P/N 315-094963-5
Installation/Wiring Instructions
Model DA-3SR/X3SR
Relay Modules for AD-3I and AD-3ILP
INSTALLATION
1. Remove the four color-coded wires (blue, brown, white, and orange)
from the terminal strip in the wiring compartment of the air duct housing.
2. Remove the 4-position terminal strip from the wiring compartment as
shown in Figure 1.
3. Install the DA-3SR or DA-X3SR as shown in Figure 2 using the hardware
provided.
4. Reconnect the four color-coded wires using the quick connect terminals
for each color as shown on the DA-3SR/X3SR printed circuit board.
Figure 1
Removing the Terminal Strip
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
firealarmresources.com
WIRING
Refer to Figures 3 and 4 for wiring the DA-3SR or DA-X3SR
in AD-3I and AD-3ILP air duct housings.
Figure 2
Installing the DA-3SR or DA-X3SR Relay Boards
firealarmresources.com
Figure 3
Typical Connections for Model AD-3I with DA-3SR Relay Modules
NOTES:
1. The relay contacts are shown with System in normal
supervisory, no alarm, condition.
2. When the relay contacts are being used to control
equipment operated by 120 VAC, ensure that the
conduit is properly attacted to the internal metal
ground strap using the proper conduit locking nuts.
SEE NOTE 4
TO NEXT DETECTOR
OR EOL DEVICE
SEE NOTE 3
RELAY
BOARD
+
+
+++
+
+
+
_
___
_
_
_
ZONE WIRES FROM
SIEMENS INDUSTRY, INC.
INITIATING CIRCUIT
OPTIONAL EQUIPMENT -
LISTED REMOTE ALARM
INDICATOR MODEL
ALARM CONTACTS
125 VAC/30 VDC, 3A
SEE NOTES 1 AND 2
ALARM CONTACTS
125 VAC/30 VDC, 3A
SEE NOTES 1 AND 2
4321
10 11
1a 1b 1a 1b 10 11
556789 556789
Model AD-3I
Model AD-3I
with DA-3SR Relay Module
Model AD-3I
with DA-3SR Relay Module
SEE NOTE 4 SEE NOTE 4
Failure to provide proper grounding may result in
fatal electrical shock and violation of national and
local codes.
3. The EOL device must be compatible with system
initiating circuit. Observe proper EOL polarity where
applicable.
4. Use DI-B3, DI-B3H, and PE-3 detectors only.
firealarmresources.com
P/N 315-094963-5
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
NOTES:
1. The relay contacts are shown just after a reset
pulse, which represents the non-alarm condition.
2. If the relay contacts are being used to control
120 VAC operated equipment, ensure that the
conduit is properly attached to the internal metal
ground strap, using the proper conduit locking
nuts. Failure to provide proper grounding
may result in fatal electrical shock and
violation of national and local codes.
3. Use ID-60IB, ID-60IBH, ILI-1B, and ILP-1
detectors only.
Figure 4
Typical Connections for Models AD-3I and AD-3ILP with DA-X3SR Relay Modules
SEE NOTE 3
WIRE NUT
REQUIRED
NOT
USED
NOT
USED
NOT
USED
TO NEXT
ADDRESSBLE
DEVICE
RELAY
BOARD
RED
+
+
+++
+
+
+_
___
_
_
_
BLACK
TERMINAL
BLOCK
ZONE WIRES FROM SIEMENS
INDUSTRY, INC. LISTED MXL
CONTROL PANEL OR ICON-1 (IXL)
OPTIONAL
REMOTE ALARM
INDICATOR
MODEL RLI-1
OR RLI-2 ALARM CONTACTS
125 VAC/24 VDC,3A
SEE NOTES 1 AND 2
ALARM CONTACTS
125 VAC/24 VDC,3A
SEE NOTES 1 AND 2
4321
10 11 10 11
5 5 6 7 8 9 556789
Model AD-3I or AD-3ILP
Model AD-3I or AD-3ILP
with DA-X3SR Relay Modules
Model AD-3I or AD-3ILP
with DA-X3SR Relay Modules
SEE NOTE 3SEE NOTE 3
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Siemens DA-3SR/X3SR Relay Modules for AD-3I and AD-3ILP User manual

Category
Fire protection
Type
User manual

Siemens DA-3SR/X3SR Relay Modules for AD-3I and AD-3ILP offer reliable control and monitoring of fire alarm systems. Designed for use with Siemens AD-3I and AD-3ILP air duct housings, these modules provide alarm contacts for remote indicators and equipment control, enhancing fire safety measures.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI