Rosemount ProBar® Flowmeter Owner's manual

Type
Owner's manual
ProBar
Ā®
Flowmeter
Installation and
Operation Manual
00809-0100-4761
DS-4125
English
Rev. CA
Product Discontinued
Product Manual
ProBar
Ā®
Flowmeter
Installation and
Operation Manual
.
Rosemount, the Rosemount logotype, PlantWeb, Fisher-Rosemount, and Managing the Process Better are marks of one of
the Fisher-Rosemount group of companies. Coplanar, MV, and Multivariable are trademarks of Rosemount Inc.
Mass ProBar, ProBar, and Annubar are registered trademarks of Dieterich Standard Inc.
HART is a registered trademark of the HART Communications Foundation.
Monel is a registered trademark of International Nickel Co.
Teflon is a registered trademark of E. I. du Pont de Nemours & Co.
Hastelloy C and Hastelloy C-276 are registered trademarks of Cabot Corp.
Windows is a trademark of Microsoft Corp.
All other marks are the property of their respective owners.
Read this manual before working with the product. For personal and system safety, and
for optimum product performance, make sure you thoroughly understand the contents
before installing, using, or maintaining this product.
Contact Dieterich Standard Inc. for technical support, quoting, and order-related
questions: 1-303-530-9600
(7:30 a.m. to 5:00 p.m. MST).
Within the United States, Rosemount Inc. has two toll-free assistance numbers.
Customer Central: 1-800-999-9307 (7:00 a.m. to 7:00 p.m. CST)
Technical support, quoting, and order-related questions.
North American 1-800-654-7768 (24 hours a day ā€“ Includes Canada)
Response Center: Equipment service needs.
For equipment service or support needs outside the United States, contact your
local representative.
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or
products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local sales representative.
NOTICE
Fisher-Rosemount satisfies all obligations coming from legislation
to harmonize product requirements in the European Union.
Dieterich Standard Inc.
5601 North 71st Street
Boulder, CO 80301
Tel (303) 530-9600
Fax (303) 530-7064
P
R
I
N
T
E
D
IN
U.
S.
A.
http://www.rosemount.com
Probar Flowmeter Installation and Operation Manual
ii
Table of Contents
Procedures and instructions in this manual may require special precautions to
ensure the safety of the personnel performing the operations. Refer to the
safety messages at the beginning of each section before performing
any operations.
IMPORTANT
iii
SECTION 1:
Introduction
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
Installation Flowchart and Checklist . . . . . . . . . . . . . . . . . . . . . . . . .1-2
SECTION 2:
Installation Location
and Orientation
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
Receiving and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
ProBar Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Structural Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Functional Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Straight Run Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
ProBar Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
Process Connections (Remote Mounted ProBar only) . . . . . . . . .2-7
Mounting Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
Bolt Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
SECTION 3:
Hardware Installation
for ProBar Regular
(Threaded, Pak-Lok)
ProBar Models PBR+15S/16S, 25S/26S, 35S/36S, 45S/46S . . . . . 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
ProBar Regular Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Step 1: Determine the Proper ProBar Orientation . . . . . . . . . . . . . . .3-2
Liquid Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . .3-2
Gas Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
Steam Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . .3-3
Liquid or Gas Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . .3-4
Steam Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
Shipping Note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
Step 2: Drill the Hole in the Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-5
Drill a Hole for Opposite-Side Support . . . . . . . . . . . . . . . . . . . . .3-5
Step 3: Tack Weld the Fittings to the Pipe . . . . . . . . . . . . . . . . . . . . .3-6
Step 4: Insert the ProBar into the Pipe . . . . . . . . . . . . . . . . . . . . . . . .3-7
iv
SECTION 4:
Hardware Installation
for ProBar Flanged
ProBar Models PBF+15S/16S, 25S/26S, 25H/26H, 25M/26M,
35S/36S, 45S/46S, 45H/46H, 45M/46M . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1
ProBar Flanged Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-2
Step 1: Determine the Proper Orientation of the ProBar . . . . . . . . . .4-2
Liquid Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . .4-2
Gas Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .4-3
Steam Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . .4-3
Liquid Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .4-3
Gas Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-4
Steam Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .4-4
Shipping Note . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-4
Step 2: Drill the Hole in the Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-4
Drill a Hole for Opposite-Side Support . . . . . . . . . . . . . . . . . . . . .4-5
Step 3: Weld the Weld-Neck Flange . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5
Step 4: Assemble the ProBar and Mounting Hardware . . . . . . . . . . .4-5
Step 5: Check the Fit-Up of the ProBar to the Pipe . . . . . . . . . . . . . .4-6
Check the Fit-Up of the ProBar with Opposite-Side Support . . .4-7
Step 6: Tack Weld the Mounting Hardware . . . . . . . . . . . . . . . . . . . .4-8
Tack Weld the Opposite-Side Support Fitting . . . . . . . . . . . . . . .4-8
Step 7: Finish Welding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-8
Step 8: Assemble the ProBar and Mounting Flange . . . . . . . . . . . . . .4-9
Opposite-Side Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-9
SECTION 5:
Hardware Installation for
ProBar Flanged Flo-Tap
ProBar Models PHF+15S, 25S, 25M, 35S, 45S, 45H, 45M . . . . . 5-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
ProBar Flo-Tap Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-2
Step 1: Determine the Proper Orientation of the ProBar . . . . . . . . . .5-2
Liquid or Steam Service in a Horizontal Pipe . . . . . . . . . . . . . . .5-2
