Altronix Maximal Fit Series Installation guide

Type
Installation guide
Expandable Power Systems
Installation Guide
Models Include:
MaxFit3FE
- 12VDC/24VDC @ 6A.
MaxFit5FE
- 12VDC @ 10A.
MaxFit7FE
- 24VDC @ 10A.
Rev. MFEPS080119
More than just power.
TM
Installing Company: ________________ Service Rep. Name: ______________________________________
Address: ___________________________________________________ Phone #: _____________________
- 2 - MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems
MaxFitFE Series Overview:
Altronix MaxFit Expandable Power Systems provide system designers and installers with optimum power
choices and the highest levels of versatility. They provide 12VDC or 24VDC via single output power supply/
charger. Includes AC fail, low battery, and battery presence monitoring. Enclosure accommodates up to four (4)
12VDC/12AH batteries. All interconnecting equipment must be UL Listed.
MaxFitFE Series Configuration Chart:
Altronix
Model
Number
120VAC
60Hz
Input
Current
Input
Fuse
Rating
Battery
Fuse
Rating
Nominal DC Output Voltage Options
Maximum
Supply
Current
for Main
and Aux.
Outputs
Ripple
Voltage
(mV)
Under
low
battery
condition
[DC] [AUX]
12VDC
Output
Range (V)
24VDC
Output
Range (V)
12VDC
Output
Range (V)
24VDC
Output
Range (V)
MaxFit3FE
3.5A 5A/250V 10A/32V 10.0-13.2 20.19-26.4 10.03-13.2 20.19-26.4 6A 910
MaxFit5FE
3.5A 5A/250V 15A/32V 10.03-13.2
10.03-13.2
10A 760
MaxFit7FE
4.5A 6.3A/250V 15A/32V
20.17-26.4
20.17-26.4 10A 700
DC outputs for these power supplies are not power-limited. If a power-limited output is required in the end-product ap-
plication, DC output from the power supply must be connected to a separately Listed control unit or accessory board that
provides power-limited outputs. The product(s) providing the power-limited output(s) must be listed as appropriate
for the particular end-productapplication and wired in accordance with the products installation instructions. Class 1
wiring methods, separation of circuits, and proper fire-rated enclosures all must be considered when connecting the
DC output of the power supply to the end-product devices. The auxiliary outputs of these units are power-limited.
MaxFitFE Series Features:
Input: 120VAC, 60Hz.
For output voltage and supply current refer to MaxFitFE series Configuration Chart, pg. 2.
Auxiliary Power-Limited output rated @ 1A (unswitched).
Overvoltage protection.
Built-in charger for sealed lead acid or gel type batteries.
Maximum charge current 1.54A.
Automatic switch over to stand-by battery when AC fails. Transfer to stand-by battery power is instantaneous
with no interruption.
Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open
(NO) or normally closed (NC) trigger.
AC fail supervision (form “C” contacts).
Battery fail & presence supervision (form “C” contacts).
Low power shutdown. Shuts down DC output terminals if battery voltage drops below 71-73% for 12V units
and 70-75% for 24V units (depending on the power supply). Prevents deep battery discharge.
For fuse ratings refer to MaxFitFE series Configuration Chart, pg. 2.
Green AC Power LED indicates 120VAC present.
AC input and DC output LED indicators.
Short circuit and overload protection.
Enclosure accommodates up to four (4) 12VDC/12AH batteries.
Enclosure dimensions (H x W x D): 20.5” x 16.5” x 6.25” (520.7mm x 419.1mm x 158.8mm).
MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems - 3 -
MaxFitFE Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI,
The Canadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product
must be located indoors within the protected premises.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top three keyholes in
the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the three upper screws; level and secure. Mark the position of the
lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the
enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to
tighten all screws (Enclosure Dimensions, pg. 8).
2. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Fig. 1a, pg. 4). Use 14 AWG
or larger for all power connections. Secure green wire lead to earth ground.
For Fire Alarm applications the outputs are “Special Applications” only.
Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires).
Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts.
Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Select desired DC output voltage by setting SW1 to the appropriate position, (MaxFit3FE) (Fig. 2a, pg. 4).
MaxFit5FE power supply is factory set at 12VDC.
MaxFit7FE power supply is factory set at 24VDC (Stand-by Battery Specifications, pg. 5).
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect devices or Altronix sub-assembly modules to be powered to the terminals marked [– DC +]
(Fig. 1h, pg. 4). For auxiliary device connection, this output will not be affected by
Low Power Disconnect or Fire Alarm Interface. Connect device to the terminals
marked [+ AUX –] (Fig. 1f, pg. 4). Refer to page 2 for non power-limited applications.
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result
in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect battery to the terminals marked [– BAT + ] (Fig. 1g, pg. 4). Use two (2) 12VDC batteries connected
in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120
(12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of
an appropriate rating.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 4) supervisory
relay outputs.
8. To delay AC reporting for 2 hrs., set DIP switch [AC Delay] to OFF position (Fig. 1c, pg. 4).
To delay AC reporting for 1 min., set DIP switch [AC Delay] to ON position (Fig. 1c, pg. 4).
Note: Must be set to ON position for Burglar Alarm Applications.
9. To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position. (Fig. 1c, pg. 4).
To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position. (Fig. 1c, pg. 4).
10. Trigger terminals are end of a line resistor supervised (10k Ohms). Opening or shorting trigger terminals
will cause [DC] output to shutdown (Fig. 1d, pg. 4).
11. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching
[Trigger EOL Shutdown] (Fig. 1d, pg. 4).
12. For Access Control Applications: mount UL Listed tamper switch (Altronix Model TS112 or equivalent) at
the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the
right side (Fig. 3a, pg. 6). Connect tamper switch wiring to the Access Control Panel input or the appropriate
UL Listed reporting device.
13. Please ensure that the cover is secured with the provided key lock.
Wiring:
Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper
voltage level (MaxFitFE Configuration Chart, pg. 2).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified
voltage at the battery terminals and at the board terminals marked [BAT +] to
ensure that there is no break in the battery connection wires.
Note: Maximum charge current 1.54A.
Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.
- 4 - MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems
Fig. 1 - eFlow Board configuration
Power Supply Board Output Voltage Settings:
LED Diagnostics:
Red (DC) Green (AC/AC1) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery is supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or no stand-by battery. No DC output.
Red (Bat) Battery Status
ON Normal operating condition.
OFF Battery fail/low battery.
LG N
NC C NO NC C NO
BAT FAIL
AC FAIL
--- DC +
AC
AC1
DC
--- BAT +
+ AUX
TRIGGER EOL
SUPERVISED
5A 250V
5A 250V
10A 32V
10A
NO GND
RESET
enable
disable
1 min.
2 hr.
AC DELAY SHUTDOWN
O
N
1a 1b
1g
1h
1e 1f1d1c
1i
OFF --- 24V
ON --- 12V
ON
--- DC +
OFF - 24V
ON - 12V
ON
ON
OFF - 24V
ON - 12V
Fig. 2
Fig. 2a
MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems - 5 -
Terminal Identification:
Terminal
Legend
Function/Description
L, N
Connect 120VAC 60Hz to these terminals: L to hot, N to neutral.
Do not use terminal marked [G] (Fig. 1a, pg. 4).
+ DC Refer to MaxFitFE Series Configuration Chart, pg. 2 (Fig. 1h, pg. 4).
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 4).
NO, GND
RESET
FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 4).
+ AUX – Auxiliary Power-Limited output rated @ 1A (unswitched) (Fig. 1f, pg. 4).
AC FAIL
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited) (Fig. 1b, pg. 4).
BAT FAIL
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized
when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 4).
+ BAT
Stand-by battery connections.
Maximum charge current 1.54A (non power-limited) (Fig. 1g, pg. 4).
Stand-by Battery Specifications:
Battery MaxFit3FE MaxFit5FE and MaxFit7FE
7AH 10 Mins./6A 5 Mins./10A
12AH 30 Mins./6A* 30 Mins./10A*
40AH Over 4 Hours/6A* Over 2 Hours/10A*
65AH Over 4 Hours/6A* Over 4 Hours/10A*
*Only these configurations can be utilized in ULC-S319 installations.
MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems - 6 -
NEC Power-Limited Wiring Requirements:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited
circuit wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all
power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through differ-
ent conduits. One such example of this is shown below. Your specific application may require different conduit
knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is
optional. All field wiring connections must be made employing suitable gauge
CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed
battery enclosure must be mounted adjacent to the power supply via Class 1
wiring methods. For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the
CM or FPL jacketed wire (Fig. 3b).
Fig. 3
A ACM8(CB), ACMS8(CB)
B
ACM4(CB),
LINQ8PD(CB),
PD4UL(CB), PD8UL(CB),
MOM5, PDS8(CB), VR6
C PD16W(CB)
D
NetWaySP3B, NetWay4EB,
NetWaySP4B, NetWaySP8B
Fig. 3a
Tamper Switch
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors
Tamper Switch
DC Output
(non power-limited)
Optional
Rechargeable
Stand-by Battery
for UL294
Applications
Note:
12V batteries
are required for
ULC-S319
installations.
Battery
(non power-
limited)
Input 120VAC, 60Hz
(non power-limited)
Supervisory Connections, Aux. Outputs to Devices and
Fire Alarm Interface (power-limited)
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC
stand-by battery. Connect red battery lead to the terminal marked [+ BAT] and
to the [positive (+)] terminal of the battery. Connect black battery lead to terminal
marked [BAT –] and to the [negative (–)] terminal of the battery.
Keep power-limited wiring separate from non power-limited.
Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that
can fit in this enclosure.
A UL listed external battery enclosure must be
used if using the 40AH or 65AH batteries.
NC C NO NC
C NO
AC FAIL BAT FAIL
TRIGGER
AC DCAC1
EOL NO GND
SUPERVISED RESET
+AUX-
- BAT +- DC +
L G N
A
B
C
D
A
B
A
B
C
C
Power
Supply/
Charger
Fig. 3b
- 7 - MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems
Notes:
- 8 - MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IIMaxFit3FE/5FE/7FE Series H21S
MEMBER
MaxFit Enclosure Dimensions (approximate):
20.5” x 16.5” x 6.25” (520.7mm x 419.1mm x 158.8mm)
16.50”
0.569”
1.00”
6.25
1.50”
1.25”
1.25” 1.25”
1.25”1.25”
1.25”
1.25”
1.25” 0.75” 1.25”
1.25”
1.50”
1.25”
20.50”
8.75”
1.50”
7.00” 7.00”
8.75”
8.75”
1.50”
7.00” 7.00”
8.75”
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8