ensure the equalisation of potential of metal parts (connector
housing, fixing elements, protective housing, etc.).
uDo not install the device in the partition between different zones.
uWhen used in zone 0, protect the sockets against intensive electrostatic charging.
3.1 Special conditions for safe operation
uAlways refer to the operating instructions for the identification, as it may not be fully applied to the
device due to lack of space.
4 Maintenance, repair and disposal
The device must not be modified nor can it be repaired. In case of a fault please contact the
manufacturer.
If needed, data sheets and type examination certificates or other certificates can be requested from
the manufacturer (Ò cover sheet / back).
/