N95001 Inductive NAMUR sensor
2
1 Safety instructions
Remarks for safe use in hazardous areas.
• The device must only be installed, connected and set up by qualified staff. The qualified staff must
have knowledge of types of protection, regulations and provisions for apparatus in hazardous
areas.
• The classification and marking of the device must be suitable for the application.
• Adhere to the respective national regulations and provisions as well as the relevant installation
regulations.
• Observe applicable documents.
2 Intended use
Use in hazardous areas according to the classification
ATEX classification Identification Permissible ambient temperature
II 2G Ex ia IIC T6 Gb Ta -20...70°C
II 1D Ex ia IIIB T₂₀₀ 90°C Da Ta -20...70°C
II 2G Ex ia IIC T5 Gb Ta -20...80°C
II 1D Ex ia IIIB T₂₀₀ 100°C Da Ta -20...80°C
Type examination certificate:
• EU: BVS 03 ATEX E131 X, BVS 04 ATEX E153 X
• IEC: IECEx BVS 06.0003X
The requirements of the following standards are met:
• EN IEC 60079-0:2018, EN 60079-11:2012
• IEC 60079-0:2017, IEC 60079-11:2011
In principle, the type examination only takes atmospheric conditions into account. For conditions
outside these ranges use must be assessed and approved by the user.
Sensors:
Connection only to intrinsically safe circuits which are approved with the type examination certificate
and do not exceed the following maximum values:
Ui = 15 V, Ii = 50 mA, Pi = 120 mW
Solenoid valve:
Connection only to intrinsically safe circuits which are approved with the type examination certificate
and do not exceed the following maximum values:
Ui = 28 V, Pi = 2 W
Pin layout connector Rd 24x1/8 (field connection):
Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6
+ sensor 1 - sensor 2 + sensor 2 - sensor 1 + solenoid valve - solenoid valve
Pin PE: Plug housing M12 connector
Pin layout M12 connector
Pin 1 Pin 2