Gas Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .5-3
Liquid or Gas Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . .5-3
Steam Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .5-4
Step 2: Obtain the Required Welding Equipment and Hardware . . .5-4
Step 3: Prepare the Weld-Neck Flange Assembly . . . . . . . . . . . . . . . .5-5
Step 4: Weld the Weld-Neck Flange . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
Step 5: Attach the Unit Isolation Valve . . . . . . . . . . . . . . . . . . . . . . . .5-6
Step 6: Attach the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
Step 7: Attach the Pressure Drilling Machine . . . . . . . . . . . . . . . . . .5-6
Step 8: Drill the Hole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7
Step 9: Remove the Drilling Machine . . . . . . . . . . . . . . . . . . . . . . . . .5-7
Step 10: Install the Flo-Tap Assembly . . . . . . . . . . . . . . . . . . . . . . . . .5-7
Step 11: Open the Isolation Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7
Step 12: Tighten the Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7
Step 13: Insert the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-8
Standard Drive (IHR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-8
Gear Drive (IHD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9
Step 14: Check for Leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9
Step 15: Retract the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Standard Drive (IHR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Gear Drive (IHD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Step 16: Close the Isolation Valve . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Step 17: Remove the Flo-Tap Assembly . . . . . . . . . . . . . . . . . . . . . . .5-10
v
SECTION 6:
Hardware Installation for
ProBar Threaded Flo-Tap
ProBar Models PHT+15S, 25S, 35S . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
ProBar Flo-Tap Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-2
Step 1: Determine the Proper Orientation of the ProBar . . . . . . . . . .6-2
Liquid or Steam Service in a Horizontal Pipe . . . . . . . . . . . . . . .6-2
Gas Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .6-3
Liquid or Gas Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . .6-3
Steam Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . .6-4
Step 2: Obtain the Required Welding Equipment and Hardware . . .6-4
Step 3: Prepare the Weld-Neck Flange Assembly . . . . . . . . . . . . . . . .6-5
Step 4: Attach the Unit Isolation Valve . . . . . . . . . . . . . . . . . . . . . . . .6-5
Step 5: Attach the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-6
Step 6: Attach the Pressure Drilling Machine . . . . . . . . . . . . . . . . . .6-6
Step 7: Drill the Hole . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-6
Step 8: Remove the Drilling Machine . . . . . . . . . . . . . . . . . . . . . . . . .6-6
Step 9: Install the Flo-Tap Assembly . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Step 10: Open the Isolation Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Step 11: Tighten the Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Step 12: Insert the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-8
Standard Drive (IHR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-8
Gear Drive (IHD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-8
Step 13: Check for Leakage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-9
Step 14: Retract the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-9
Standard Drive (IHR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-9
Gear Drive (IHD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-10
Step 16: Close the Isolation Valve . . . . . . . . . . . . . . . . . . . . . . . . . . .6-10
Step 17: Remove the Flo-Tap Assembly . . . . . . . . . . . . . . . . . . . . . . .6-10
SECTION 7:
Hardware Installation
for ProBar In-Line
ProBar Models PNT+10S, PNW+10S, PNF+10S, 10H, 10M . . . . 7-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-1
ProBar In-Line Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-2
Liquid Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . .7-3
Gas Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-4
Steam Service in a Horizontal Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . .7-5
Liquid Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-6
Gas Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-7
Steam Service in a Vertical Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8
SECTION 8:
ProBar Remote Mounting
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-1
ProBar Valves and Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-2
Impulse Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-3
Equipment Required to Remote Mount the ProBar Electronics . . . .8-4
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-4
Supplies Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-4
Instrument Manifolds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-4
Location for the ProBar Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . .8-6
Liquid Service up to 250 Ā°F (121 Ā°C) . . . . . . . . . . . . . . . . . . . . . . .8-6
Gas Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-8
Steam or Liquid Service above 250 Ā°F (121 Ā°C) . . . . . . . . . . . . .8-10
vi
SECTION 9:
ProBar Electronics
Functions
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-1
Commissioning the Flowmeter on the Bench . . . . . . . . . . . . . . . . . . .9-2
Failure Mode Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-2
Failure Mode Alarm vs. Saturation Output Values . . . . . . . . . . .9-2
Alarm and Saturation Values for Flowmeters
Set to Burst Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-3
Alarm Level Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-3
Flowmeter Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-4
Commissioning the ProBar with a HART-Based Communicator . . . .9-5
Setting the Loop to Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-5
Wiring Diagrams (Bench Hook-up) . . . . . . . . . . . . . . . . . . . . . . . .9-5
Wiring Diagrams (Field Hook-up) . . . . . . . . . . . . . . . . . . . . . . . . .9-6
Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-7
Check Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-7
Process Variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-7
