•Units Supplied With Lead Calcium Batteries
7. DetermineproperbatteryorientationfromFig.3(singleharnessleadconnection)orFig.4(doubleharnesslead
connection).Batteryispositionedtotheleftofthecircuitboard.Removeprotectivelinerfromdoublesidedtape,locatedon
oorofenclosure.
Note:a1/4”space(minimum)isrequiredbetweenthefrontofthebatteryandtheinnerlipoftheenclosuretoprovide
clearanceforcover.Placebatteryintoenclosure,andpressdownrmlytosecurebatterytoenclosure.
8. Connectpositive(+,red)andnegative(–,yellow)batteryharnessleadsfromprintedcircuitboardtocorrespondingbattery
terminals as shown in Fig. 3 or Fig. 4.
9. Check all wiring for loose or missing connections.
10. Replacecover.Besurethateach“starwasher”isproperlypositionedbetweenthescrewheadandtheoutersurfaceofthe
cover.Tightenretainingscrews.Adjustlightingheadstodesiredposition.
11. EnergizeunitwithACpower.Pressandholdthe“TEST”button(seeFig.1for“TEST”buttonlocation)toconrm
illuminationandproperaimingofemergencylamps.(“ACON”indicatorLEDshouldgooff).Releasethe“TEST”button;
emergencylampsshouldextinguish.Normaloperationbegins.
12. NormalOperation:withpowersupplied,“ACON”LEDindicatorisilluminatedandemergencylampsareoff.
•Units Supplied With Nickel Cadmium Batteries
7. DetermineproperbatteryorientationfromFig.5(singleharnessleadconnection)orFig.6(doubleharnesslead
connection).Batteryispositionedtotheleftofthecircuitboard.Removeprotectivelinerfromdoublesidedtape,locatedon
the battery.
Note:a1/4”space(minimum)isrequiredbetweenthefrontofthebatteryandtheinnerlipoftheenclosuretoprovide
clearanceforcover.Placebatteryintoenclosure,andpressdownrmlytosecurebatterytoenclosure.
8. Connect battery harness leads from printed circuit board to corresponding battery harness leads as shown in Fig. 5
or Fig. 6.
9. Check all wiring for loose or missing connections.
10. Replacecover.Besurethateach“starwasher”isproperlypositionedbetweenthescrewheadandtheoutersurfaceofthe
cover.Tightenretainingscrews.Adjustlightingheadstodesiredposition.
11. EnergizeunitwithACpower.
Note: allow unit to charge for 24 hours prior to testing.
Pressandholdthe“TEST”button(seeFig.2for“TEST”buttonlocation)toconrmilluminationandproperaimingof
emergencylamps.(“ACON”indicatorLEDshouldbeoff).Releasethe“TEST”button;emergencylampsshouldextinguish.
Normal operation begins.
12. NormalOperation:withpowersupplied,“ACON”LEDindicatorisilluminatedandemergencylampsareoff.
ROUTINE TEST CYCLING
1. Monthly:Iftherehasbeennopowerfailure,pressandholdthe“TEST”buttonforatleastthirty(30)seconds
toconrmemergencylampoperation.Release“TEST”buttontoreturntobatterychargingmode.
2. Onceayear:Performafullbatteryconditioningcyclebyde-energizingtheACcircuittowhichtheunitisconnected,and
allowtheunittooperateforninety(90)minutesonbatterypower.Followingsuccessfultest,energizeACcircuittobegin
battery charging cycle.
Note: ACONLEDblinkswhenbatteryisfullycharged.
REPLACING EMERGENCY LAMPS AND BATTERIES
General •Battery
1. De-energizetheACpowersupplytotheunit. 4. Removedefectivebattery.Recycleresponsibly.
2. Removeenclosurecover. Replacewithgenuinemanufacturerbatteryonly.
3. Disconnectpositive(+,red)batterylead(nickel cadmium models- 5. Placenewbatteryinenclosure.Make
disconnectbatteryandprintedcircuitboardconnectors). connectionsfollowingstepsoutlinedabove.
6. Test unit.
•Emergency Lamp
Plastic Sealed Beam Type Heads Plastic Sealed Beam Heads Metal Heads
4. Gentlyprylamplens 4. Prytoremove 4. Gentlypryretainingring
atarrowindicatormarks outerring. outofgrooveto
toremovelens. 5. Replacelamp. accesslamp.
5. Replacelamp. 5. Replacelamp.
Fig. 1 Pure-LeadOrLead-CalciumBattery
Fig. 2 Nickel-CadmiumBattery
Fig. 3 Single Harness Lead Connection
Pure-LeadOrLead-CalciumBatteries
Cover
Retaining
Screw &
Star Washer
Ground
Wire
(Green)
Tape,
Double Sided
Transformer Ground
Wire (Green)
RemoteDCLamps
Positive(+)LeadWith
“On-Board”Fuse
RemoteDCLamps
Negative(–)Lead(s)
Transformer
120VAC–White&Black
277VAC–White&Red
Note: PotentialShock
Hazard–Insulate Unusead
Lead
Test Switch
“ACOn”LED
YellowNegative(–)
BatteryLead
RedPositive(+)
BatteryLead
RemoteDCLamps
Positive(+)Lead(s)
With“On-Board”Fuse
RemoteDCLamps
Positive(+)Lead(s)
With“Off-Board”Fuse
RemoteDCLamps
Negative(–)Lead(s)
Ground
Wire
(Green)
Cover
Retaining
Screw &
Star Washer
Transformer–“OffBoard”
(ModelLM15NHas“OnBoard”
Transformer
120VAC–White&Black
277VAC–White&Brown
Note: PotentialShockHazard
–Insulate Unusead Lead
BatteryLeads
& Connectors
Test Switch
“ACOn”LED
Plate
Ground
Wire
(Green)
RemoteDCLamps
Negative(–)Lead
(Yellow) RemoteDCLamps
Positive(+)Lead
“On-Board”Fuse
(Blue)
12VoltPack
TopView
12VoltPack
12VoltPure-LeadPack
12VoltSingle
6VoltSingle
Enclosure
CircuitBoard
Tape, Typical
6VoltSinglePure-Lead
4. Identify unit as using either:
•lead calcium batteries(standardmodels,i.e.LM30,LMP66)or
•nickel cadmium batteries(modelnumberendingwith“N”,i.eLM30N,LMP50N-12V)
5. Connectremotelamps(ifused)toblue(+,fused)andyellow(–)leads(Fig.1orFig.2).
6. Connect120or277VACinputconnectionstotransformer(Fig.1orFig.2).Connectgreenwiretobuildingground.
Note:insulatetheunusedtransformerleadtopreventpotentialshockhazard.
Note: LM33l-03L with Spectron must use its internal lamp load (6W) in addition to a remote lamp load between 6W and
15W to obtain lamp sensitivity adjustment