Acuity Controls nLight ECLYPSE Safety Instructions

Type
Safety Instructions
nLight ECLYPSE Enclosure
912-00023-001
Page 1
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2017 Acuity Brands Lighting, Inc. All rights reserved. 06/21/17
Always read complete installation instructions prior to installation!
SAVE THESE INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
All servicing should be performed by qualified service personnel.
When using electrical equipment, basic safety precautions should always be followed including the
following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
Do not use outdoors.
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Do not use this equipment for other than intended use.
SAVE THESE INSTRUCTIONS.
Remove internal assembly prior to drilling/punching additional or larger holes for conduits, and
remove excess metal shavings and contaminants prior to powering the panel
!
Acuity Controls assumes no responsibility for claims arising out of improper or careless installation or handling of this product. Failure to follow any of
these instructions could void product warranty.
For a complete listing of product Terms and Conditions, please visit www.AcuityControls.com
!
!
nLight ECLYPSE Enclosure
SURFACE MOUNT ENCLOSURE WITH SCREW COVER
TO REMOVE RELAY PANEL COVER:
1) UNFASTEN FOUR PHILLIPS SCREWS AT CORNERS OF COVER
2) REMOVE COVER FROM RIGHT EDGE AND ENGAGEMENT FEATURES ON LEFT SIDE WILL RELEASE
TO INSTALL THE PANEL COVER:
1) HOOK IN THE ENGAGEMENT FEATURES ON THE LEFT FROM THE OUTSIDE
2) FASTEN THE FOUR PHILLIPS SCREWS AT THE CORNERS OF THE COVER
Note: If cover hardware is misplaced, utilize screws and lockwashers with paint-piercing features. Enclosure
utilizes "SEMS" and "KEPS" fasteners with integrated toothed lock washers for paint piercing to ensure proper
bonding of painted enclosure parts.
ENCLOSURE UNTILIZES "SEMS" AND "KEPS" FASTENERS:
INTEGRATED TOOTHED LOCK WASHERS FOR PAINT
PIERCING TO ENSURE PROPER BONDING OF PAINTED
ENCLOSURE PARTS.
912-00023-001
Page 2
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2017 Acuity Brands Lighting, Inc. All rights reserved. 06/21/17
ENCLOSURE MOUNTING INSTRUCTIONS
nLight ECLYPSE Enclosure
12"
12 3/4"
8-Relay
Panel
20 3/4"
16-Relay
Panel
3/4"
1 1/8" 1 1/8"
3/4"
14 1/4"
2 1/8"
TYP
10" TYP
1 5/16"
TYP
14 1/4"
8-Relay
Panel
22 1/4"
16-Relay
Panel
4"
5/8"
3/4"
n9/32" Mounting Holes
4 Places
All knockouts are dual
concentric style for 1/2"
& 3/4" trade size fittings
For Flush Mount Installations:
Alignment markings on all sides for 5/8" & 3/4" thick wallboards.
Align with stud surfaces for proper protrusion of box edge to be
flush finished wall surface. Verify with actual wall material
thicknesses to ensure a proper finished installation.
wall
stud
wall board
align marks with wall stud surface
for flush mount installs
Flush Mount
Install example
Flush
8-RELAY SIZED PANEL SHOWN, BUT APPLIES TO 16-RELAY VERSION
Box Dimensions & Installation Application Notes
TOP
912-00023-001
Page 3
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2017 Acuity Brands Lighting, Inc. All rights reserved. 06/21/17
SURFACE MOUNT ENCLOSURE MOUNTING AND KNOCKOUT DIMENSIONS
nLight ECLYPSE Enclosure
912-00023-001
Page 4
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2017 Acuity Brands Lighting, Inc. All rights reserved. 06/21/17
BOX DIMENSIONS & INSTALLATION APPLICATION NOTES
The NECY enclosure was designed with minimal knockouts to provide installers the freedom to add additional conduit feeds to
better meet specific site conditions without locking them into confined positions or preset trade size fittings.
The dimensions provided are for reference only. Verify all clearances with the actual panel and its components in place prior to
performing any added punch-out work. Note: For Canadian configured devices with step-down transformers (for 347V), added
conduit feed access is more constricted as shown by the added step-down transformer.
WIRING INSTRUCTIONS
DE-ENERGIZE THE PANEL BEFORE MAKING ANY WIRING
CONNECTIONS.
DO NOT DISCARD THESE INSTALLATION INSTRUCTIONS.
PLEASE KEEP FOR FUTURE REFERENCE AND OPERATION
INFORMATION.
NOTE: Make certain that high voltage and low voltage
wiring enters the enclosure separately.
High Voltage wiring should be brought into the upper-
right section of the enclosure, inside the high-voltage
compartment.
Low Voltage wire should enter in the low voltage wiring
areas of the enclosure.
Failure to separate high voltage from low voltage wiring
may cause electrical interference.
HIGH VOLTAGE CONNECTIONS
• Always de energize panel before wiring.
• Use only at the listed voltage per panel specs
• All installation service must be performed by qualified
personnel.
WIRING THE POWER SUPPLY
The Acuity Relay Panel is factory configured with a 120-
277V 50W switching power supply (MVOLT) , and optionally
can be supplied with a 347V to 277V step-down transformer
(CNDV).
• Connect wires to the power supply. You must provide
a dedicated circuit with circuit protection for the power
supply. Earth ground must be connected to the lug labeled
"FOR EQUIPMENT GROUNDING ONLY," located in the high
voltage compartment
• It is recommended that all low voltage wiring be done
with power removed from the system, to protect from
potential shorts during the wiring process.
• All low voltage wiring must be run in separate conduit
from line voltage wiring. DO NOT MIX CLASS 1 AND CLASS 2
CIRCUITS IN THE SAME CONDUIT
Test all low voltage wiring for shorts to AC ground before
connection to the controller.
APPLYING POWER
• Once the wiring is complete, make certain that the
enclosure is clean of any wire clippings and that no
fragments are present.
• Ensure that there are no loose wires or exposed wires that
could short to other wires or components.
• Power up the unit from the circuit breaker.
a) The green power supply input terminal block receives
the line voltage feed wires, 120-277VAC, Neutral,
Ground
nLight ECLYPSE Enclosure
912-00023-001
Page 5
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2017 Acuity Brands Lighting, Inc. All rights reserved. 06/21/17
Knockout Knockout (High Voltage)
Knockout Knockout
nLight Port 1
nLight Port 2
USB 1
USB 2
DIN Rail
DIN Clip
nLight Port 3
(Supports
GFX module)
Ethernet Secondary
Ethernet Primary
Modbus
RS-485
nLIGHT ECLYPSE WIRING DIAGRAM
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5