BB i-bus
®
KNX
DALI Gateway Emergency Lighting
DGN/S 1.16.1
Product Manual
ABB i-bus
®
KNX
Contents
DGN/S 1.16.1 | 2CDC 507 114 D0201 i
Contents
Page
1 General .................................................................................................3
1.1 Product and functional overview...................................................................................................4
1.2 DALI general.................................................................................................................................6
1.3 ABB i-bus
®
DALI-Gateway in comparison....................................................................................7
1.3.1 DGN/S 1.16.1 system description (group control) ........................................................................8
1.3.2 DGN/S 1.16.1 emergency lighting test .......................................................................................10
1.3.2.1 Function test...............................................................................................................................10
1.3.2.2 Duration test...............................................................................................................................10
1.3.2.3 Partial duration test.....................................................................................................................10
2 Device Technology............................................................................ 11
2.1 Technical data............................................................................................................................12
2.2 Circuit diagram ...........................................................................................................................14
2.3 Dimension drawing.....................................................................................................................15
2.4 Assembly and installation...........................................................................................................16
2.5 Description of the inputs and outputs .........................................................................................18
2.6 Manual operation........................................................................................................................19
2.6.1 Display elements........................................................................................................................20
3 Commissioning.................................................................................. 21
3.1 Overview ....................................................................................................................................22
3.1.1 Conversion of previous application program versions................................................................24
3.1.1.1 Procedure...................................................................................................................................25
3.2 Parameters.................................................................................................................................26
3.2.1 Parameter window General........................................................................................................27
3.2.2 Parameter window Central.........................................................................................................32
3.2.2.1 Parameter window - Emergency.................................................................................................39
3.2.2.2 Parameter window - Status ........................................................................................................42
3.2.2.3 Parameter window Gx Group.....................................................................................................51
3.2.2.4 Parameter window – Gx Status..................................................................................................60
3.2.2.5 Parameter window – Gx Fault....................................................................................................64
3.2.2.6 Parameter window – Gx Slave emergency.................................................................................68
3.2.2.7 Parameter window - Gx Slave....................................................................................................70
3.2.2.8 Parameter window - Gx Sequence.............................................................................................74
3.2.2.9 Parameter window - Gx Staircase lighting..................................................................................77
3.2.3 Parameter window Scenes.........................................................................................................84
3.2.4 Parameter window Scene x........................................................................................................85
3.2.5 Parameter window Sequence.....................................................................................................87
3.2.6 Parameter window Emergency Converter..................................................................................90
3.2.6.1 Parameter window Cx…Cy Converter........................................................................................92
3.2.6.2 Parameter window - Cx…Cy Test ..............................................................................................95
3.3 Communication objects..............................................................................................................98
3.3.1 Brief overview of the communication objects..............................................................................99
3.3.2 Communication objects General...............................................................................................101
3.3.3 Communication objects DALI output ........................................................................................102
3.3.4 Communication objects Group x...............................................................................................118
3.3.5 Communication objects Fault ...................................................................................................120
3.3.6 Communication objects Converter x.........................................................................................122
3.3.7 Communication objects Scene x/y............................................................................................124
3.3.8 Communication objects function Slave.....................................................................................126
3.3.9 Communication objects function Sequence..............................................................................127
3.3.10 Communication objects function Staircase lighting...................................................................128
4 Planning and Application................................................................129
4.1 Automatic DALI addressing......................................................................................................129
4.2 Function chart...........................................................................................................................130
4.3 Monitoring of lamps and ballasts..............................................................................................131
ABB i-bus
®
KNX
Contents
ii 2CDC 507 114 D0201 | DGN/S 1.16.1
4.4 Exchange of DALI devices....................................................................................................... 132
4.5 Burning-in of luminaries........................................................................................................... 133
4.6 Staircase lighting ..................................................................................................................... 134
4.7 Scene ...................................................................................................................................... 136
4.8 Slave........................................................................................................................................ 139
4.9 Sequence................................................................................................................................. 142
4.10 DALI lighting curve................................................................................................................... 147
4.10.1 Characteristic adjustment of the linear dimming curve ............................................................149
4.10.2 Characteristic adjustment with physical minimum dimming value............................................ 150
A Appendix...........................................................................................151
A.1 Code table Fault group/device (no. 20).................................................................................... 151
A.2 Code table 8 bit scene (no. 232).............................................................................................. 154
A.3 Code table Diagnostics byte “request“ (no. 25)........................................................................ 155
A.4 Code table Diagnostics byte “feedback“ (no. 25)..................................................................... 156
A.5 Further information about DALI................................................................................................ 158
A.6 Scope of delivery..................................................................................................................... 159
A.7 Ordering Information................................................................................................................ 160
A.8 DALI equipment....................................................................................................................... 161
A.9 Notes ....................................................................................................................................... 162
ABB i-bus
®
KNX
General
DGN/S 1.16.1 | 2CDC 507 114 D0201 3
1 General
This manual provides you with detailed technical information relating to the group-orientated ABB i-bus
®
KNX DALI Gateway with Emergency Lighting Function DGN/S 1.16.1. The installation, programming and
commissioning and the device are described using examples. Furthermore, basic terminology used with
emergency lighting technology is explained.
The DGN/S is used for control of DALI equipment, e.g. ballasts, transformers or LED converters with DALI
interfaces compliant to EN 62386 via KNX. Furthermore, DALI self-contained emergency lighting (device
type 1) with individual batteries can be integrated to EN 62386-202.
Here the DGN/S 1.16.1 itself does not offer a functionality in terms of the emergency lighting regulations,
e.g. protocoling functions or other associated stipulated functions. It serves as an intelligent mediator be-
tween KNX and DALI.
The different mandatory tests for emergency lighting, e.g. functional tests or duration testing, can be trig-
gered via KNX, and the result can be provided again on the KNX via communication objects.
The DGN/S combines both the internationally standardized and open standards in the digital illumination
control DALI (EN 62386) and intelligent installation system KNX (ISO/IEC 14543-3 and EN 50090).
ABB i-bus
®
KNX
General
4 2CDC 507 114 D0201 | DGN/S 1.16.1
1.1 Product and functional overview
The group-orientated KNX DALI Gateway DGN/S 1.16.1 is a modular installation device in ProM design.
Up to 64 DALI devices can be connected to a DALI output. These 64 DALI devices can be divided into up
to 16 lighting groups. Every lighting group can be independently switched, dimmed and a brightness value
can be set via the KNX. For each group, a KNX communication object is available for indicating a lamp,
ballast or the combination of lamp and ballast fault on the KNX. The fault status of an individual device can
also be signalled or queried via coded communication objects. Furthermore, the functions Scene (up to
14), Staircase lighting, Slave and Sequence are available.
The special feature of the DGN/S 1.16.1 is that DALI emergency lighting converters can also be connected
as DALI devices. A DALI emergency lighting converter is a DALI device, which monitors and tests the sta-
te of an individual battery of an emergency lighting device and that provides the information via standard-
ized DALI telegrams compliant to EN 62 386-202. The DALI Gateway with Emergency Lighting Function
DGN/S 1.16.1 evaluates this information and sends it on the KNX.
A self-contained emergency lighting can have
x two DALI devices (ballast and emergency lighting converter) or
x one DALI device, which features the function of the emergency lighting converter and the control of
the lighting equipment, usually LEDs.
In the first case, the DGN/S 1.16.1 controls a maximum of 32 emergency lights, as the DALI standard lim-
its the number of DALI devices to 64 DALI devices. In the second case, DALI emergency lighting convert-
ers with two functions as a DALI device can connect up to 64 emergency lights to the DGN/S.
Access to the individual devices for the determined individual functionalities is possible. In the case of mo-
nitoring of individual lamps or batteries, the information is available as coded KNX telegrams that are up to
4 bytes in length.
The DGN/S 1.16.1 does not support overlapping DALI lighting groups. Cross-lighting groups should be
formed by KNX group addressing. Furthermore, it is possible to commonly control all DALI devices con-
nected to a DALI output via DALI output telegrams (DALI broadcast control).
The DALI power supply for the 64 DALI devices is integrated into the DGN/S 1.16.1.
Readdressing of the DALI devices and the assignment of the 64 DALI devices into 16 lighting groups is
implemented in an ETS independent DALI-Software-Tool, so that for example, a facility manager without
ETS knowledge is capable of exchanging and reassigning DALI devices, should maintenance be required.
Furthermore, the error states of the individual DALI devices and/or lighting groups are represented graphi-
cally with the DALI-Software-Tool.
The setting of the parameters and allocation of the group addresses is implemented primarily with the En-
gineering Tool Software ETS. The most up-to-date version should be used. The minimum requirement is
version ETS2 V1.3.
