Zodiac Z300 Series Instructions For Installation And Use Manual

Category
Heat pumps
Type
Instructions For Installation And Use Manual

Zodiac Z300 Series

The Zodiac Z300 Series heat pumps are designed to heat swimming pools, extending their use throughout the year. With a wide range of models available, there is a solution for pools of all sizes. With its efficient and environmentally friendly operation, the Z300 Series offers a cost-effective way to enjoy a warm and inviting pool.

  • Efficient and economical: The Z300 Series heat pumps use advanced technology to efficiently transfer heat from the air to the pool water, resulting in low operating costs.

  • Environmentally friendly: The Z300 Series heat pumps use R410A refrigerant, which has a low global warming potential, making it an environmentally friendly choice.

Zodiac Z300 Series

The Zodiac Z300 Series heat pumps are designed to heat swimming pools, extending their use throughout the year. With a wide range of models available, there is a solution for pools of all sizes. With its efficient and environmentally friendly operation, the Z300 Series offers a cost-effective way to enjoy a warm and inviting pool.

  • Efficient and economical: The Z300 Series heat pumps use advanced technology to efficiently transfer heat from the air to the pool water, resulting in low operating costs.

  • Environmentally friendly: The Z300 Series heat pumps use R410A refrigerant, which has a low global warming potential, making it an environmentally friendly choice.

H0439100.A - 2013/10
Instruc ons for installa on and use
English
More languages on:
www.zodiac-poolcare.com
H0439100.A1.EN2013/10
1
Readthismanualcarefullybeforeinstalling,maintaining,orrepairingthisdevice!
Thesymbolindicatesimportantinformationthatmustbetakenintoaccountinordertoavoid
riskofpersonalinjuryand/ordamagetotheappliance.
Thesymbolindicatesusefulinformation.
Warnings
Ourproductsmaybesubjecttochangewithoutnoticeaspartofourcontinuousimprovement
policy.
Exclusiveuse:poolwaterheating(mustnotbeusedforanyotherpurpose).
Thedevicemustbeinstalledbyaqualifiedtechnicianaccordingtothemanufacturer’sinstructions
andincompliancewithlocalregulations.Theinstallerisresponsibleforthecorrectinstallationof
thedeviceandforensuringcompliancewithlocalregulations.Themanufacturershallnotbeheld
liableforanypotentialissuesthatmayoccurasaresultoffailuretocomplywithlocalstandards
pertainingtoinstallation.
Thisappliancemustbehandledbycompetentandqualifiedpersonnel(physicallyandmentally)who
arefamiliarwiththeoperatinginstructions(byreadingtheuserguide).Individualswhodonot
satisfytheserequirementsmustnothandlethedevicesoastoavoidexposuretopotentially
dangerousparts.
Inthecaseofdevicemalfunction:donotattempttorepairthedeviceyourself,callyourinstaller.
Beforecarryingoutanyoperationonthedevice,ensurethatthepowersupplyisoff,thatthedevice
isdecommissioned,andthatthe"heatingpriority"functionisdeactivated.
Beforereconnectinganycomponent,checkthatthevoltageindicatedonthedevicecorrespondsto
themainsvoltage.
Ifanysafetydeviceisremovedorshunted,thewarrantywillautomaticallybevoid.Thiswillalso
applyifpartsarereplacedwithpartsacquiredelsewherethaninourstores.
DonotventR410Afluidintotheatmosphere:R410Aisafluorinatedgreenhousegasthatiscovered
bytheKyotoProtocol,withaGlobalWarmingPotential(GWP)=1975‐(seeregulationon
fluorinatedgreenhousegases,EuropeanCommunityDirectiveEC842/2006).
Incorrectinstallationmaycauseseriousdamageand/orpersonalinjuries(potentiallydeath).
Keepthedeviceoutofthereachofchildren.
Thisheatpumpiscompatiblewithalltypesofwatertreatmentsystems.
H0439100.A1.EN2013/10
2
Summary
1.Informationbeforeinstallation................................................................................2
1.1Generaltermsofdelivery,storageandtransport.......................................................................................2
1.2Content........................................................................................................................................................2
1.3Operatingconditions...................................................................................................................................3
1.4Technicalspecifications...............................................................................................................................3
2.Installation...............................................................................................................3
2.1Accesstothetechnicalcompartment.........................................................................................................3
2.2Selectinganinstallationsite........................................................................................................................3
2.3Installingthedevice.....................................................................................................................................4
2.4Hydraulicconnections..................................................................................................................................4
2.5Electricalconnections..................................................................................................................................5
3.Use..........................................................................................................................7
3.1Presentationoftheregulation.....................................................................................................................7
3.2Startingthedevice.......................................................................................................................................8
3.3Checkstoperformafterstartup.................................................................................................................8
3.4Winterstorage.............................................................................................................................................9
4.Maintenance............................................................................................................9
4.1Maintenanceinstructions............................................................................................................................9
4.2Additionalrecommendations......................................................................................................................9
4.3Availableaccessories.................................................................................................................................10
4.4Recycling....................................................................................................................................................10
5.Troubleshooting....................................................................................................10
5.1Displayoftheregulator.............................................................................................................................10
5.2Sovlingmalfunctions..................................................................................................................................12
5.3FAQ.............................................................................................................................................................12
6.Productregistration...............................................................................................13
Informationincludedattheendofthemanual:
- wiringdiagrams
- dimensions
- description
- compliancecertificate

1.Informationbeforeinstallation
1.1Generaltermsofdelivery,storageandtransport
Anyequipment,evenshippingandpackingfree,travelsattheconsignee'srisk.Ifanydamagecausedduring
transportisidentified,theconsigneeshouldmakeanyreservationsinwritingonthecarrier'sbilloflading
(confirmationtobesenttothecarrierwithin48hoursbyregisteredmailwithacknowledgementofreceipt).
Thedevicemustbetransportedandstoreduprightonitspalletinitsoriginalpackaging.
Ifthedevicehasbeenturnedonitsside,thisshouldbementionedinthereservationsmadeinwritingtothe
carrier.
1.2Content
Ø50
X1X2X2X1
inabaginthetechnicalcompartment,see§2.1
H0439100.A1.EN2013/10
3
1.3Operatingconditions
Operatingrange:
airtemperatureofbetween5°Cand38°Cforstandardmodels,
airtemperatureofbetween‐8°Cand38°CforDmodels,
watertemperatureofbetween10°Cand32°C,
Maximumtemperatureof32°Ctoprotectthepoolliner.
TheDversionalsofeaturesadeicingfunctionbyusingforcedventilationorreversedcycle.
1.4Technicalspecifications
Z300VoltagePowerinput* Poweroutput*Nominalcurrentinput*COP*
kWkWA
M4230V50Hz1.77.67.94.5
M5230V50Hz2.210.410.34.7
T5400V50Hz2.210.54.254.8
M7230V50Hz2.8813.9134.8
MD5230V50Hz2.210.7104.9
TD5400V50Hz2.210.54.44.8
MD8230V50Hz3.615.7164.5
TD8400V50Hz3.615.77.44.5
*withambientairat+15°C,poolwaterat26°C,andrelativehumidityof70%(accordingtoFrenchstandardNF
414)
protectionclass:IP24
refrigerantgas:R410A
refrigerantcharge:seeproductinformationplate
class:I,
degreeofpollution:2,
overvoltagecategory:II
2.Installation
Donottakegripontheoutercasingtopickupthedevice,holdthebase.
2.1Accesstothetechnicalcompartment
  
2.2Selectinganinstallationsite
Thedevicemustbeinstalledoutdoorsandtheremustbeadequateopenspacesurroundingit(see
§2.4).
theheatpumpmustbeinstalledatacertaindistancefromthepoolsoastoavoidexposuretowatersplashes.
Theappropriatedistanceshouldbedefinedaccordingtothenationalelectricalstandardsthatapplyinthe
countryofinstallation(forFrance:3.5meters).
theheatpumpmustnotbeinstalled:
- nearasourceofheatorinflammablegas,
- neararoad/passagewherethereisariskofwaterandmudsplashes,
- facingastrongwind,
- withtheventfacingtowardapermanentortemporaryobstacle(window,wall,hedge,etc…),itmustbeat
least4metersfromanypotentialobstacle.
H0439100.A1.EN2013/10
4
2.3Installingthedevice
placeonastable,solid(concreteslabtype),levelandplanesurface,
ensurethatitwillnotbefloodedbycondensationwaterproducedbythedeviceduringoperation(see§2.4)
Theantivibrationblocsarefittedunderthebaseoftheheatpump.
Theheatpumpcanbefixedtothegroundusingthebracketsatthebaseoftheunit(attachmentsnot
included).Adiagramfordrillingisfeaturedonthebackofthepackingbox.
2.4Hydraulicconnections
Checkthedirectionofthepipeworkconnection(see§“Dimensions”intheappendix).
TheconnectionincludeaØ50PVCrigidpipe,fromabypass,ontheswimmingpoolfiltrationcircuit,afterthe
filterandbeforeanywatertreatmentunit.
checkthetighteningofthehydraulicconnections,andcheckforleaks,
Z300
HydrauliccircuitpressureConnections
=inlet
=outlet
Meanwater
flowrate
Headloss
test
test service
barbarm³/hmCE
M4
31.5Ø50
41.4
M5T5
MD5TD551.5
M761.5
MD8TD86.51.1
V1V2V3:bypassvalves
V5V4:settingvalves(optional)
*minimumdistance
bypass
filter
watertreatmentunit
electricalprotectionboxes
Fixingholes
H0439100.A1.EN2013/10
5
Disposingofcondensation:
Warning:yourdevicecanproduceseverallitresofwaterperday.Itisstronglyrecommendedtoguidethe
flowtodrains.
connectaØ18interiorpipe(notsupplied),tothegroovedendpiecemountedonthebaseofthe
appliance,
outlet:tothebackorontheside:
2.5Electricalconnections
2.5.1Voltageandprotection
theelectricalsupplytotheheatpumpmustincludeaprotectionandcircuitbreakerdevice(notsupplied)
complyingwiththestandardsandregulationsinforceinthecountry,
additionalprotectionmayberequiredduringinstallationtoprotectagainstovervoltagecategoryII,
thedeviceisdesignedforconnectiontoageneralpowergridwithTTandTN.Sgroundingsystems,
electricalprotection:circuitbreaker(curveD)orfuse(Am)(see§2.5.3forratings),andwitha30mAdedicated
differentialtripswitch(circuitbreakerorswitch).
electricalconduitsmustbesecured,
toleranceforvoltagevariation:±6%(duringoperation),
usecablesuitableforoutdooruse,typeRO2VorequivalentincountriesoutsideoftheEuropean
community,withanouterdiameterbetween9and18mm,
usethecableglandtorunthesupplycableintothedevice.
2.5.2Connections
theelectricalsupplycablemustnotbeexposedtoelementsthataresharp,hotoratriskofbeingcrushed,
checkthatallcablesaresecureandallterminalconnectionsarecorrect.
Looseterminalsmaycausethesupplyterminalboardtooverheatandwillvoidthewarranty.
Thedevicemustbeconnectedtotheearth(grounded)
Riskofelectricshockinsidethedevice
Thedevicemustonlybecommissionedbyaqualifiedandexperiencedtechnician
Ifthepowercableisdamaged,itmustbereplacedbyaqualifiedtechnician
Singlephase Threephase

2.5.3Cablecrosssections
•supplycablecrosssection:cableswithamaximumlengthof20metres(calculationbase:5A/mm²),mustbe
checkedandadapteddependingoninstallationconditions.

Z300VoltageMaximumIinputCablecrosssectionElectricalprotection
Amm²  A
M4230V50Hz103x2.5 3G2.516
M6MD6230V50Hz14.53x2.5 3G2.516
T6TD6400V50Hz55x2.55G2.510
M7230V50Hz16.13x43G420
MD8230V50Hz223x6 3G625
TD8400V50Hz9.45x2.55G2.510
phase(L)+neutral(N)+Earth(PE)phases(L1+L2+L3)+neutral(N)
+Earth(PE)
H0439100.A1.EN2013/10
6
2.5.4Connectionofoptions
usecableswithacrosssection:of2x0.75mm²orlarger,oftypeRO2Vorequivalentincountriesoutsideofthe
EuropeanCommunity,withanouterdiameterofbetween8and13mm.
Removethelid(justabovethecablegland)andfitthesuppliedcableglandstorunthecablesintothe
device.Thecablesusedfortheoptionalfeaturesandthepowersupplymustbeheldtogetherusinga
collarinsidethedevice,justafterthecablegland.
Anyincorrectconnectiontoterminals1to8coulddamagetheregulatorandvoidthewarranty.
Neversupplythemotorofthefilterpumpdirectlyusingterminals12.
Iforangeterminals1to8areserviced,backcurrentmayexist.
"heatingpriority"
- Function:servofunctiontocontrolthefiltrationpumpoperation(byaminimum5minutecycleeveryhour,
withfiltrationmaintainedifthepooltemperatureisbelowtherequiredtemperature),
- thankstoadrycontact(withoutmax.Ipolarity=8A)
- betweenterminals12,
alarm
- Function:connectarelaytothealarmterminal,
- thankstoadrycontact(withoutmax.Ipolarity=2A)
- betweenterminals56,
remoteon/offcontrol
- Function:connectaremote"start/stop"button
- thankstoazeropotentialfreecontact,without230V‐50Hzpolarity,connectthecabletothebusbar
betweenterminals78,
- activatethecommandbypressingfor5secondswhenregulationisnotonstandby:
then,thenpress3secondson :,select“Yes”usingkey ,then
validatebypressing :,presstoexit.

remotecontrolunit
- Function:controltheheatpumpremotely,
- refertotheinstructionsfortheremotecontrolunitforconnections.
filtertimer
powercontactor(3poleor2pole),supplyingthe
filterpump
A1A2:supplytothepowercontactorcoilofthefilter
pump
independentconnectingcableforthe"heating
priority"function
terminal
independentconnectingcableforalarmcontact
relay
alarmcontactrelay
remoteon/offswitch
independentconnectingcableforremoteon/off
control
PhasePhase
Neutral
Neutral
H0439100.A1.EN2013/10
7
3.Use
3.1Presentationoftheregulation
SymbolDesignationsteadyflashing
waterflowwaterflowrateokwaterflowtooweak,highorabsent
ambientairtemperatureadequateinadequate
operationindicatorDuringheatingorair
conditioning
Onstandbyuntiloperatingcommand
received
defrostindicatorDefrostinprogress/
On/offbutton
buttontosetandconfirmparameters

