WarmlyYours nSpiration Series Thermostat TempZone Single Custom Product information

Type
Product information
ENSURE THE SYSTEM
IS GROUNDED
HOUSE GROUND
6/2016
MULTIPLE ROLL WIRING DIAGRAM
For 120V & 240V Single Conductor TempZone with
nSpire Touch Wi-Fi (UWG4), nSpire Touch (UDG4),
nHance (UDG), nTrust (UTN4), nJoin (USG)
Installation Support •(800) 875-5285 • www.WarmlyYours.com
ELECTRICAL ROUGH-IN
6/17/99
- 1/2" CONDUIT
(FHE-ROUGH-IN-CND)
IF ONLY ONE ROLL IS USED
- 3/4" CONDUIT IF 2 OR 3
ROLLS ARE USED
1/2" CONDUIT
FOR FLOOR
SENSOR
(FHE-ROUGH-IN-CND)
(IF REQUIRED)
CONDUIT TO
POWER SOURCE
WARMING SYSTEM
4" x 4" DEEP SQUARE BOX
(FHE-ROUGH-IN-BOX)
WITH SINGLE GANG MUD
RING / PLASTER RING
(FHE-ROUGH-IN-MUD)
FOR CONNECTION
TO THERMOSTAT
REAR OF THE BASE
FACEPLATE REMOVAL
LISTED
C US
HOT (240V) or
NEUTRAL (120V)
HOT
FROM
POWER
FLOOR
FRONT OF THE BASE
FLOOR SENSOR
1. MAT HAS NO POLARITY
2. RED OR YELLOW INDICATORS ON COLD LEAD INDICATE
“BEGINNING” OF MAT. WHITE INDICATORS SIGNIFY “END” OF MAT
3. COLD LEAD IS 13” AT “BEGINNING” OF MAT, 26’ AT “END”
OF MAT (20’ & 40’ LEADS ON 3’ WIDE MATS)
4. ENSURE THAT ALL COLD LEADS PRESENT IN THERMOSTAT BOX
ARE THE SAME DIAMETER
5. DO NOT SHORTEN MAT
6. DO NOT CUT THE HEATING WIRE
7. ALWAYS TEST OHMS OF ROLL BEFORE, DURING AND AFTER
INSTALLATION
8. ALWAYS TEST SENSOR AND VERIFY 8-15 K OHM RESISTANCE
9. NEVER INSTALL ELECTRIC FLOOR HEATING UNDER PERMANENT
FIXTURES
10. THE INSTALLATION MUST COMPLY WITH ALL NATIONAL AND LOCAL
ELECTRICAL AND BUILDING CODES, INCLUDING AUTHORITY HAVING
JURISDICTION.
LOAD
1
2
L1(L)
L2(N) LINE
1800W/3600W MAX 15A
120/240VAC
FR
OM
P
O
WER
FL
OOR
LO
AD
1
2
L
1
(
L
)
L
2
(
N
)
LINE
1800W
3600W MAX 15A
120/240VA
C
A B C D
out
in / sensor
r
A
B
C
D
ou
t
in / sensor
r
  • Page 1 1