ABB i-bus
®
KNX
General
DGN/S 1.16.1 | 2CDC 507 114 D0201 5
The application program offers a range of functions:
x Switching, dimming, setting of brightness values
x Status feedbacks via common or separate communication objects
x Status response of a lamp and/or ballast malfunction
x Programming of individual maximum and minimum dimming limit values (dimming thresholds)
x Different dimming speeds for switching, setting brightness values and dimming
x Reaction at DALI and KNX voltage failure and recovery
x Programming of the brightness value (power ON level) after a ballast operating voltage recovery
x KNX control of all connected DALI devices without prior commissioning (DALI group assignment)
x Triggering of the emergency lighting test via a DALI emergency lighting converter
x Function test
x Duration test
x Partial duration test
x Battery charge state
x Transfer of the emergency lighting test results to the KNX
Various operating modes, e.g.:
x Function Slave for integration of the lighting groups in an energy efficient lighting control
x 14 independent light scenes, which can be recalled or stored via 1 bit or 8 bit telegrams
x Function Staircase lighting including pre-warning
x Function Sequence for programming of running lights or colour effects
ABB i-bus
®
KNX
General
6 2CDC 507 114 D0201 | DGN/S 1.16.1
1.2 DALI general
The requirements for modern lighting technology are extremely varied. While previously lighting was only
required for visual tasks, nowadays factors such as comfort, ambience, functionality and energy efficiency
are in the foreground. Furthermore, a modern lighting system is increasingly being incorporated into the
facility management of the building installation in order to monitor the status of the entire lighting system.
Often, a complex lighting management system is needed, which meets the uses of the premises. All these
requirements are either not adequately met by the traditional 1–10 V electrical installation or only with con-
siderable effort and cost. The DALI standard (EN 60929 previously EN 62386) has emerged against this
background in conjunction with leading manufacturers of lamp ballasts. It describes and defines the digital
interface DALI (Digital Addressable Lighting Interface) for lighting technology equipment.
DALI has become established as an independent standard in the field of lighting technology. The range of
ballasts, transformers, dimmers and relays with DALI interfaces has decisively influenced modern lighting
technology.
Part 202 of DALI standard 62386 described DALI commands to communicate with emergency converters.
With this DALI commands emergency test (e.g. function test, duration test, and battery capacity informa-
tion) can be triggered. The test result will send back from the emergency converter to DALI and over the
DGN/S to KNX.
This KNX DALI technique allows a management building system to trigger the demanded emergency tests
and documented the test results.
More detailed information concerning the DALI can be found in the manuals DALI Gateway DGN/S 1.16.1, The DALI
Manual or the DALI, Manual of DALI AG, which is part of the ZVEI.
ABB i-bus
®
KNX
General
DGN/S 1.16.1 | 2CDC 507 114 D0201 7
1.3 ABB i-bus
®
DALI-Gateway in comparison
ABB Stotz Kontakt GmbH currently has different KNX DALI-Gateway devices in the ABB i-bus
®
range, for
integration of DALI interfaces into a KNX building installation. Every DALI Gateway has benefits that can
be specifically utilised on different project types.
These differences are described in the following.
The differences are listed briefly below in the table. A detailed description can be found in the chapters that
follow.
Property
DG/S 8.1
Control
Central
DG/S 1.1
Control
Individual
DG/S 1.16.1
Control
Group
DGN/S 1.16.1
Control
Group
Design MDRC MDRC MDRC MDRC
Mounting width 6 4 4 4
DALI outputs 8 (A…H) 2 (A & B) 1 (A) 1 (A)
DALI device (ballast)
per Gateway
128 (max.16
per output)
128 (max. 64
per output)
64
64
(ballasts and
emergency lighting
converter)
DALI emergency lighting converter - - - 64
Lighting groups per Gateway 8 (installation)
A:
max. 255 (KNX)
B: 1
16
*)
(DALI) 16 (DALI)
Lighting groups
established via
cable installation
A: KNX
B: cable installation
DALI DALI
DALI devices (e.g. ballasts) per
lighting group
max. 16
A: max. 64
B: max. 64
Max. 64 Max. 64
DALI addressing not required
A: 64 individual
B: 64 individual
64 individual 64 individual
Number of DALI telegrams per KNX
telegram of the group
1 telegram
A: max. 64 telegrams
B: 1 telegram
1 telegram
per group
1 telegram
per group
Power supply to the KNX processor via KNX KNX KNX KNX
DALI voltage
integrated
power supply
integrated
power supply
integrated
power supply
integrated
power supply
*) The 16th lighting group can also be used internally as an option. The DGN/S 1.16.1 assigns the DALI devices, that do not
belong to any other lighting group, to group 16. In this way, commissioning of all devices using the KNX via the communi-
cation objects DALI output is also possible without prior group assignment.