Sensor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-7
Basic Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-8
Set Process Variable Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-8
Set Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-8
Rerange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
Damping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-13
LCD Meter Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-13
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-14
Local Span and Zero Control . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-14
Diagnostics and Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-14
Transmitter Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-14
Loop Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-14
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-15
Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-16
Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-18
Analog Output Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-20
Advanced Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-21
Saving, Recalling, and Cloning Configuration Data . . . . . . . . . .9-21
Burst Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-22
Multidrop Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-22
SECTION 10:
Field Wiring and
Electrical Considerations
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-1
Wiring Diagrams (Field Hook-Up) . . . . . . . . . . . . . . . . . . . . . . . . . . .10-2
Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-2
Power Supply (4ā€“20mA Electronics) . . . . . . . . . . . . . . . . . . . . . . . . .10-2
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-3
Hazardous Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-3
Grounding the Signal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
Grounding the ProBar Case . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
Access Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
Process Flange Orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
Housing Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
Terminal Side of the Electronics Housing . . . . . . . . . . . . . . . . . .10-5
Circuit Side of the Electronics Housing . . . . . . . . . . . . . . . . . . .10-5
Exterior of the Electronics Housing . . . . . . . . . . . . . . . . . . . . . .10-5
Cover Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-5
vii
SECTION 11:
Direct Mount
ProBar Commissioning
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-1
Commissioning Direct Mounted ProBars . . . . . . . . . . . . . . . . . . . . .11-2
Liquid Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-2
Gas Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-3
Steam Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-4
SECTION 12:
Remote Mount
ProBar Commissioning
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-1
Commissioning Remote Mounted Flowmeters . . . . . . . . . . . . . . . . .12-2
ProBar Valve Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-2
Zero the Electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-3
Check for System Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-3
ā€œCalibrate Outā€ Temperature Effects . . . . . . . . . . . . . . . . . . . . .12-4
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-5
Liquid Service Below 250 Ā°F (121 Ā°C) . . . . . . . . . . . . . . . . . . . . .12-5
Gas Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-6
Steam Service or Liquid Service above 250 Ā°F (121 Ā°C) . . . . . . .12-7
SECTION 13:
Installation Options
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-1
Integral Zero and Span Adjustment Options . . . . . . . . . . . . . . . . . .13-1
Disabling the Zero and Span Adjustments . . . . . . . . . . . . . . . . .13-2
LCD Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-2
Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13-4
SECTION 14:
Maintenance for
the Optional RTD
ProBar RTD Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-1
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-1
Replacing a Direct Mount RTD . . . . . . . . . . . . . . . . . . . . . . . . . .14-2
Replacing a Remote Mount RTD . . . . . . . . . . . . . . . . . . . . . . . . .14-2
SECTION 15:
Troubleshooting
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-1
Before you Disassemble the ProBar Electronics . . . . . . . . . . . . . . . .15-3
Remove the Flowmeter from Service . . . . . . . . . . . . . . . . . . . . . . . . .15-4
Remove the Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-4
Remove the Electronics Board . . . . . . . . . . . . . . . . . . . . . . . . . . .15-5
Remove the Sensor Module from the Electronics Housing
(For service-type ProBar UC, uncalibrated ProBar only) . . . . . . . . .15-6
Attach the Sensor Module to the Electronics Housing Block . . . . . .15-7
Attahc the Electronics Board . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-8
Install the Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-9
Returning Products and/or Materials . . . . . . . . . . . . . . . . . . . . . . . .15-9
SECTION 16:
Specifications
and Reference Data
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-1
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-1
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-3
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-5
Flanged Pipe Section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-6
viii
APPENDIX A:
HART Communicator
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Connections and hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Communicator Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9
Fast Key Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11
Menus and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-12
Online Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-13
Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-14
APPENDIX B:
Standard ODF Dimensions
Standard ODF Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
APPENDIX C:
Approval Drawings
Approval Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1
INDEX
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I-1
Section
1-1
1 Introduction
USING THIS MANUAL
This product manual provides installation, configuration,
calibration, troubleshooting, and maintenance instructions
for the ProBar Flowmeter.