valuesettingbuttons
3.1.1Readingandchangingparameters
Watertemperature
Setpointtemperature
Coldmode
(onlyonDmodels)
H0439100.A1.EN2013/10
8
3.1.2Lockingandreleasingthekeypad
Pressandfor3seconds:or
3.2Startingthedevice
checkthatnotoolsorotherobjectshavebeenleftinsidethedevice,
theaccessdoorfortechnicalcomponentsmustbefitted,
setthebypassandsettingvalves(see§2.4)asfollows:
- valve1completelyopen,
- valves234&5closed.
Anincorrectsettingofthebypassvalvemayleadtodevicemalfunction
switchonthefiltersystem,
progressivelyclosevalve1inordertoincreasethefilterpressureto150g(0.150bar),
openvalves2,3and4completely,thenhalfopenvalve5(see§2.4)(theairaccumulatedintheheatpump
condenserandinthefiltercircuitisthenbled),
Ifvalves4and5arenotfitted,openvalve1completely,andhalfclosevalve3.
poweruptheheatpump,
iftheheatpumpisonstandby:,pressonfor3seconds,willappear
for2seconds,and(dieSoftnummerhängtvondemModellab)for3seconds,andthewater
andsetpointtemperatureswillbedisplayed:,a2minutedelaywillstart,
settherequiredwatertemperature:
- presstoincreasetemperature,
- presstodecreasetemperature,
Whenthepoolreachestherequiredtemperature,theheatpumpwillautomaticallystop.
setthewaterflowrateusingthemenu,whentheindicatorissteady:presstodisplaythewater
flowratestatus:
Statuswaterflowrateoknowaterflowwaterflowratetooweakwaterflowratetoostrong
Display
settheflowrateusingvalve5(or3ifnovalve5isfitted),and,toquitthemenu,press .
Duringthisadjustmentphase,waitforafewminutesaftereachchangeinvalvepositiontoallowthe
devicetobalance.
3.3Checkstoperformafterstartup
Theheatpumpmuststopwhen:
thesetpointtemperatureisloweredusingthedigitalcontrolpanel,
filteringisstoppedorvalve2or3isclosed3,
thedigitalcontrolpanelisturnedoffbypressing ,
H0439100.A1.EN2013/10
9
3.4Winterstorage
Winterstorageisessentialduetotheriskofthecondenserfreezingandbreaking.Thissituationisnot
coveredbythewarranty.
Toavoiddamagingthedevicewithcondensation,donotcoveritwithanairtightcover.
switchthedigitalcontrolpanelto"standby"modebypressingfor3seconds,andcutthepowersupply,
openvalve1,
closevalves2and3,andopenvalves4and5(iffitted),
ensurethatnowaterisflowingthroughtheheatpump,
drainthewatercondenserbyunscrewingthetwopoolwaterinletandoutletconnectionsatthebackofthe
heatpump,
inthecaseoffullwinterstorageconditionsforthepool:reconnecttheinletandoutletconnectionstoavoid
foreignbodiesenteringintothecondenser,
inthecaseofwinterstoragefortheheatpumpalone:donotreconnecttheinletandoutletconnectors,instead
placetwoplugs(supplied)onthecondenserwaterinletandoutlet.
covertheheatpumpwithamicrobreathingoverwinteringcover(optionalaccessory,see§4.3).
4.Maintenance
4.1Maintenanceinstructions
Itisrecommendedthatthedevicebegeneralservicedonayearlybasistoensureproperoperation,
maintainperformancelevelsandpreventsomepotentialfailures.
Thisistheresponsibilityoftheuserandmustbeperformedbyaqualifiedtechnician.
Donotuseahighpressurewaterhose.
ensurenoforeignbodiesobstructthefangrid.
cleantheevaporatorwithasoftbrushandafreshwaterjet(disconnectthepowercable),donottwistorbend
themetalblades,thentocleanthedischargepipeofthecondensatesinordertoevacuatetheimpuritieswhich
couldblockit,
cleantheoutsideoftheunitwithasolventfreeproduct.AspecificPACNETcleaningkitisavailableasan
optionalextra(see§4.3),
checkthatthewatercondensationflowsoutproperlyduringtheoperationofthedevice.
checktheproperoperationoftheregulator,
checkelectricalcomponents,
checkthatallmetalelementsaregrounded,
checkthetighteningandconnectionsofelectriccablesandthecleanlinessoftheelectricalcompartment.
4.2Additionalrecommendations
inrelationtothePressureEquipmentDirective(PED97/23/CE)
4.2.1Installationandmaintenance
theunitmaynotbeinstalledclosetocombustiblematerials,ortheairductinletofanadjacentbuilding.
withsomedevices,itisessentialtofitprotectiongridsiftheunitisinstalledinanareawithuncontrolledaccess.
duringinstallation,troubleshootingandmaintenance,pipesmaynotbeusedassteps:thepipecouldbreak
undertheweight,spillingrefrigerantandpossiblycausingseriousburns.
whenservicingtheappliance,thecompositionandstateofheatcarryingfluidmustbechecked,aswellasthe
absenceofanyrefrigerant.
duringtheannualunitsealingtestinaccordancewithapplicablelegislation,thehighandlowpressureswitches
mustbecheckedtoensurethattheyaresecurelyfastenedtothecoolantcircuitandthattheycutoffthe
electricalcircuitwhentripped.
duringmaintenancework,ensuretherearenotracesofcorrosionoroilaroundcoolingcomponents.
beforebeginningworkonthecoolingcircuit,stopthedeviceandwaitforafewminutesbeforefittingthe
temperatureandpressuresensors.Someelementssuchasthecompressorandpipingmayreachtemperatures
inexcessof100°Candhighpressureswiththeconsequentriskofseverescalding.
H0439100.A1.EN2013/10
10
4.2.2Troubleshooting
allsolderingworkmustbecarriedoutbyasomeonequalifiedtodoso.
replacementpipesmustalwaysbemadeofcopperincompliancewithstandardNFEN127351.
leakdetection;pressuretest:
- neveruseoxygenordryair,riskoffireorexplosion,
- usedrynitrogenorthemixtureofnitrogenandrefrigerantindicatedontheinformationplate,
- thetestpressureforboththehighandlowpressurecircuitsmustnotexceed42bar.
thehighpressurecircuitpipesaremadeofcopperandhaveadiameterequaltoorgreaterthan1’’5/8.A
certificateasindicatedin§2.1incompliancewithstandardNFEN10204willberequestedfromthesupplierand
filedininstallationtechnicaldocumentation.
technicaldatarelativetothesafetyrequirementsofthevariousapplicabledirectivesmustbeindicatedonthe
informationplate.
Thisdatamustberecordedintheinstallationinstructionsforthedevicewhichareincludedintheinstallation
technicalfile:model,code,serialnumber,maximumandminimumOT,OP,yearofmanufacture,EClabel,
manufacturer’saddress,refrigerantandweight,electricalparameters,thermodynamicandacoustic
performances.
4.3Availableaccessories
NamePACNETWinteringcoverRemotecontrolunitTechnicalroomkit
Representation

4.4Recycling
Thissymbolmeansthatyourdevicemustnotbethrowninthebin.Thedevicemustbecollectedbya
selectivesysteminviewofreuse,recyclingorsimilar.Anysubstancesitmaycontainwhichare
potentiallydangeroustotheenvironmentshallbeeliminatedorneutralised.
Requestinformationonrecyclingproceduresfromyourretailer.
5.Troubleshooting
5.1Displayoftheregulator
DisplayDesignationCauseSolutionReset
Protectionof
heatexchanger
incoldmode
TemperatureofST4
sensortoolow
Waitforthesurrounding
temperaturetobecome
warmer
Automatic
High
temperature
defectforthe
evaporatorin
"cooling"mode
TemperatureprobeST3
above60°Cor
evaporatorscaledup
Cleantheevaporator,ifthe
defectpersists,contactan
approvedtechnician
Automaticif
temperature
probeST3is
below45°C
Phaseorder
defect(onlyon
threephased
models)
1.wiringincorrecton
thesupplyterminal
boardofthedevice,
2.modificationofphase
orderbyelectrical
supplier,
3.temporaryfailureof
oneorseveralphases
1.reversethephasesonthe
supplyterminalboard
(withoutpowertothedevice)
2,3,4.contactyourelectricity
providertofindoutif
modificationshavebeenmade
toyourequipment.
Switchthe
power
supplyoffor
press
H0439100.A1.EN2013/10
11
DisplayDesignationCauseSolutionReset
Refrigerant
circuitlow
pressuredefect
Lowpressurecircuit
pressuredefect(if
thedefectremains
afterreset)
Contactanapproved
technician
Automaticreset
(forlessthan4
defectsperhour)
orpress
Refrigerant
circuithigh
pressuredefect
1.waterandair
mixturepassingin
theappliance,
2.unsatisfactory
waterflow,
3.blockedflow
controller
4.cloggedorblocked
heatexchanger
1.checkthepoolhydraulic
circuit
2.increasetheflowrate
usingthebypass,checkthat
thepoolfilterisnotclogged)
3.checktheflowrate
controller
4.cleantheexchanger
5.ifthedefectpersists,
contactanapproved
technician
Automaticreset
(forlessthan4
defectsperhour)
orpress
Compressor
discharge
temperature
defect
Compressor
discharge
temperaturetoo
high
contactanapproved
technician
pressfor3
seconds
Controlsensor
defect(ST1)
Sensoroutoforder
ordisconnected
(connectorJ2redon
plateA1)
Replaceorreconnectthe
sensor
Switchthepower
supplyoffor
press
Waterflowrate
sensordefect
(ST4)
Sensoroutoforder
ordisconnected
(connectorJ8white
onplateA1)
Replaceorreconnectthe
sensor
Switchthepower
supplyoffor
automaticresetif
thedefect
disappears
Defrostsensor
defect(ST3)
Sensoroutoforder
ordisconnected
(terminals12of
connectorJ3white
onplateA2)
Replaceorreconnectthe
sensor
Switchthepower
supplyoffor
press
Antifreeze
sensordefect
(ST2)
Sensoroutoforder
ordisconnected
(terminals
34ofconnectorJ3
whiteonplateA2)
Replaceorreconnectthe
sensor
Switchthepower
supplyoffor
press
Compressor
discharge
sensordefect
(ST5)
Sensoroutoforder
ordisconnected
(connectorJ7black
onplateA1)
Replaceorreconnectthe
sensor
Switchthepower
supplyoffor
automaticresetif
thedefect
disappears.
Communication
s'defect
betweenthe
maincardA1
andthedisplay
cardA2
1.Incorrect
connectionbetween
platesA1andA2
2.Cardsupplydefect
3.Cardsoutoforder
1and2.Checkconnections
(connectorsJ8andJ9yellow,
andJ7andJ4J5black)
1,2and3.ifthedefect
persists,contactan