ABB i-bus
®
KNX
General
8 2CDC 507 114 D0201 | DGN/S 1.16.1
1.3.1 DGN/S 1.16.1 system description (group control)
The KNX/DALI Gateway DGN/S 1.16.1 with emergency lighting function is primarily a “normal” DALI Ga-
teway with group control. However, additional DALI devices for self-contained emergency lighting (device
type 1) with individual batteries compliant to the DALI standard EN 62386-202 are supported. Up to 64
DALI devices can be connected to a DALI output. DALI emergency lighting devices and normal DALI de-
vices can be combined as required. An emergency light can consist of two separate DALI devices or also
of just one individual device:
x Two separate DALI devices:
1 ballast (DALI device 1) for normal lighting. It assumes the control of the lighting equipment in normal
operation.
1 emergency lighting converter (DALI device 2), which controls the lighting equipment in emergency
lighting operation. Generally, the emergency lighting converter disconnects the normal ballast in
emergency lighting operation and autonomously assumes control of the emergency lighting. The
emergency lighting converter will switch back to the normal ballast only after emergency lighting op-
eration has ended.
x One DALI device:
1 combined emergency lighting converter, which assumes the control of the lighting equipment in
normal and in emergency lighting operation. Usually, they are LED based solutions.
If battery-operated emergency lighting contains two DALI devices (a ballast and a converter, each with a
DALI interface), up to 32 battery operated emergency lights can be connected. The DALI Gateway auto-
matically recognizes whether the connected DALI device is a battery operated emergency converter and
thus an emergency lighting device (device type 1) compliant to EN 62386-202. This information is indi-
cated by the DALI-Software-Tool. It is possible that both “normal” lamps as well as battery operated emer-
gency lighting are connected in a mixed configuration to the DGN/S 1.16.1. However, the maximum per-
mitted number of 64 DALI devices may not be exceeded.
Self tests of every individual emergency lighting converter is started by request via the KNX. The test re-
sult is reported via the KNX. The communication object Emergency test trigger starts the emergency light-
ing test (function test, short duration test or duration test) or queries emergency lighting tests already un-
der way. The test result is automatically sent via the 4 byte communication object Emergency test result.
Via the communication object Slave emergency active/status, all the lamps in a group controlled by the
DGN/S to the parameterized Brightness value are set. This is independent of whether the lamps them-
selves are affected by an emergency lighting operating voltage failure, mains voltage failure or DALI volt-
age failure. The response during the emergency lighting operation activated by the DALI Gateway can be
parameterized. The prerequisite is that the DGN/S is supplied by the DALI operating voltage.
The Slave emergency is not tripped by a voltage failure. It is triggered by DGN/S if a parameterised num-
ber of lamp or ballast failures exist.
Note
During emergency lighting operation, the DALI devices cannot be commissioned.
ABB i-bus
®
KNX
General
DGN/S 1.16.1 | 2CDC 507 114 D0201 9
The following diagram illustrates the function of the group-orientated DGN/S 1.16.1.
Output A
...
...
...
1
3
2
16
KNX
Ballast
Ballast
Ballast
Ballast
Ballast
Con-
verter
Con-
verter
Ballast Ballast
Ballast
Ballast
Con-
verter
Ballast
Con-
verter
1
2
3
4
64
DALI-Gateway
Emergency
Lighting
DGN/S 1.16.1
...
ABB i-bus
®
KNX
General
10 2CDC 507 114 D0201 | DGN/S 1.16.1
1.3.2 DGN/S 1.16.1 emergency lighting test
The DGN/S 1.16.1 serves as a gateway for self-contained emergency lighting systems and KNX building
management. On this way it is possible to controlled and monitored DALI-based emergency self-contained
lighting devices (converters) compliant with IEC 62 386-202.
A DALI device to IEC 62 386-202 (Device type 1), for self-contained emergency lighting with individual bat-
teries, is described in this manual in shortened form as an emergency lighting converter.