This section contains an explanation of each section of the manual, a
flowchart for using the manual, and an installation checklist.
Section 2: Installation Location and Orientation explains initial
inspection, operating limitations, and in what location and
orientation to install the ProBar Flowmeter.
Section 3: Hardware Installation for ProBar Regular (Threaded, Pak-Lok)
explains how to install the direct mounted regular ProBar model for
liquid, gas or steam service.
Section 4: Hardware Installation for ProBar Flanged explains how to
install the direct mounted flanged ProBar models for liquid, gas or
steam service.
Section 5: Hardware Installation for ProBar Flanged Flo-Tap explains
how to install the direct mounted Flo-Tap ProBar models for liquid,
gas or steam service.
Section 6: Hardware Installation for ProBar Threaded Flo-Tap explains
how to install the direct mounted Flo-Tap ProBar models for liquid,
gas or steam service.
Section 7: Hardware Installation for ProBar In-Line explains how to
install the direct in-line series ProBar for liquid, gas or steam service.
Section 8: ProBar Remote Mounting explains how to install the
remote mounted ProBar series flowmeter electronics for liquid,
gas or steam service.
Section 9: ProBar Electronic Functions provides information
for commissioning the electronics, including operation of the
software functions, configuration parameters, and on-line
variables of the flowmeter.
Section 10: Field Wiring and Electrical Considerations provides
electrical considerations and field wiring diagrams to wire
the ProBar flowmeter.
Section 11: Direct Mount ProBar Commissioning describes how to
commission a direct mounted ProBar flowmeter after installation.
ProBar Flowmeter
1-2
Section 12: Remote Mount ProBar Commissioning describes how to
commission a remote mounted ProBar flowmeter after installation.
Section 13: Installation Options provides information about LCD
meters and zero and span adjustment options.
Section 14: Maintenance for the Optional RTD provides information
on how to wire your integral or remote RTD and maintenance for
integral RTDs.
Section 15: Troubleshooting provides troubleshooting techniques for
common operating problems associated with the ProBar flowmeter.
Section 16: Specifications and Reference Data provides specification
and reference data for the ProBar flowmeter series.
Appendix A: HART Communicator contains a communicator overview,
a HART communicator menu tree for the ProBar model family, and a
table of diagnostic messages associated with the communicator.
Appendix B: Standard ODF Dimensions provides mounting height
dimensions necessary for installing the ProBar flowmeter.
Appendix C: Approval Drawings illustrates Factory Mutual (FM) and
Canadian Standards Association (CSA) certified drawings.
INSTALLATION
FLOWCHART AND
CHECKLIST
Figure 1-1 on page 1-3 shows an installation flowchart to provide
guidance through the ProBar installation process. Following the figure,
an installation checklist has been provided to verify that all critical
steps have been taken in the installation process. The checklist
numbers are indicated in the flowchart.
1-3
Introduction
FIGURE 1-1. ProBar Installation Chart
Steps 1, 2
Step 3
Step 4
Steps 5ā€“9
Steps 5ā€“9
Steps 11ā€“14
Steps 11ā€“14
ProBar Flowmeter
1-4
The following list is a summary of the steps required to complete a
ProBar flowmeter installation. If this is an entirely new installation,
begin with step 1. If the mounting is already in place, verify that the
hole size and the fittings match the recommended specifications, and
begin with step 5.