approvedtechnician
Switchthepower
supplyoffor
automaticresetif
thedefect
disappears
H0439100.A1.EN2013/10 12
5.2Solvingdevicemalfunctions
DysfunctionCausesVerification/solution
Thedeviceisnot
operational
NodisplayCheckthesupplyvoltageandthefuseF1
Thepooltemperatureisabovethe
setpointtemperatureIncreasethesetpointtemperature
AmessageisdisplayedonthescreenCheckthemeaningofmessage§5.1
AbsentorinadequatewaterflowrateCheckthewaterflowrate(bypass,filtration)
Thedeviceis
operational,butwater
temperaturefailsto
rise
InadequatefilteringtimeSetthefilteringsystemtomanual24‐hour
operationfortemperaturecontrol
NoncompliantperiodofuseCheckthatoutdoortemperatureiswithinthe
operatingrange(see§1.3)
TheheatpumpisunderdimensionedCheckthecharacteristicsoftheheatpump
accordingtothepool
Theautomaticpoolwaterfilleris
blockedintheopenposition
Checkthecorrectoperationoftheautomatic
filler
TheheatinsulatingcoverisnotusedFittheheatinsulatingcover
TheevaporatoriscloggedCleantheevaporator(see§4.1)
Thedeviceisincorrectlyinstalled
Thedevicemustbeinstalledoutdoors.
Checkthatthereisnoobstaclelessthan4
metresfromwheretheblowerisfacing,and
0.50metresbehindtheheatpump.
AmessageisdisplayedonthescreenCheckthemeaningofmessage§5.1
Thefanisturning,but
thecompressorstops
fromtimetotime
withoutanerror
messageappearing
Theheatpumpdoesdefrostcycles
fromtimetotime
Thisisnormaliftheoutdoortemperatureis
below10°C
TheevaporatoriscloggedCleantheevaporator(see§4.1)
theheatpumpmakes
tripthecircuitbreaker
Thecircuitbreakerratingistoolowor
inappropriate
Checkthecircuitbreaker(see§2.5.3).
ThecablecrosssectionistoosmallCheckthecablecrosssection(see§2.5.3)
ThesupplyvoltageistoolowCallyourelectricityprovider
Voltagedropswhenthecompressor
ispoweredon
AddasoftstarterformodelsM5,MD5and
M7
Varistor(s)VA1and/orVA2is/areout
oforderReplacethevaristor(s)
5.3FAQ
Isitpossibleto
improve
temperature
performance?
Inorderto
improvethe
efficiencyof
yourheat
pumpitis
recommended
thatyou:
protectthepoolwithacover(floatingcover,rollercover,etc.),toavoidheat
loss
chooseperiodswhentheoutsidetemperatureiswarm(onaverage>10°C)
inordertofacilitatethetemperatureincrease(thismaytakeseveraldays.
Theactualtimewillvaryaccordingtoweatherconditionsandthepowerof
theheatpump)
thehighertheambientairtemperature,themoreefficienttheheatpump
willbe
keeptheevaporatorclean
Checkthat
filtrationtime
issufficient
duringtheheatingphase,waterflowmustbecontinuous(24/24)
tomaintainthetemperaturethroughouttheseason,allowfor“automatic”
flowofatleast12hours/day(thelongerautomaticflowisused,themore
timetheheatpumpwillhavetofunctionandtoheatthewater)
Settingthesetpointtomaximumwillnotheatthewateranyfaster
H0439100.A1.EN2013/10 13
Whyismyheat
pumpnotheating?
onstartupthedeviceremainson“pause”for3minutesbeforeactuallystartingup:
checkthatthisperiodhaspassed
oncethepoolhasreachedthesetpointtemperature,theheatpumpswitchesoff:check
thatthewatertemperatureislowerthantherequestedtemperature(see§3.2)
ifthewaterflowrateiszeroorinadequate,theheatpumpwillstop:checkthatwateris
flowingcorrectlythroughtheheatpump,andcheckthehydraulicconnections
whentheoutdoorairtemperaturedropsbelow5or‐8°C,theheatpumpwillstop:check
theoutdoortemperature
theheatpumpmayhavedetectedamalfunction:checkifanerrorcodeisdisplayedon
thescreen,ifsoreferto§5.1
Iftheproblempersistsafteryouhavecheckedalloftheabovepoints:contactyour
installer
Whereshouldmy
watertreatment
systembe
positionedwith
respecttothe
heatingsystem?
Thewatertreatmentsystem(chlorinator,saltchlorinator,etc.)mustbeinstalled
preferablydownstreamfromtheheatpump(seeinstallation§2.4),andmustbe
compatiblewiththelatter(checkwiththemanufacturer)
Theheatpumpis
givingoffwater:is
thisnormal?
Yourheatpumpwillgiveoffwaterintheformofcondensation.Thiswateristhe
humiditycontainedintheair,whichcondensesoncontactwithcertaincoldcomponents
insidetheheatpump.
Note:yourdevicecanproduceseverallitresofwaterperday.
6.Productregistration
Registeryourproductusingourwebsite:
- youwillbeamongthefirsttobeinformedofnewZodiacproductsandspecialoffers,
- Youcanhelpustoconstantlyimproveourproductquality.
AustraliaNewZealandwww.zodiac.com.au
Europe,SouthAfricaandrestoftheworldwww.zodiacpoolcare.com
H0439100.A1.FR2013/10 1
Schémaélectrique
Z300M4M5M7
H0439100.A1.FR2013/10 2
Z300T5
H0439100.A1.FR2013/10 3
Z300MD5
H0439100.A1.FR2013/10 4
Z300MD8
H0439100.A1.FR2013/10 5
Z300TD5TD8
H0439100.A1.FR2013/10
6
LNPEAlimentation(230V1N50Hz)
L1L2L3NPEAlimentation(400V/3N/50Hz)
PE()Terre
12Commandepompe(contact8Amaximum)
34Commanderéchauffeurélectrique(contact2Amaximum)
56Commandealarme(contact2Amaximum)
78Commandeàdistance
20SBobinevanne4voies
A1Carteélectroniquederégulation
A2Carteélectroniqued’affichage
C1Condensateurventilateur
C2Condensateurcompresseur
C3filtre
D1Démarreurprogressif
HRésistancedégivrage
HPPressostathautepression
LPPressostatbassepression
J1Interrupteurdedébit
M1Moteurventilateur
M2Moteurcompresseur
MOVDétendeur
PHCContrôleurd’ordredephase
R1R2Contacteur
ST1Sondederégulation
ST2Sondeantigel
ST3Sondededégivrage
ST4Sondeligneliquide
ST5Sonderefoulementcompresseur
VA1VA2varistance
BKNoir
BNMarron
BUBleu
GGris
GN/YEVert/jaune
PKrose
OGOrange
RDRouge
VTViolet
WHBlanc
YEJaune
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22

Zodiac Z300 Series Instructions For Installation And Use Manual

Category
Heat pumps
Type
Instructions For Installation And Use Manual

Zodiac Z300 Series

The Zodiac Z300 Series heat pumps are designed to heat swimming pools, extending their use throughout the year. With a wide range of models available, there is a solution for pools of all sizes. With its efficient and environmentally friendly operation, the Z300 Series offers a cost-effective way to enjoy a warm and inviting pool.

  • Efficient and economical: The Z300 Series heat pumps use advanced technology to efficiently transfer heat from the air to the pool water, resulting in low operating costs.

  • Environmentally friendly: The Z300 Series heat pumps use R410A refrigerant, which has a low global warming potential, making it an environmentally friendly choice.

Ask a question and I''ll find the answer in the document