The DGN/S 1.16.1 itself does not offer functionality in terms of the emergency lighting regulations, e.g.
protocoling functions or other associated stipulated functions. It is used exclusively as a gateway between
the KNX communication objects and the DALI commands.
The different mandatory tests for emergency lighting are controlled by KNX communication objects. The
test sequence is subsequently monitored by KNX communication objects, and the results are signalled by
further communication objects on the KNX.
A further possibility is the use of an automated test interval that is controlled by the DALI emergency light-
ing converter itself. The interval duration is determined by the KNX parameter. KNX communication ob-
jects transfer the results.
1.3.2.1 Function test
The function test is undertaken by the emergency lighting converter itself. The function test is requested at
a parameterizable interval in the emergency lighting converter or by a KNX communication object. The
functional security of the emergency lighting converter electronics and correct operation of a lamp and a
switch-over device for an individual battery are tested.
1.3.2.2 Duration test
The duration test is implemented on the basis of the IEC 62 386-202 and is used to determine whether the
individual battery of the system is within the limits of the rated operating duration in emergency lighting op-
eration.
1.3.2.3 Partial duration test
The partial duration test is controlled with the aid of the duration test of the DALI device by the Gateway.
This is possible as a partial duration test is not stipulated or described by the standards. It simply offers an
additional and enhanced possibility for operation readiness of emergency lighting in a simple and time-
efficient way without completely discharging the battery.
ABB i-bus
®
KNX
Device Technology
DGN/S 1.16.1 | 2CDC 507 114 D0201 11
2 Device Technology
The KNX ABB i-bus
®
DALI Gateway with
Emergency Lighting Function DGN/S
1.16.1 is a KNX- modular installation
device (MDRC) in Pro M-design for
installation in the distribution board on
35 mm mounting rails.
The DGN/S integrates operating devices
with DALI interfaces to EN 62386 into a
KNX building installation. The connection
to the ABB i-bus
®
is implemented via a
KNX connection terminal on the device
shoulders.
The DALI output of the DGN/S can be
used to connect up to 64 DALI devices. It
can also exclusively contain 64 DALI
devices for self-contained emergency
lighting compliant to EN 6286-202. Both
“normal” lamps as well as battery oper-
ated emergency lighting can be con-
nected in a mixed configuration to the
DGN/S 1.16.1.
Control of the lamps via KNX is under-
taken by 16 lighting groups, which can be
comprised of any 64 DALI devices.
An individual project-related DALI device
group assignment is possible using the
DALI-Software-Tool.
The fault status (lamps, ballasts or
emergency light converter) of every
individual DALI device or of the lighting
group is sent via different KNX commu-
nication objects on the KNX.
In addition to the standard functions, e.g.
switching, dimming and brightness value
setting with the corresponding feed-
backs, the DGN/S has the functions
Staircase lighting, Scene, Sequence and
Slave. The lighting groups can be
integrated in this way into a constant
lighting control.
Function, duration and partial duration
tests and battery tests for the emergency
lighting systems with individual batteries
to EN 62386-202 can be triggered and
stopped via KNX. The test results are
made available on the KNX.
All DALI devices can be controlled
together in KNX mode as well as manual
mode.
The DGN/S is a DALI control device
(master) and requires an AC or DC
auxiliary power supply. A separate DALI
power supply is not required. The DALI
power source for the 64 DALI devices is
integrated into the DGN/S.
2CDC 071 009 S0011
ABB i-bus
®
KNX
Device Technology
12 2CDC 507 114 D0201 | DGN/S 1.16.1
2.1 Technical data
Supply
gateway operating voltage 85…265 V AC, 50/60 Hz
110…240 V DC
power consumption total via mains maximum 8 W at 230 V AC and max. load
current consumption total via mains maximum 35 mA at 230 V AC and max. load
leakage loss total for device maximum 3 W at 230 V AC and max. load
current consumption KNX maximum 10 mA
power consumption via KNX maximum 210 mW
DALI outputs (channels):
number of outputs 1 x 64 DALI device (16 lighting groups)
number of DALI devices
maximum 64 to EN 62 386; DALI devices for
self-contained emergency lighting to EN 62 386-
202 are supported.
2)
distance between DGN/S and last DALI device
cable cross-section 0.5 mm
2
0.75 mm
2
1.0 mm
2
1.5 mm
2
100 m
1)
150 m
1)
200 m
1)
300 m
1)
Connections
KNX KNX connection terminal,
0.8 mm Ø, single core
DALI outputs and
mains voltage
screw terminal
0.2…2.5 mm
2
stranded
0.2…4 mm
2
single core
tightening torque maximum 0.6 Nm
Operating and display elements
button
DALI output test
button/LED
for assignment of the physical address
LED
, green
display for operation readiness
LED
, yellow for displaying DALI fault, constant light
for displaying test mode, slow flashing
for displaying initialisation or more than 64 DALI
devices, quick flashing
Enclosure
IP 20 to EN 60529
Safety class
II to EN 61140
Isolation category
overvoltage category
pollution degree
III to EN 60 664-1
2 to EN 60664-1
KNX safety extra low voltage
SELV 24 V DC
DALI voltage
typical 16 V DC (9.5…22.5 V DC)
no-load voltage
lowest supply current at 11.5 V
highest supply current
to EN 60929 and EN 62386
16 V DC
160 mA
230 mA
ABB i-bus
®
KNX
Device Technology
DGN/S 1.16.1 | 2CDC 507 114 D0201 13
Temperature range
operation -5 °C…+45 °C
storage -25 °C…+55 °C
transport -25 °C…+70 °C
Environmental conditions
humidity
maximum 93 %, moisture condensation should
be excluded
Design
modular installation device (MDRC) modular installation device, ProM
dimensions 90 x 72 x 64.5 mm (H x W x D)
mounting width 4 modules at 18 mm
mounting depth 68 mm
Installation
on 35 mm mounting rail to EN 60 715
Mounting position
as required
Weight
0.16 kg
Housing, colour
plastic housing, grey
Approvals
KNX to EN 50 090-1, -2 certification
CE mark in accordance with the EMC guideline and low
voltage guideline
1)
The length relates to the common DALI control cable. The maximum values are rounded off and relate to the resistance values. EMC influences
are not considered. For this reason, the values should be considered as absolute maximum values.
2)
Both “normal” lamps as well as battery operated emergency lighting can be connected in a mixed configuration to the DGN/S 1.16.1. However, the
maximum number of DALI devices may not exceed 64.
Device type Application program Maximum number of
communication objects
Maximum number of
group addresses
Maximum number of
associations
DGN/S 1.16.1 Switch Dim Emergency 1f
DALI/…*
246 254 255
* … = current version number of the application program. Please observe the software information on our homepage for this purpose.
Note
The DGN/S is compliant to the SELV characteristics to IEC 60 364-4-41 (VDE 0100-410).
DALI does not need to feature SELV properties, and it is possible to route the DALI control lines to-
gether with the mains voltage on a multi-core cable.
Note
The ETS and the current version of the device application program are required for programming.
The current version of the application program is available for download on the internet at
www.abb.com/knx. After import in the ETS, it is available in the ETS under ABB//Lighting/ DALI/ Switch
Dim Emergency 1f DALI.
The device does not support the closing function of a KNX device in the ETS. If you inhibit access to all
devices of the project with a BCU code, it has no effect on this device. Reading out data and program-
ming is still possible.
ABB i-bus
®
KNX
Device Technology
14 2CDC 507 114 D0201 | DGN/S 1.16.1
2.2 Circuit diagram
DGN/S 1.16.1
1 Label carrier
2 Button
(KNX)
3 LED
, red (KNX)
4 Connection terminal (KNX)
5 LED
, yellow (DALI fault)
6 LED
, green (Gateway ON)
7 Gateway operating voltage
8 Output (DALI)
9 Button
(DALI)
10 DALI device, without/with function self-contained emergency lighting
2CDC 072 012 F0011
ABB i-bus
®
KNX
Device Technology
DGN/S 1.16.1 | 2CDC 507 114 D0201 15
2.3 Dimension drawing
DGN/S 1.16.1
2CDC 072 014 F0011
ABB i-bus
®
KNX
Device Technology
16 2CDC 507 114 D0201 | DGN/S 1.16.1
2.4 Assembly and installation
The device is a modular installation device for quick installation in the distribution board on 35 mm mount-
ing rails to EN 60 715. The mounting position can be selected as required.
The electrical connection is implemented using screw terminals. The connection to the KNX is imple-
mented using the supplied KNX connection terminal. The terminal assignment is located on the housing.
The device is ready for operation after connection to the KNX voltage and the gateway operating voltage.
Accessibility of the devices for the purpose of operation, testing, visual inspection, maintenance and repair
must be provided compliant to VDE 0100-520.
Commissioning requirements
In order to commission the device, a PC with ETS and a KNX interface, e.g. USB or IP, are required. The
device is ready to operate when the KNX voltage and the gateway operating voltage are applied.
The assignment of the DALI devices to the lighting groups as well as the configuration of the emergency
lighting converter is undertaken with the DALI-Software-Tool.
The emergency lighting battery must be charged for commissioning of the DALI emergency lighting con-
verter. Commissioning without emergency lighting operation is not possible.
Important
Acceptance of the emergency lighting monitoring must be discussed with the corresponding approval
agency.
The installation and commissioning may only be carried out by qualified electrical specialists. The appro-
priate norms, guidelines, regulations and specifications for your country should be observed when plan-
ning and setting up electrical installations and security systems for intrusion and fire detection.
Protect the device from damp, dirt and damage during transport, storage and operation.
Only operate the device within the specified technical data limits!
The device should only be operated in an enclosed housing (distribution board)!
The voltage supply to the device must be switched off, before mounting work is performed.
Manual operation
The device incorporates manual operating features. The device features a button
for manual switching
of the DALI output.
ABB i-bus
®
KNX
Device Technology
DGN/S 1.16.1 | 2CDC 507 114 D0201 17
Supplied state
The device is supplied with the physical address 15.15.255. The application program is preloaded. It is
therefore only necessary to load group addresses and parameters during commissioning.
However, the complete application program can be reloaded if required. A longer downtime may result if
the application program is changed or after a discharge.
Assignment of the physical address
The assignment and programming of the physical address is carried out in the ETS.
The device features a
button for assignment of the physical device address. The red LED lights up,
after the button has been pushed. It switches off as soon as the ETS has assigned the physical address or
the
button is pressed again.
Download response
Depending on the PC, which is used, the progress bar for the download may take up to one and a half mi-
nutes, before it appears, due to the complexity of the device.
Cleaning
If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution.
Corrosive agents or solutions should never be used.
Maintenance
The device is maintenance-free. No repairs should be carried out by unauthorised personnel if damage
occurs, e.g. during transport and/or storage.
ABB i-bus
®
KNX
Device Technology
18 2CDC 507 114 D0201 | DGN/S 1.16.1
2.5 Description of the inputs and outputs
On the DALI output up to 64 devices can be connected with a DALI interface. The DGN/S is a DALI master
with integrated DALI power supply.
Important
Other DALI masters may not be connected to the output of the DGN/S.
The connection of another master to the single master system can cause communication malfunctions.
Caution
Other DALI power supplies may not be connected to the output of the DGN/S.
The connection of further DALI supply voltages may destroy the DGN/S due to voltage summation.
Connection of 230 V mains voltage to the DALI output will destroy the DALI end stage and the DALI
output.
A control line on the DALI output with the following maximum length can be used:
Cable length [mm
2
]
2 x 0.5 2 x 0.75 2 x 1.0 2 x 1.5
Max. cable length [m] from the DGN/S to DALI device
100 150 200 300
These values are rounded off and relate to the resistance values. EMC influences are not considered. For
this reason, the values should be considered as absolute maximum values.
It is possible to assemble the DALI control cable with conventional installation material for mains cables.
The two cores of the five-core NYM 5 x 1.5 mm
2
, which are not required, can be used without considera-
tion of the polarity. It is not mandatory to lay a separate control cable.
The isolation between DALI control cables and the power supply is assured by the simple insulation prop-
erties according to EN 410. SELV properties are not featured.
The device is ready for operation after connection of the gateway operating voltage. The green operating
LED on the front of the device lights up.
The yellow flashing (10 Hz) DALI LED indicates the maximum 90 second initialisation phase of the DGN/S.
The DALI system environment is analysed in this phase. If required, new DALI devices are allocated a
DALI address and can be assigned to a lighting group with the DALI-Software-Tool, whereby the lamps
are integrated into the KNX building automation. During this phase, it cannot be guaranteed that an incom-
ing telegram will be processed.
Note
The initialisation phase will not end if more than 64 DALI devices are connected.
The initialisation phase starts automatically after download, gateway operating voltage recovery and KNX
voltage recovery.
The initialisation phase is undertaken if in the parameterization Enable automatic DALI addressing has be-
en deactivated.
/