1. Determine where the ProBar is to be placed within the
piping system.
2. Establish the proper orientation as determined by the intended
ProBar service for the flowmeter.
3. Review Appendix C: Approval Drawings if the flowmeter is
located in a hazardous location.
4. Confirm the ProBar configuration.
5. Drill the correct size hole in the pipe.
ā€¢ For ProBar models equipped with opposite-side support, drill a
second, identical hole 180 degrees from the first hole.
6. Weld the mounting, and clean the burrs and welds.
7. Measure the pipeā€™s internal diameter (ID), preferably at 1 x ID
from the hole (upstream or downstream).
NOTE
Providing the pipe internal diameter at the time of purchase is
necessary to maintain published flowmeter accuracy.
8. Check the fit-up of the ProBar assembly to the pipe.
9. Install the flowmeter.
10. Wire the ProBar electronics.
11. Supply power to the flowmeter.
12. Perform a zero trim for mounting effects.
13. Check for leaks.
14. Commission the ProBar.
Section
2-1
2 Installation Location
and Orientation
This section describes the orientation, location, and alignment limits for
installing the ProBar flowmeter. Read it thoroughly before any
installation is performed.
SAFETY MESSAGES
Instructions and procedures in this section may require special
precautions to ensure the safety of the personnel performing the
operations. Please refer to the following safety messages before
performing any operation in this section.
RECEIVING
AND INSPECTION
ProBar flowmeters are available in different models and with different
options, so it is important to inspect and know which model you have
before beginning installation.
Upon receipt of the shipment, check the packing list against the material
received and the purchase order. All items are tagged
with a model number, serial number, and customer tag number.
Report any damage to the carrier.
Explosions could result in death or serious injury:
ā€¢ Do not remove the transmitter cover in explosive atmospheres when the circuit is alive.
ā€¢ Before connecting a HART-based communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
ā€¢ Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
ā€¢ Both transmitter covers must be fully engaged to meet explosion-proof requirements.
Failure to follow these installation guidelines could result in death or serious injury:
ā€¢ Make sure only qualified personnel perform the installation.
ProBar Flowmeter
2-2
PROBAR
CONFIGURATIONS
The ProBar is available in a variety of mounting configurations and has
two methods of electronic mounting: integral mount (or, direct mount)
and remote mount. An integrally-mounted ProBar may be shipped with
the electronics already bolted directly to the sensor.
FIGURE 2-1.
ProBar Mounting Configuration
Examples: A (Integral Mount)
and B (Remote Mount).
The ProBar may be purchased as a multipoint flow calibrated unit for
enhanced accuracy and turndown, or as a non-flow calibrated unit.
The multipoint flow calibrated units are identified by a note (or in the
model callout) which reads:
NOTE
Replacing the electronics may affect performance.
STRUCTURAL
LIMITATIONS
ProBar
Electronics
ProBar
Sensor
Mounting
Configuration
ProBar
Electronics
ProBar
Sensor
Mounting
Configuration
AB
8900-8900V30A, 8900_28A
Structural limitations are printed on the ProBar sensor tag. Exceeding the ProBar
structural limitations may cause the sensor to fail.
2-3
Installation Location and Orientation
FUNCTIONAL
LIMITATIONS
The ProBar best produces accurate and repeatable flow measurement
under the following conditions:
ā€¢ The maximum differential pressure, as printed on the tag
attached to the ProBar, is not exceeded.
ā€¢ The ProBar is not used for two-phase flow or for steam service
below saturation temperature.
Install the ProBar in the correct location within the piping branch to
prevent measurement inaccuracies caused by flow disturbances.
ProBar installation allows for a maximum misalignment of 3 degrees,
as illustrated in Figure 2-2. Misalignment beyond 3 degrees will cause
errors in flow measurement.
FIGURE 2-2.
Permissible Misalignment
for the ProBar.
Straight Run Requirements
Use Table 2-1 to determine the proper ProBar straight run requirements.
NOTES
For gas service, multiply values from Table 2-1 by 1.5.
If longer lengths of straight run are available, position the ProBar where
80% of the run is upstream of the ProBar and 20% is downstream.
Information contained in this manual applies to circular pipes only.
Consult the factory for instructions regarding ProBar use in square or
rectangular ducts.
Straightening vanes may be used to reduce the required straight run
length and will improve performance.
Row 6 in Table 2-1 applies to gate, globe, plug, and other throttling
valves that are partially opened. If a ā€œthrough-typeā€ valve will remain
open, use the values shown in Row 5. Refer to Row 6 for the straight
run requirements of a ProBar located downstream of the control valve.
3Ā° max.
3Ā° max. 3Ā° max.
8900-8900V14A
ProBar Flowmeter
2-4
TABLE 2-1. Straight Run Requirements.
Upstream dimension
Downstream
Dimensions
Without vanes With vanes
In plane
A
Out of
plane A
Aā€™ C Cā€™
8
ā€“
10
ā€“
ā€“
8
ā€“
4
ā€“
4
4
4
11
ā€“
16
ā€“
ā€“
8
ā€“
4
ā€“
4
4
4
23
ā€“
28
ā€“
ā€“
8
ā€“
4
ā€“
4
4
4
12
ā€“
12
ā€“
ā€“
8
ā€“
4
ā€“
4
4
4
18
ā€“
18
ā€“
ā€“
8
ā€“
4
ā€“
4
4
4
30
ā€“
30
ā€“
ā€“
8
ā€“
4
ā€“
4
4
4
1295-0573B
1.
1295-0573C
2.
1295-0573D
3.
1295-0573E
4.
1295-0573F
5.
1295-0573G
6.
2-5
Installation Location and Orientation
ENVIRONMENTAL
CONSIDERATIONS
Location of the ProBar in pulsating flow will cause a noisy signal.
Vibration can also distort the output signal and compromise the
structural limits of the flowmeter. Mount the ProBar in a secure
run of pipe as far as possible from pulsation sources such as check
valves, reciprocating compressors or pumps, and control valves. Mount
the transmitter to minimize ambient temperature changes. Section 15:
Specifications and Reference Data lists the temperature operating
limits. Mount the transmitter to avoid vibration and mechanical shock;
mounting will also avoid external contact with corrosive materials. See
Section 8: ProBar Electronics Functions for environmental
considerations.
ProBar Orientation
Proper venting or draining must be considered when selecting a
ProBar location.
For liquid service, mount the side drain/vent valve upward; this allows
gases to vent. For gas service, mount the drain/vent valve down to allow
any accumulated liquid to drain. In steam service, fill lines with water
to prevent contact of the live steam with the electronics; condensate
chambers are not needed because the volumetric displacement of the
electronics is negligible.
ProBar instrument head connections differ on horizontal and vertical
pipes. Refer to the specification head code number to confirm the
proper pipe orientation for your ProBar.
Horizontal Pipe:
Liquid or Steam Application
Due to the possibility of air getting trapped in the probe, the ProBar
should be located per the drawing below. The area between 0Ā° and
50Ā° (50Ā° angle) should not be used unless full bleeding of air from the
probe is possible. Figure 2-3 illustrates the recommended location
of the flowmeter.
FIGURE 2-3.
Liquid or Steam Service
in a Horizontal Pipe.
8900-8900V15A
80Ā° (Recommended Zone)
50Ā°50Ā°
ProBar Flowmeter
2-6
Horizontal Pipe:
Air and Gas Applications
The ProBar should be located on the upper half of the pipe, at least 30Ā°
above the horizontal line. Figure 2-4 illustrates the recommended
location of the flowmeter.
FIGURE 2-4.
Air and Gas Applications
in a Horizontal Pipe.
Vertical Pipe: Liquid, Air,
Gas, and Steam Applications
The ProBar can be installed in any position around the circumference of
the pipe, provided the vents are positioned properly for bleeding or
venting. Vertical pipe installations require more frequent bleeding or
venting depending on the location. Figure 2-5 illustrates the
recommended location of the flowmeter.
FIGURE 2-5.
Liquid, Air, and Gas Applications
in a Vertical Pipe.
Remote mounting is required for steam installations; see Figure 2-6.
FIGURE 2-6.
Steam Service in a Vertical Pipe.
8900-8900V16A
120Ā° (Recommended
Zone)
30Ā° 30Ā°
8900-8900V19A
Flow
360Ā°
Opposite-Side Support
ProBar
Remote Head
8900-8900_04A
Instrument Valve
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188

Rosemount ProBar® Flowmeter Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI