Legrand LightSaver® LCD-203 Dimming Controller Installation guide

Type
Installation guide

Legrand LightSaver® LCD-203 Dimming Controller can provide automatic dimming for fluorescent and HID lighting, based on daylight contribution. It works with standard 0-10 volt dimming ballasts. It provides three control channels and can control a maximum of fifty ballasts per channel. You can also connect other devices to the LCD-203 to enhance its control capability, such as an occupancy sensor, relay panel, BAS or time clock. An optional wall switch, model LS-4C or LS-5C, allows manual dimming and ON/OFF control.

Legrand LightSaver® LCD-203 Dimming Controller can provide automatic dimming for fluorescent and HID lighting, based on daylight contribution. It works with standard 0-10 volt dimming ballasts. It provides three control channels and can control a maximum of fifty ballasts per channel. You can also connect other devices to the LCD-203 to enhance its control capability, such as an occupancy sensor, relay panel, BAS or time clock. An optional wall switch, model LS-4C or LS-5C, allows manual dimming and ON/OFF control.

Copyright© 2007 Watt Stopper/Legrand
®
04251r2 07/2007
LightSaver
®
LCD-203 Daylighting
Controller
DESCRIPTION
The LCD-203 controller provides automatic dimming for
fluorescent and HID lighting, based on daylight contribution.
The LCD-203 controller works with standard 0-10 volt dimming
ballasts. It provides three control channels. The LCD-203
provides dimming control for a maximum of fifty ballasts per
channel.
The programmable adjustments for your application can be
easily selected and customized directly from the face of the
LCD-203. You can also observe specific system operation
directly from the controller display.
The BT-203 Power Pack powers the LCD-203 and has three
relays for ON/OFF switching, one for each channel.
The LCD-203 connects to one LS-290C photocell to detect the
incoming daylight level. Light level at the LS-290C displays on
the face of the LCD-203.
An optional wall switch, model LS-4C or LS-5C, allows manual
dimming and ON/OFF control.
Lighting Channels
Lighting channels are groups of fixtures that receive about the
same daylight contribution. Typically, for a multi-channel
application, fixtures nearest daylight sources are grouped
together in the same channel. Rows of fixtures farther back
should be grouped together. The fixtures farthest from the
daylight are grouped into the last channel. When distributed in
this manner the individual channel dimming response
adjustments allow the light level to be balanced across an area.
Control Input Options
In addition to the photocell and the wall switch, you can connect
other devices to the LCD-203 to enhance its control capability.
For example, to automatically dim and/or shut off the lights
during the unoccupied periods, an occupancy sensor, relay
panel, BAS or time clock can be wired to the LCD-203
controller. For manual control during occupied periods, you can
connect a momentary manual switch. For energy conservation
or emergency shut-down, you can connect it to a load shed
system. See the Low Voltage Wiring section for details.
1.800.879.8585
Navigation and
selection buttons
DIN Rail
Display
A
LightSaver
®
LCD-203
45 78123 129 10 116
A
45 78123 129 10 116
B
B
412 653
D
D
RJ12: quick connect to BT-203
LightSaver
®
BT-203
1.800.879.8585
Not Used
D terminals:
0-10VDC dimming ballast control
BT-203 Power Pack LCD-203 Controller
Line Voltage
Not Used
Figure 1: BT-203 Power Pack and LCD-203 Controller on DIN Rail
Installation Instructions
CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Lighting Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Control Input Options . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
PHOTOCELL PLACEMENT . . . . . . . . . . . . . . . . . . . . .2
LCD-203 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . .2
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Automatic Dimming . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
On/Off Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Manual Dimming Control . . . . . . . . . . . . . . . . . . . . . . . . .2
Wall Switch (LS-4C or LS5C) . . . . . . . . . . . . . . . . . .2
Manual Dimming Operation . . . . . . . . . . . . . . . . . . .3
When starting from automat . . . . . . . . . . . . . . . . . . .3
LOW VOLTAGE WIRING . . . . . . . . . . . . . . . . . . . . . . .3
Photocell, Terminal A10, A11, A12, . . . . . . . . . . . . . . . . . .3
Ballast Dimming Control, Terminals D1-D6 . . . . . . . . . . .3
Occupancy Sensor, Terminal A8, A11, A12 . . . . . . . . . . .4
Door Switch, Terminal B9 . . . . . . . . . . . . . . . . . . . . . . . . .4
Wall Switch, Terminal B2 to B8 . . . . . . . . . . . . . . . . . . . .4
Load Shed, Terminal B12 . . . . . . . . . . . . . . . . . . . . . . . . .4
Time Switch, Terminal B11 . . . . . . . . . . . . . . . . . . . . . . . .4
Class Room Whiteboard, Terminal B10 . . . . . . . . . . . . . .4
USER MENU AND DISPLAY . . . . . . . . . . . . . . . . . . . .5
Programmable Controller Adjustments . . . . . . . . . . . . . . .5
RUN mode -vs- Programming/Diagnostic mode . . .5
How to use the Programming Guide . . . . . . . . . . . .5
Navigation Quick Guide . . . . . . . . . . . . . . . . . . . . . . . . . .5
GENERAL SET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Daylight Factor Submenu . . . . . . . . . . . . . . . . . . . . .7
Adjust Settings Submenu . . . . . . . . . . . . . . . . . . . . .8
Adjust Ch# Submenu . . . . . . . . . . . . . . . . . . . . . . . .8
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
WARRANTY INFORMATION . . . . . . . . . . . . . . . . . . .10
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . .10
ORDERING INFORMATION . . . . . . . . . . . . . . . . . . . .10
PHOTOCELL PLACEMENT
In applications where windows
are the primary source of
daylight, the LS-290C photocell
typically mounts on the ceiling
between the window and the
first row of fixtures. For skylight
applications, the photocell
mounts in the lightwell. The
photocell is aimed toward the
daylight. Maximum wire
distance from the controller to
the photocell is 250 feet.
You need a light meter to
measure light levels at task
areas.
See the LS-290C Photocell
installation instructions for
information about placement,
mounting and testing.
LCD-203 INSTALLATION
1. The LCD-203 controller mounts onto a DIN rail inside of an
electrical enclosure rated for the application. Typically, a NEMA 1
rated enclosure such as the Watt Stopper LS-E8 is used. One
LCD-203 and one BT-203 can be mounted in an LS-E8.
2. All wiring connected to the LCD-203 is low voltage. Low voltage
wiring must be separated from line voltage wiring. Low voltage
wiring must enter the enclosure through knockouts separate from
high voltage wiring.
Switch and sensor wires terminate at the terminal strips on the
top rows (labeled A and B).
Ballast control wires terminate on the bottom row (labeled D).
Wire all devices to the LCD-203 before connecting it to the
power pack or making any adjustments or program changes.
See the Low Voltage Wiring section for information about wiring
each device.
Use the quick connect cable supplied with the LCD-203 to
connect it to the BT-203 Power Pack.
Figure 3: Wiring terminal locations
Adjustments
The display and buttons on the face of the LCD-203 allow you to
make various system adjustments. The LCD-203 comes with 3 pre-
programmed applications. Each application has factory default
settings. Depending on the circumstances of your installation,
adjustments may not be necessary. Program adjustments allow you to
set the speeds at which lights are raised or lowered, the maximum
and minimum lighting output levels, and other options. See the
Controller Adjustments and Display section for details.
1.800.879.8585
"B" Terminals
"A" Terminals
A
LightSaver
®
LCD-203
45 78123 12910116
A
45 78123 12910116
B
B
412 653
D
D
RJ12: quick connect to BT-203
LightSaver
®
BT-203
1.800.879.8585
Not Used
"D" terminals
Line Voltage
Terminals 1-8
Not Used
LCD-203: Low Voltage
D
D
BT-203: High Voltage
43
65
87
21
OPERATION
Automatic Dimming
When in Automatic mode, the LCD-203 system adjusts the lights in
each channel based on the amount of daylight measured by the
photocell. The LCD-203 automatically calculates the ratio of dimming
to daylight contribution to meet the programmed light level
requirements.
The LCD-203 provides a 0-10 volt control signal to the ballasts in
each channel. A 10 volt signal commands the lights to their full output
and a 0 volt signal commands the lights to their minimum output. The
outputs for each channel automatically raise or lower based on the
light level and daylight factors programmed, as well as each channel’s
minimum and maximum control output levels, and fade and ramp rate.
In a typical application, the channel closest to the window or skylight
gets the most daylight. The lights in this channel are dimmed most
aggressively. Channels farther from the window or skylight get less
light from daylight and more electric light is needed to maintain the
required light levels.
On/Off Switching
The BT-203 provides ON/OFF switching based on the combined
requirements of daylighting, occupancy, time clock and manual control
inputs to the LCD-203. The three normally open relays built into the
BT-203 Power Pack are closed whenever the LCD-203 determines
that the electric lights are required.
Full Daylight: The contacts open if the LCD-203 determines that
there is sufficient daylight in a channel and no supplemental electric
light is needed.
First, the channel must dim to the programmed minimum output. Then
the channel’s programmable
Cut off
timer begins. If the channel
remains dimmed to minimum for the duration of the timer, the contact
opens. The contact closes again when the daylight has decreased
sufficiently to require additional light in the channel.
Manual Off: When the wall switch is used, the contacts open to
switch the lights OFF. With the LS-4C, press the I/O button or the
Auto button to close the contacts. With the LS-5C, press the On/Off
button to change from automatic to manual mode and open the
contacts.
Time Clock Interlock: When the LCD-203 receives a contact closure
at terminal B11, it signals an unoccupied period. The unoccupied
signal immediately opens the contacts for all three channel relays.
This turns lights OFF and holds them OFF until the Time Clock
Interlock contact opens.
End of Occupancy: When the occupancy sensors internal delay
expires and it removes the occupancy signal from the LCD’s terminal
A8, a one-minute delay timer starts. If there is no occupancy signal
when the delay expires, the dimming output signal from the LCD-203
drops to the minimum programmed output for each channel. The
dimming output remains at this level for the duration of the cutoff timer
if there is no occupancy signal, then the lights turn off.
NOTE: The LCD’s low voltage control signal to the ballast remains on
at the lowest programmed level for each channel until the BT-203 line
voltage relay for every channel is OFF, then it drops to 0 volts.
Manual Dimming Control
The LS-4C and LS-5C are optional wall switches that provide manual
override of all channels in unison. Once manually set, the lights
remain at that level until the LCD-203 resumes Automatic operation.
To resume Automatic operation you simply press and release the Auto
button on the wall switch. For another way to return the LCD-203 to
Automatic mode, see LOW VOLTAGE WIRING, Occupancy Sensor,
on page 4.
Wall Switch (LS-4C or LS5C)
The LED next to the Auto button lights when the LCD-203 is dimming
in automatic mode. The LED next to the I/O or On/Off button lights
when the LCD-203 is in manual mode. Both LEDs are off when in
programming or diagnostic mode or when the time clock signal is
present. See Figure 7 and 7a or the instructions that came with the
switch for wiring instructions.
Peak
Sensitivity
LS-290C
Light Fixture
Window
45°
Figure 2: Photocell placement for a
window application
page 2
page 3
Call 800.879.8585 or 972.578.1699 for Technical Support
LOW VOLTAGE WIRING
Photocell, Terminal A10, A11, A12,
The LS-290C photocell provides daylight contribution measurements
to the LCD-203. There are two versions of the photocell. The only
difference between versions is the way they connect to the controller.
Connect the photocell to the LCD-203 as shown in Figure 5 or 5a, as
appropriate. If you are NOT installing an occupancy sensor, put a wire
jumper between terminals A8 and A11.
For photocell placement and installation, see page 2 of this manual
and the Installation Instructions provided with the photocell. For
programming and adjustment information, see the User Menu and
Display,
ADJUSTMENT
,
Daylight Factor
section of this manual.
Ballast Dimming Control, Terminals D1-D6
The LCD-203 provides 0-10VDC output to the ballast dimming control
inputs. As shown in Figure 5, terminals D1-D2 control Channel 1,
D3-D4 control Channel 2, D5-D6 control Channel 3. Each channel
can control up to 50 dimming ballasts.
Line voltage and ON/OFF relay control to the lighting fixture is
provided by connecting the fixture to the BT-203 Power Pack. See
On/Off Switching on page 2 of this manual and the BT-203 Installation
Instructions for more information.
LightSaver
®
LCD-203
78 1291011
A
A
45 78123 12910116
B
B
Original
LS-290C
Photocell
123
to A12
to A11
to A10
Jumper from A8 to A11
if no occupancy sensor
Figure 5: LS290C v2 Photocell and ballast dimming control wiring
Manual Dimming Operation
When starting from automatic mode (Auto LED is on), there are
two ways to initiate manual dimming:
1. Press and release the I/O (On/Off) button on the switch. The
Manual (I/O or On/Off) LED goes on. If the lights were previously:
ON but dimmed, all channels go to maximum programmed
output.
OFF (BT-203 relay open), all relays close and channels go to the
maximum programmed output.
-or-
2. Press and hold the (Lower) button to dim or (Raise) to raise
the lights.
The Manual (I/O or On/Off) LED goes on.
If lights were previously OFF (BT-203 relay open), all relays close.
All channels ramp up or fade down equally from their present level
until you release the button or they meet their programmed
maximum or minimum output levels.
When starting from manual mode (I/O or On/Off) LED is on):
If lights are ON:
Pressing the (Lower) button fades all channels down equally
from their present level until you release the button or they meet
their programmed minimum output levels.
Pressing the (Raise) button ramps up all channels equally
from their present level until you release the button or they meet
their programmed maximum output levels.
Pressing the I/O (On/Off) button turns all the lights OFF.
(BT-203 relays open and the dimming output goes to 0VDC.)
If lights are OFF:
Pressing the (Lower) button closes the BT-203 relays and the
dimming output goes to the minimum programmed output.
Pressing the (Raise) button closes the BT-203 relays and the
lights ramp up equally from their present level until you release
the button or they meet their programmed maximum output
levels.
Pressing the I/O (On/Off) button turns the lights ON
(BT-203 relays close and the dimming output goes to the
maximum programmed output.)
Auto
l/O
LED on:
Automatic
LED on:
Manual
Raise
lights
Lower
lights
Set to
Automatic
Set to
Manual &
ON/OFF
toggle
Figure 4: Wall Switch controls
LightSaver
®
LCD-203
1.800.879.8585
78 1291011
A
A
45 78123 12910116
B
B
412 653
D
D
LS-290C v2
Photocell
Jumper from A8 to A11
if no occupancy sensor
+
-
0-10V
Violet
Gray
More Chan 1
Ballasts
(up to 50)
0-10V
Violet
Gray
+
-
0-10V
Violet
Gray
More Chan 2
Ballasts
(up to 50)
0-10V
Violet
Gray
+
-
0-10V
Violet
Gray
More Chan 3
Ballasts
(up to 50)
0-10V
Violet
Gray
123
to A11
to A12
to A10
Figure 5a: Original LS290C Photocell wiring (no version mark on unit)
see Figure 5 for ballast wiring
On / Off
Auto
Raise
Lower
LS-4C
LS-5C
Class Room Whiteboard, Terminal B10
This terminal is only
functional as an ON/OFF
switching device when the
Class Rm application is
programmed and Channel
3 is activated (see
programming for
GENERAL
SET->Channels 3Ch
).
Time Switch, Terminal B11
Open contact: Occupied
period. Lights respond to
sensor and switch inputs.
Closed contact:
Unoccupied period. Turns
lights OFF and holds lights
OFF. The controller ignores
all other control signals
(such as LS-4C, manual
switches, photocell,
occupancy sensor, load
shed).
LightSaver
®
LCD-203
78 1291011
A
A
45 78123 12910116
B
B
Time Switch or Relay Panel or BAS
Common
to B2
to B11
Jumper from A8 to A11
if no occupancy sensor
LightSaver
®
LCD-203
78 1291011
A
A
45 78123 12910116
B
B
Common to B2
Momentary Manual
Whiteboard Switch
(Class RM only)
to B10
Jumper from A8 to A11
if no occupancy sensor
Load Shed, Terminal B12
Open contact: Normal operation.
Closed contact: If
automatic dimming is active
and lights are on with a
control output greater than
the level programmed in
Adjustment> Adjust Ch#
> Loadshed #
, the lights
will dim to the programmed
load shed level and hold
there. If daylight levels
increase, the control output
will be further reduced.
LightSaver
®
LCD-203
78 1291011
A
A
45 78123 12910116
B
B
Common
to A12
Load Shed System
to B12
Jumper from A8 to A11
if no occupancy sensor
Wall Switch, Terminal B2 to B8
LightSaver
®
LCD-203
78 1291011
A
A
45 78123 12910116
B
B
LS-4C Switch
Auto
I/O
Red to B8
Brown to B7
Blue to B5
Green to B2
Black to B3
White to B4
Orange to B6
Figure 7: LS-4C wiring
Figure 9: Time switch wiring
Figure 8: Class room whiteboard
switch wiring
Figure 10: Load shed wiring
Occupancy Sensor, Terminal A8, A11, A12
An occupancy sensor can be connected to the controller
so that when no occupancy is detected, lights dim then
turn off. See Figure 6 for wiring.
You can program the controller to either turn on the lights
automatically at the beginning of occupancy, or so that the
lights must be manually turned on with the wall switch.
When the controller is programmed for an Auto On
application, if the occupancy sensor detects occupancy,
the LCD-203 controller goes into Automatic mode to turn
on lights and dim them as needed.
When it is programmed for a Manual On application, once
the lights are turned on by a switch, the occupancy sensor
signal holds the lights on.
If the LCD-203 is in Manual mode when the occupancy
signal is removed:
The lights stay on at their current level for one minute
then they shut OFF.
When the occupancy signal returns, the LCD-203
controller returns in Automatic dimming mode.
If the LCD-203 is in Automatic dimming mode when the
occupancy signal is removed:
The lights stay on at their current level for one minute
then they begin to dim according to the
Fade Rate
for
each channel. When the output reaches minimum, the
Cut off
delay timer begins for each channel. As each
channel’s timer expires, the lights go OFF in that
channel.
Door Switch, Terminal B9
This terminal is functional as an ON/OFF switching device
when the Manual On or Class Rm application is
programmed.
When the Momentary Manual Switch operates it toggles
the state of the BT-203 relays.
If automatic dimming is active and lights are on, control
output drops to 0.0VDC. If automatic dimming is active and
lights were shut off with the switch, activating it again
resumes automatic dimming level.
Do not use this input if the controller is programmed for
the Auto On application.
LightSaver
®
LCD-203
78 1291011
A
A
45 78123 12910116
B
B
Control Output
to A8
+
24VDC
to A11
Common
to A12
24VDC Occupancy
Sensor
Momentary
Manual
Door
Switch
Common
to B2
to B9
Figure 6: Occupancy sensor and door switch wiring
page 4
For operation see
the Manual
Dimming Control
chapter on pages
2-3 and the
Instructions
provided with the
wall switch.
45678123
LCD-203
Wire colors shown are
Belden 8467 or equivalent
7-conductor 18 AWG cable
P2 (Red) to B8
S2 (White) to B4
S1 (Black) to B3
COM (Green) to B2
S3 (Blue) to B5
S4 (Orange) to B6
P1 (Brown) to B7
B
A
45678123
LS-5C
Figure 7a: LS-5C wiring
USER MENU AND DISPLAY
The user menu display and navigation buttons on the face of the
LCD-203 give you access to two menus of programmable controller
adjustments and two menus of real-time system operation data.
Programmable Controller Adjustments
There are two programming sections.
GENERAL SET
, is used to
determine the overall parameters of the system.
ADJUSTMENTS
, lets
you customize parameters for each lighting control channel.
RUN mode -vs- Programming/Diagnostic mode
When the controller is powered up and no buttons have been pushed
recently, the screen shows
The Watt Stopper
along with the current
photocell light level reading. The photocell readings dynamically
update. For an example, see the illustration below.
Pressing any button on the LCD-203 puts the controller into the
programming/diagnostic mode. When in this mode:
Switch inputs are ignored
LEDs on the LS-4C or LS-5C wall switch are off
The LCD-203 continues to monitor light levels at the photocell
The LCD-203 continues to dim lights
To exit the programming/diagnostic mode and return to the RUN
mode, press the key repeatedly until
The Watt Stopper
shows in
the display. The programming/diagnostics mode will also automatically
time out and return the controller to RUN operation after 5 minutes
without a button press.
GENERAL SET
RUN SEE
NEXT
ADJUSTMENT
BACK SEE
NEXT
STATUS
BACK SEE
NEXT
TERMINAL DATA
BACK SEE
Type Auto On
EXIT NEXT
ADJ
Daylight Factor
EXIT NEXT
ADJ
Ch1 ON
EXIT NEXT
PIR unocc
EXIT NEXT
Navigation Quick Guide
ADJ
Adjust the programming for this item or submenu.
BACK
Go back to the previous main menu title.
ESC
Abandon the current selection, do not save
change, return to last saved selection.
EXIT
Leave this screen and go back one menu or
submenu level.
NEXT
Advance to the next menu or program item without
leaving the current program level.
RUN
Return the controller to normal operation.
SAVE
Save changes to this selection and show the new
selection on the screen.The controller powers up
after saving
GENERAL SET->Type
and other items.
SEE
View the program items within a menu.
LightSaver
®
LCD-203
1.800.879.8585
The Watt Stopper
0085fc
RUN Mode: The numbers in the display indicate the current light level
(in footcandles) at the LS-290C Photocell.
Press any button to enter the programming/diagnostic mode.
To other
GENERAL
Items
To other
ADJUSTMENT
Items
To other
STATUS
Items
To other
TERMINAL DATA
Items
How to use the Programming Guide
In this manual,
This Kind of Typeface
indicates the text that
appears in the display.
When you see an arrow (
>
) between words, it means to advance the
display to another level to see the next program item listed. Typically
you will press the or button to advance to that level, but you
may need to press or to get there, depending on where you are
inside the program.
The illustration below shows the top level of the programming/
diagnostics menu and the first program item within each section. The
details of each program item, selection and diagnostic tool will be
described in the sections that follow.
page 5
}
PROGRAMMING
}
DIAGNOSTIC
GENERAL SET
BACK SEE
NEXT
Type Auto on
EXIT NEXT
ADJ
Channels 1Ch
EXIT NEXT
ADJ
Run Test Mode?
EXIT YES
Auto on
The light switches on when the occupancy sensor detects occupancy and there is
a need for electric lights. While the sensor detects occupancy, the LCD-203
automatically controls the electric lights using
Daylight Factor
adjustment
programming. As daylight increases, the light dims to maintain the minimum light
level setpoint for each channel. At the end of occupancy, the lights dim then turn
off.
Manual on
The light must be manually turned on using a momentary manual switch or the
I/O (On/Off) button on the LS-4C or LS-5C. When the switch input is received, the
LCD-203 goes into automatic mode and the lights come on if needed. When the
LS-4C or LS-5C is used, you must press the Auto button to put the LCD-203 into
automatic mode. As long as there is an occupancy signal (from an occupancy
sensor, time clock or BAS) or until the switch is pressed again to turn the lights
off, the LCD-203 automatically controls the electric lights using daylight factor
programming.
Class RM
(Class Room) Works like the Manual On application, but with channels 1 and 2
available for dimming control and channel 3 dedicated to ON/OFF control of a
whiteboard light with a dedicated switch.
During the test mode, the controller only responds to input from the photocell. All other switch
and control inputs are ignored. Lights will dim according to Daylight Factor programming. Test
Mode bypasses the time delays programmed in each channel’s
Cut off
timer for switching off
the electric lights when daylight is contributing 100% of the programmed setpoint.
When you exit test mode, the controller resets and may turn off the lights momentarily.
Selections
Auto on
Manual on
Class RM
1Ch
2Ch
3Ch
Powerup System
Please wait
Sets the number of active channels. The output and channel information displayed for
operational, diagnostic and programming purposes is determined by this setting.
NOTE: If
Type
(above) is set to
Class Rm
, you must set this item to 3 channels for whiteboard
switch operation. No programming items or status will display for channel 3.
In Test Mode
EXIT
GENERAL SET
In
GENERAL SET
, you select the type of application
and the number of channels. This menu also
provides access to the LCD’s
Test Mode
.
page 6
The LCD-203 comes with three basic application types already saved in its memory. The
program items are the same for each application type, but the entry selections are different,
depending on how the programmable feature is used in the application.
page 7
ADJUSTMENT
In ADJUSTMENT you set the daylight factors and
select individual operating parameters for each channel.
This menu also provides a way to save application
settings for future use and a way to restore the factory
defaults. There are three submenus within
ADJUSTMENT as shown below.
The program items for each submenu are described in
the sections that follow.
ADJUSTMENT
BACK SEE
NEXT
Daylight Factor
EXIT NEXT
ADJ
Adjust Ch#
EXIT NEXT
ADJ
Adjust Settings
EXIT ADJ
Range 30-3000fc
EXIT NEXT
ADJ
Select the light level range that matches the jumper setting on the LS-290C
Photocell. The default for both the LCD-203 and the LS-290C is 30-3000fc.
If the expected maximum light at the photocell is:..........Set
Range
for:
less than 250fc (darker locations)......................................3-300fc
more than 250fc, less than 2800fc (typical)...................30-3000fc
more than 2800 (inside skylight lightwell)......................60-6000fc
Selections
3-300fc
30-3000fc
60-6000fc
Enter information about the photocell and the light level at the task area for
each channel. See
Daylight Factor
Submenu for a description of each
program item. Entries in this submenu are mandatory.
Set each channel’s reaction to various system inputs. See
Adjust Ch#
Submenu for a description of each program item.
# Each channel enabled in the GENERAL SET menu is programmed in
a separate submenu for that channel. In a
Class Rm
application, channel
3 is dedicated to an ON/OFF switch at the whiteboard, so no
programming adjustments are presented.
Use this item to save your program selections, or to have items return to
the factory defaults.
Daylight Factor Submenu
Theses entries allow the LCD-203 to calculate the ratio
of dimming to the amount of daylight contributing to the
illumination of the channel. This relationship is
determined by light meter measurements at the task
level for each channel and the light received at the
LS-290C Photocell.
Daylight Factor
EXIT NEXT
ADJ
To
Adjust Ch1
Task FC1 20fc
NEXT
ADJ
Select the light level that matches the light meter measurement you took at
the task level for Channel 1. The default is 20fc.
5fc
to
100fc
Task FC2 20fc
NEXT
ADJ
Select the light level that matches the light meter measurement you took at
the task level for Channel 2. The default is 20fc.
5fc
to
100fc
Task FC3 20fc
NEXT
ADJ
Select the light level that matches the light meter measurement you took at
the task level for Channel 3. The default is 20fc.
5fc
to
100fc
If Channel 2
is available
If Channel 3
is available
Photocell 0467fc
EXIT ADJ
When you press ADJ, the display captures the light level currently
measured at the LS-290C photocell. You can manually adjust the setting if
necessary. For example, if you manually recorded the photocell light level at
the time the measurements were taken at the task level, you may want to
enter that level, rather than the level at the present time. (The available
selections vary depending on the photocell
Range
.) The
Photocell
entry
MUST be greater than the
Task FC
entry for each channel, otherwise a
Daylight Factor error message appears in the
STATUS
menu.
3fc
to
6000fc
When you program Daylight Factor, use a light meter to measure
the light level at a representative task area for each dimming channel. Make
note of the photocell light level reading at the time that the task level
readings are taken.
Adjust Ch# Submenu
Each channel has its own submenu. (To select the
number of channels in your system, see
GENERAL SET >
Channels
.)
Setp1 36fc
EXIT NEXT
ADJ
Select the light level setpoint for the Channel indicated. This sets the target
setpoint to maintain when automatically dimming. When set for OFF or ON,
the lights assume and maintain that state when in automatic and an
occupancy signal is present.
Selections
OFF
5fc to 60fc
ON
Vout min1 1.0V
EXIT NEXT
ADJ
Select the minimum dimming control output voltage. When the area is
occupied, the output voltage will not go below this level.
0.0VDC
to
4.0VDC
Vout max1 10.0V
EXIT NEXT
ADJ
Select the maximum dimming control output voltage.When the area is
occupied, the output voltage will not go above this level.
6.0VDC
to
10.0VDC
Ramp up1 05S
EXIT NEXT
ADJ
Set the number of seconds it takes to ramp from the minimum dimming
countrol output level to the maximum output level. The default is 5 seconds
because normally you want to light the room quickly.
5 to 60
seconds
Fade down1 60S
EXIT NEXT
ADJ
Set the number of seconds it takes to fade from the maximum dimming
countrol output level to the minimum output level. The default is 60 seconds
because normally you want the room to darken slowly.
5 to 60
seconds
Adjust Ch1
EXIT NEXT
ADJ
To:
Adjust Ch2
Adjust Ch3
and
Adjust Settings
Cut off1 12M
EXIT NEXT
ADJ
Set the number of minutes after the channel dims to minimum that the
lights will shut off (BT-203 relay opens).
0 to 20
minutes
or infinity
Loadshed1 10.0V
EXIT ADJ
Set the maximum control output level to use during Load Shed events.
Load shed events are triggered by an input from a BAS or other load shed
signalling device connected to LCD-203 terminal B12.
0.0VDC
to
10.0VDC
After you adjust Channel 1, if more channels are available, their submenus
appear in the display after you
EXIT
the first
Adjust Ch
submenu. If no
more channels are available, the display advances directly to the
Adjust
Settings
submenu when you exit the channel.
Copy Settings?
EXIT ADJ
Custom->Backup?
COPY ADJ
ESC
Adjust Settings
EXIT ADJ
Adjust Settings Submenu
These program items allow you to make a backup copy of
the
ADJUSTMENT
programming, restoring from the backup,
and returning to factory defaults.
The LCD-203 displays the current
ADJUSTMENT
settings in
a program called “Custom.”
Backup->Custom?
COPY
ADJ
ESC
Factory->Custom?
COPY
ADJ ESC
Display pauses and
responses are delayed
during copy process
When you select COPY, here is what happens for each function:
Custom->Backup
: Makes a backup copy of the
ADJUSTMENT
menu settings
currently operating in the controller.
Backup->Custom
: Replaces the current controller
ADJUSTMENT
menu
settings with the backup copy.
Factory->Custom
: Restores the factory default settings for all items in the
ADJUSTMENT
menu.
page 8
If you need to test an alternate set of adjustments, you may save time by
making a backup copy of the current settings, changing the desired
settings, then testing. If you want to return to the previous settings, you can
restore the settings from the backup copy.
If you need to return to the
ADJUSTMENT
default settings originally
programmed, you can copy the Factory program into the current “Custom”
program.
}
The
Adjust
program items repeat in submenus for
Channel 2 and Channel 3, if the channels are enabled.
page 9
Diagnostics
There are two menus that provide real-time data about the system’s
current state.
The
STATUS
menu gives information about the ballast channel outputs
at the BT-203 power pack and the LCD-203 terminal D. It also
displays the daylight factor calculated by the LCD-203 for each
channel.
Note: No status is displayed for Channel 3 in the
Class RM
application.
STATUS
BACK SEE
NEXT
Ch1 ON
EXIT NEXT
Ch2 ON
EXIT NEXT
Ch3 ON
EXIT NEXT
Vout1 <1.0V
EXIT NEXT
Vout2 7.0V
EXIT NEXT
Vout3 10.0V
EXIT NEXT
Df1 10.00%
EXIT NEXT
Df2 10.00%
EXIT NEXT
Df3 20.00%
EXIT
Shows the ON/OFF
status of the BT-203
power pack relay
associated with each
channel enabled in the
program.
Shows the control
voltage output level to
each ballast channel.
Shows the Daylight
Factor the LCD-203
calculated for each
channel. Higher numbers
indicate more daylight
contribution. To adjust
values such as photocell
light level and channel
setpoints, see the
ADJUSTMENT
menu.
If an ERROR message
appears, check
programming for
Photocell
and
Task FC
.
Data
Format
ON or OFF
Data
Format
numeric
volts DC
<1.0
to
10.0
Data
Format
0.16% to
98%
TERMINAL DATA
BACK SEE
PIR unocc
EXIT NEXT
Photocell 0427fc
EXIT NEXT
Auto#3 lo
EXIT NEXT
Manual#4 lo
EXIT NEXT
Dim up#5 lo
EXIT NEXT
Dim down#6 lo
EXIT NEXT
Door#9 lo
EXIT NEXT
Whiteboard#10 lo
EXIT NEXT
Time#11 lo
EXIT NEXT
Occupancy sensor input
indicates “occupied” or
“unoccupied”.
Data
Format
occ or
unocc
Auto LED on
EXIT NEXT
Manual LED on
EXIT
numeric
footcandles
lo to hi
lo to hi
lo to hi
lo to hi
lo to hi
lo to hi
lo to hi
on
on
Current light level at the
photocell.
Wall switch Auto button
input at terminal B3.
Wall switch I/O or On/Off
button input at terminal B4.
Wall switch or Raise
button input at terminal B5.
Wall switch Lower button
input at terminal B6.
Momentary switch input at
terminal B9. (Not available
in
Auto On
application.)
Switch input at terminal
B10. (Only available in
Class RM
application.)
Clock, relay or panel input
at terminal B11.
Tests the Auto LED on the
wall switch. Viewing this
screen turns LED on.
Tests the Maunal LED on
the wall switch. Viewing this
screen turns LED on.
Loadshed#12 lo
EXIT NEXT
lo to hi
Load Shed signal from BAS
or other load shed control at
terminal B12.
The
TERMINAL DATA
menu gives information about switch and sensor
inputs at terminal A and B. This menu is very helpful in verifying wiring
connections. When you activate the device connected to the input, the
change of state is held in the display until you acknowledge it by
advancing through the menu.
SPECIFICATIONS
UL and cUL Listed
Class 2
Input
Supply voltage:
Provided by BT-203 Power Pack............................................24VDC
Operating characteristics
Control output voltage to ballasts............................................0–10VDC
Programmable features:
Minimum output setting......................................................... 0-4VDC
Maximum output setting.......................................................6-10VDC
Fade and Ramp Rate...................................................5–60 seconds
Cut off delay...................................................0-20 minutes, or infinity
Maximum Sink ...........................................................50mA per channel
Maximum Source.........................................................3mA per channel
Maximum Ballasts...........................................................50 per channel
ORDERING INFORMATION
Catalog # Description
BT-203 3-Relay Power Pack, input: 120–277VAC 50/60Hz
LCD-203 Indoor daylighting controller, 3-channel, 24VDC
LS-290C Photocell, 3-6000 footcandle range
LS-4C Wall Switch
LS-5C Wall Switch
LS-E8 8 inch square NEMA type 1 enclosure with cover,
includes 1 DIN rail
LS-E12 12 inch square NEMA type 1 enclosure with cover,
includes 2 DIN rails
2800 De La Cruz Boulevard, Santa Clara, CA 95050 • Technical Support: 800.879.8585
www.wattstopper.com
Copyright© 2007 Watt Stopper/Legrand
®
04251r2 07/2007
TROUBLESHOOTING
The lights do not dim automatically when daylight levels are
high enough for dimming to occur.
Verify that the LCD-203 system is operating in Automatic mode
(refer to the “Operation” section).
Check photocell light level reading on the controller display.
Verify that the photocell is positioned properly (refer to the
“Installation” section, and the separate photocell instructions).
The lights are fully dimmed or off when you expect them to be
on.
Verify that the LCD-203 is powered. The display on the Controller
Module will have text when the unit is powered.
Verify that the occupancy signal is present (24VDC at terminal 8).
Verify that the time clock signal is in occupied mode. (There must
not be closure between terminals B2 and B11.)
Not enough light in a channel.
Check the control voltage output to the channel. It is programmed
in
ADJUSTMENT > Adjust Ch# > Vout max#
. Set the output to a
higher level.
Check the footcandle setpoint programmed in
ADJUSTMENT >
Adjust Ch# > Setp#
. If it seems low, enter a higher number.
Retake the light meter readings at the task level. Check program
settings in the
ADJUSTMENT > Daylight Factor
program. Enter
new data into the program as necessary.
Check the photocell light level reading. If it is less than 225fc during
sunny conditions, the range should be set to 3-300fc. Set the
jumper position on the LS-290C photocell and the
Daylight
Factor > Range
setting in the LCD-203 to 3-300fc.
Verify that the photocell is installed correctly. The photocell should
be installed on the room side of curtains or blinds and should view
the daylight that is entering the area.
The lights will not turn on.
Verify that power is present to the ballast and that it has not been
switched off at the breaker or by a wall switch.
Verify line voltage wiring connections to the BT-203.
Make sure the quick connect cable is connected between the
LCD-203 and BT-203.
Verify switch and sensor wiring to the LCD-203.
ERROR
message in the STATUS display instead of
Df# %
.
The programmed
Task FC
for the channel is higher than the
programmed
Photocell
measurement. Go to:
WARRANTY INFORMATION
Watt Stopper/Legrand warranties its products to be free of defects in
materials and workmanship for a period of five (5) years. There are
no obligations or liabilities on the part of Watt Stopper/Legrand for
consequential damages arising out of, or in connection with, the use
or performance of this product or other indirect damages with respect
to loss of property, revenue or profit, or cost of removal, installation or
reinstallation.
GENERAL SET
RUN SEE
NEXT
ADJUSTMENT
BACK SEE
NEXT
Daylight Factor
EXIT NEXT
ADJ
Range 30-3000fc
EXIT NEXT
ADJ
Task FC1 100fc
NEXT
ADJ
Task FC2 20fc
NEXT
ADJ
Task FC3 20fc
NEXT
ADJ
Photocell 080fc
EXIT ADJ
Notice that in this example,
Task FC1
is
set very high at 100fc.
Check the
Photocell
setting. It is very
low at 80fc.
Consider adjusting
Task FC1
to a
lower setting.
Adjust the
Photocell
setting.
Please
Recycle
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10

Legrand LightSaver® LCD-203 Dimming Controller Installation guide

Type
Installation guide

Legrand LightSaver® LCD-203 Dimming Controller can provide automatic dimming for fluorescent and HID lighting, based on daylight contribution. It works with standard 0-10 volt dimming ballasts. It provides three control channels and can control a maximum of fifty ballasts per channel. You can also connect other devices to the LCD-203 to enhance its control capability, such as an occupancy sensor, relay panel, BAS or time clock. An optional wall switch, model LS-4C or LS-5C, allows manual dimming and ON/OFF control.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI