Siemens BTC-1 Backup Tone Card User manual

Type
User manual
INTRODUCTION
The Model BTC-1 Backup Tone Card from
Siemens Industry, Inc. provides two tones
for the MXLV System that can be selected
by dipswitches. This card can be installed on
top of the ACM-1 to provide backup of the
two primary tones should the tone generator
of the ACM-1 fail. The BTC-1 can also be
installed on the OCC-1 Output Control Card
module to provide a default tone when the
low power riser fails and when the OCC-1
loses contact with the MMB.
Select the two backup tones on switch S1 by
matching SW1-SW4 and SW5-SW8 to the
CSG-M (AccuLINK) configuration tone selec-
tions. Table 1 on the next page shows the
switch settings for each available tone.
For additional information on the Voice
System, refer to the MXLV Manual, P/N
315-092036.
INSTALLATION
Remove all system power before installa-
tion, first battery and then AC. (To power
up, first connect the AC and then the battery.)
1. Remove the card from its protective bag.
Installation Instructions
Model BTC-1
Backup Tone Card
2. Refer to the function section of the CSG-M
configuration printout for the tones to be
configured.
3. Set the desired tones on switch S1 using
dipswitches SW1-SW4 for the first tone
selection and dipswitches SW5-SW8 for
the second tone selection.
a. Refer to Figure 2 or 3 on page 3
for the location of S1.
b. Refer to Table 1 for the switch set-
tings and their associated tones.
c. Set the tones (See Note at the top
of the next page).
Do not install the BTC-1 on the ACM-1
or OCC-1 until the system is ready for
the installation of PC cards. Until then,
keep the BTC-1 in its protective bag.
Mounting
The BTC-1 mounts on either the ACM-1
(See Figure 2) or the OCC-1 (See Figure 3)
with two snap-in type standoffs and a comb-
like connector.
1. Install the standoffs and comb connector
in the component side of the ACM-1 or
the OCC-1, whichever is appropriate.
(See Note at top of the next page.)
P/N 315-090919-8
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
firealarmresources.com
2
GNITTES
ENOT
12345678
00000000 lagellI
X000X000 emihC
0X000X00zH0002
XX00XX00poohWwolS
00X000X0pleY
X0X0X0X0liaW
0XX00XX0edocainrofilaC
XXX0XXX0etunimrepseslup03tadeslupzH009
000X000Xlagelll
X00XX00XnroH
0X0X0X0X3edoclaropmeT
XX0XXX0Xetunimrepseslup03tadeslupzH009
00XX00XXwoeY
X0XXX0XXwoL/hgiH
0XXX0XXXlagellI
XXXXXXXXenotzH009
Note: To open a dipswitch, press down on the side of the dipswitch marked OPEN. To close a
dipswitch, press down on the side of the dipswitch opposite the side marked OPEN.
To open a slide switch, push the slide to the side opposite the side marked ON. To close a
slide switch, push the slide to the side marked ON.
X = Switch closed OR ON; 0 = Switch open OR OFF
Setting the Tones on Switch 1
TABLE 1
Figure 1
BTC-1 Backup Tone Card Module
Mount on an OCC-1 to provide
a default tone in degrade mode
when communication to the
MXL fails and there is a local
alarm detected. This is useful
only if the OCC-1 is providing
input to the amplifier.
Note: Mount on an ACM-1 to provide
a backup for the two primary
tones.
firealarmresources.com
3
2. Position the BTC-1 over the connector
and standoffs with the components of
the board facing out. Be certain that the
standoffs and the connector pins line
up with their respective holes in the
BTC-1 card and connector.
3. Place the BTC-1 on the standoffs and
connector by pressing them into place.
This takes some effort. Be careful be-
cause once the standoffs are installed,
they are difficult to remove. (If it is
Figure 3
Mounting the BTC-1 on the OCC-1
Figure 2
Mounting the BTC-1 on the ACM-1
necessary to remove the BTC-1 from
either the ACM-1 or the OCC-1, first
disconnect the system.)
ELECTRICAL RATINGS
tnerruCeludoMCDV5evitcAAm01
tnerruCeludoMCDV42evitcAAm04
tnerruCeludoMCDV42ybdnatSAm54
firealarmresources.com
P/N 315-090919-8
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Siemens BTC-1 Backup Tone Card User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI